Scanned/Finished Bin | Original | / | 1/8/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1147669 |
To Be Scanned Bin | Original | / | 1/7/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1147600 |
Water Division | Original | N | 1/7/2019 | CSUREVIEW | CSUREVIEW | No new water service outside of building. JPN | jnoble | Water Division | 1147581 |
Waste Water Div | Original | N | 1/7/2019 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. JPN | jnoble | Waste Water Div | 1147579 |
CSU Utilities | Original | / | 1/4/2019 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 1146831 |
CO Springs Fire | Original | N | 1/4/2019 | CSFIRE | CSFIRE | | wtaylor | CO Springs Fire | 1146830 |
Hazmat | Original | N | 1/4/2019 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1146829 |
Fire | Original | / | 1/2/2019 | | SDALSING | Location = Fire by SDALSING | | Fire | 1146094 |
CO Springs DRE | Original | N | 1/2/2019 | SDALSING | SDALSING | Interior remodel - no change of use and no exterior work permitted at this time. (see full review) | | CO Springs DRE | 1146093 |
Zoning/Planning | Original | / | 12/26/2018 | | RITA | Location = Zoning/Planning by RITA | | Zoning/Planning | 1144843 |
Electrical | Original | A | 12/26/2018 | SHELBY | SHELBY | | | Electrical | 1144837 |
Plumbing | Original | A | 12/26/2018 | SHANEN | SHANEN | OK see alternate method for drinking fountain | | Plumbing | 1144829 |
Mechanical | Original | A | 12/21/2018 | JUSTINC | JUSTINC | | | Mechanical | 1144487 |
Electrical | Original | D | 12/21/2018 | BERTHA | BERTHA | Provide panel schedule D. Provide panel D on one-line. Homogenize Service Load Summary and load on panels.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1144463 |
Mechanical | Original | D | 11/30/2018 | TCRIPPEN | TCRIPPEN | need to adjust ventilation table (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1136575 |
Plumbing | Original | D | 11/30/2018 | TCRIPPEN | TCRIPPEN | drinking fountain required (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1136573 |
Construction | Original | A | 11/30/2018 | BPHILLIPS | BPHILLIPS | | | Construction | 1136564 |
Enumeration | Original | A | 11/30/2018 | BRENT | BRENT | Splitting Suite 100 into 2 suites, 100 and 110 | | Enumeration | 1136534 |
Out to Review | Original | / | 11/30/2018 | SHELBY | SHELBY | | | Out to Review | 1136504 |
Electrical | Original | A | 11/30/2018 | SHELBY | SHELBY | | | Electrical | 1136503 |
Floodplain | Original | N | 11/30/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6327116024) | | Floodplain | 1136444 |