Plumbing | Splice 10/21/19 | A | 10/21/2019 | SHANEN | SHANEN | Delta 2 revisions revised waste piping plan | | Plumbing | 1247688 |
Out to Review | Splice 10/21/19 | / | 10/21/2019 | BECKYA | BECKYA | | | Out to Review | 1247677 |
Scanned/Finished Bin | Original | / | 3/26/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1170989 |
To Be Scanned Bin | Original | / | 3/25/2019 | | JANE | Location = To Be Scanned Bin by JANE | | To Be Scanned Bin | 1170417 |
Enumeration | Original | A | 3/25/2019 | BRENT | BRENT | | | Enumeration | 1170408 |
Health Dept. | Original | A | 3/25/2019 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | Aparikh | Health Dept. | 1170318 |
Water Division | Original | A | 3/22/2019 | CSUREVIEW | CSUREVIEW | Comments addressed. RDS | rsolberg | Water Division | 1170048 |
Mechanical | Original | A | 3/21/2019 | DALEH | DALEH | | | Mechanical | 1169681 |
CO Springs Fire | Original | A | 3/21/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1169649 |
Hazmat | Original | N | 3/21/2019 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1169648 |
Plumbing | Original | A | 3/13/2019 | SHANEN | SHANEN | OK | | Plumbing | 1167451 |
Electrical | Original | A | 3/13/2019 | BERTHA | BERTHA | | | Electrical | 1167429 |
Mechanical | Original | D | 3/11/2019 | JUSTINC | JUSTINC | Provide refrigeration calculations per 09' IMC 1103.1 Add note as shown on plan (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1166965 |
Construction | Original | A | 3/11/2019 | DANM | DANM | | | Construction | 1166938 |
Out to Review | Original | / | 3/7/2019 | NELIDA | NELIDA | Ralph 719-632-3384 | | Out to Review | 1165865 |
Enumeration | Original | D | 2/4/2019 | BRENT | BRENT | North arrow appears to be incorrect on the site plan, leading to incorrect suite numbering. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1155424 |
Finished Bin | Original | / | 1/3/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1146539 |
Health Dept. | Original | D | 1/3/2019 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions contact Environmental Health at 719-578-3278. | Aparikh | Health Dept. | 1146436 |
Health Dept. | Original | / | 12/31/2018 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1145930 |
Water Division | Original | D | 12/31/2018 | CSUREVIEW | CSUREVIEW | Requires submittal of a Backflow Assembly Plan Review Form to determine if the service backflow prevention meets Standards. Form can be found at: https://www.csu.org/CSUDocuments/backflowdomesticform.pdf Contact Chelsa Shull at 719-668-8755 or Holly Link at 719-668-4733 with any questions.AJ | ajuvera | Water Division | 1145916 |
Waste Water Div | Original | N | 12/31/2018 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | Waste Water Div | 1145915 |
CSU Utilities | Original | / | 12/28/2018 | | CSFIRE | Location = CSU Utilities by CSFIRE | dwithee | CSU Utilities | 1145647 |
Hazmat | Original | D | 12/28/2018 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1145646 |
CO Springs Fire | Original | D | 12/28/2018 | CSFIRE | CSFIRE | REFERENCE CSFD REVIEW REPORT WITHIN PLANS FOR DETAILS | dwithee | CO Springs Fire | 1145645 |
Fire | Original | / | 12/19/2018 | | SDALSING | Location = Fire by SDALSING | | Fire | 1143484 |
CO Springs DRE | Original | A | 12/19/2018 | SDALSING | SDALSING | INT FINISH - USE ALLOWED. NO EXTERIOR WORK OR SIGNAGE APPROVED WITH THIS REVIEW. (see full review) | | CO Springs DRE | 1143483 |
Zoning/Planning | Original | / | 12/17/2018 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1142115 |
Plan Coordinator | Original | / | 12/17/2018 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1142055 |
Plumbing | Original | D | 12/17/2018 | SHANEN | SHANEN | See A pages : Need 18" at pull side of door. Background may change. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1142053 |
Plumbing | Original | / | 12/17/2018 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1141998 |
Plumbing | Original | / | 12/14/2018 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1141527 |
Plan Coordinator | Original | / | 12/13/2018 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1141482 |
Mechanical | Original | D | 12/13/2018 | DALEH | DALEH | refrigeration calcs? co2 tanks? pvc pipe in open plenum space ? see plans for complete red lines no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1141480 |
Mechanical | Original | / | 12/13/2018 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1141412 |
Mechanical | Original | / | 12/6/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1138351 |
Plan Coordinator | Original | / | 12/5/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1137843 |
Electrical | Original | D | 12/5/2018 | SHELBY | SHELBY | Clearly indicate if unit panel is fully or series rated. If series ration provide manufacturers data showing listed components. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1137842 |
Electrical | Original | / | 12/5/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1137831 |
Electrical | Original | / | 11/30/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1136520 |
Plan Coordinator | Original | / | 11/30/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1136511 |
Construction | Original | D | 11/30/2018 | MICHAELA | MICHAELA | Provide 18" at pull side of door Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1136509 |
Construction | Original | / | 11/30/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1136298 |
Construction | Original | / | 11/29/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1135955 |
Plan Coordinator | Original | / | 11/29/2018 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1135742 |
Enumeration | Original | A | 11/29/2018 | BRENT | BRENT | | | Enumeration | 1135741 |
Enumeration | Original | / | 11/29/2018 | BRENT | BRENT | In Current Review by BRENT | | Enumeration | 1135735 |
Floodplain | Original | N | 11/21/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5317116260) | | Floodplain | 1133436 |