Enumeration | Original | A | 12/11/2018 | BRENT | BRENT | Scope of work is support room in basement | | Enumeration | 1140181 |
Electrical | Original | A | 12/11/2018 | SHELBY | SHELBY | | | Electrical | 1140166 |
Mechanical | Original | A | 12/11/2018 | TCRIPPEN | TCRIPPEN | OK | | Mechanical | 1140119 |
Waste Water Div | Original | N | 11/27/2018 | CSUREVIEW | CSUREVIEW | No wastewater work proposed. JPN | jnoble | Waste Water Div | 1134526 |
Water Division | Original | N | 11/27/2018 | CSUREVIEW | CSUREVIEW | No water work proposed. JPN | jnoble | Water Division | 1134525 |
Hazmat | Original | N | 11/27/2018 | CSFIRE | CSFIRE | | fdjah74 | Hazmat | 1134516 |
CO Springs Fire | Original | N | 11/27/2018 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1134512 |
Out to Review | Original | / | 11/27/2018 | RDCUSER | RDCUSER | | | Out to Review | 1134506 |
CO Springs DRE | Original | N | 11/27/2018 | RDCUSER | RDCUSER | INTERIOR REMODEL ONLY, NO CHANGE OF USE (see full review) | | CO Springs DRE | 1134505 |
Construction | Original | N | 11/27/2018 | DANM | DANM | | | Construction | 1134484 |
Electrical | Original | D | 11/27/2018 | BERTHA | BERTHA | 1. Provide conductor size type and quantity - beginning at the utility transformer through the scope of work. 2. Provide panel schedule LPA.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1134471 |
Mechanical | Original | D | 11/27/2018 | TCRIPPEN | TCRIPPEN | show chase detail, need refrg, allowable amounts need return on added supply, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1134465 |
Plumbing | Original | N | 11/27/2018 | TCRIPPEN | TCRIPPEN | no plumbing work issue no permit | | Plumbing | 1134462 |
Out to Review | Original | / | 11/27/2018 | JANE | JANE | walking | | Out to Review | 1134434 |
Floodplain | Original | N | 11/27/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6416218038) | | Floodplain | 1134433 |