Construction | Splice 04/25/19 | A | 4/25/2019 | LBENNETT | LBENNETT | Added guard to rooftop around mechanical equipment | | Construction | 1182849 |
Out to Review | Splice 04/25/19 | / | 4/25/2019 | BECKYA | BECKYA | | | Out to Review | 1182840 |
Mechanical | Splice 04/11/19 | A | 4/11/2019 | JUSTINC | JUSTINC | Revised grease duct and RTU schedule | | Mechanical | 1177442 |
Out to Review | Original | / | 2/7/2019 | SCANNING | SCANNING | Stephan | | Out to Review | 1157164 |
Scanned/Finished Bin | Original | / | 2/7/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1157145 |
To Be Scanned Bin | Original | / | 2/7/2019 | | GITA | Location = To Be Scanned Bin by GITA | | To Be Scanned Bin | 1156893 |
Electrical | Original | A | 2/4/2019 | BERTHA | BERTHA | | | Electrical | 1155569 |
Electrical | Original | D | 1/30/2019 | BERTHA | BERTHA | Comply with previous review comments 1 and 3.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1154474 |
Mechanical | Original | A | 1/30/2019 | TCRIPPEN | TCRIPPEN | okay | | Mechanical | 1154466 |
Plumbing | Original | A | 1/30/2019 | SHANEN | SHANEN | OK | | Plumbing | 1154442 |
Hazmat | Original | N | 1/30/2019 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1154424 |
CO Springs Fire | Original | A | 1/30/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1154423 |
Construction | Original | A | 1/30/2019 | MICHAELA | MICHAELA | | | Construction | 1154407 |
Enumeration | Original | A | 1/30/2019 | BRENT | BRENT | Code study form corrected | | Enumeration | 1154393 |
Out to Review | Original | / | 1/17/2019 | GITA | GITA | 7196515642 John | | Out to Review | 1150452 |
Finished Bin | Original | / | 1/15/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1149820 |
CO Springs Fire | Original | D | 1/15/2019 | CSFIRE | CSFIRE | See CSFD Plan Review Comments at: http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp (see full review) | wtaylor | CO Springs Fire | 1149686 |
Hazmat | Original | D | 1/15/2019 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1149685 |
Fire | Original | / | 1/11/2019 | | PTHAYER | Location = Fire by PTHAYER | | Fire | 1149085 |
CO Springs DRE | Original | A | 1/11/2019 | PTHAYER | PTHAYER | PDT per SRD Approved: Interior Finish for a New Restaurant. | | CO Springs DRE | 1149084 |
Health Dept. | Original | A | 1/11/2019 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | Aparikh | Health Dept. | 1149033 |
Zoning/Planning | Original | / | 1/7/2019 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1147597 |
City Engr | Original | N | 1/7/2019 | CSENGINEER | CSENGINEER | Plans routed to RBD. jad | csengineer | City Engr | 1147519 |
Water Division | Original | N | 1/3/2019 | CSUREVIEW | CSUREVIEW | No new water service outside of building. RDS | rsolberg | Water Division | 1146403 |
Waste Water Div | Original | N | 1/3/2019 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. RDS | rsolberg | Waste Water Div | 1146402 |
Gas/Elec. Utils | Original | N | 1/3/2019 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Gas/Elec. Utils | 1146401 |
CSU Contract Admin. | Original | N | 1/3/2019 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved and applicable Development fees/charges paid - master meter configuration. AG | aguerin | CSU Contract Admin. | 1146396 |
CSU Contract Admin. | Original | / | 1/2/2019 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 1146341 |
Plan Coordinator | Original | / | 1/2/2019 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1146333 |
Mechanical | Original | D | 1/2/2019 | TCRIPPEN | TCRIPPEN | # 1 Provide a wall detail showing none combustion able materials or how protecting, #2 call out hoods. Clarify if Fire Wrap is being used if so provide detail and schedule type. Provide allowable amount of refrigeration for walk in cooler and walk in freezer per the 2015 IMC. Provide a note or roof plan showing 10 foot separation between hood exhaust and RTU 1B (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1146331 |
Mechanical | Original | / | 1/2/2019 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Mechanical | 1146229 |
Plumbing | Original | D | 12/31/2018 | SHANEN | SHANEN | Schedule mop sink. Provide soap dispenser detail. All fixtures more than 50 ft. from hot water source will require a pump. Schedule re-circ. pump and provide detail. Show piping for MAU water supply and drain. Each well of 3-comp. sink to discharge independently to waste receptor per section 802.1.1. Mop sink faucet not to be used for chemical dispensing. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1145797 |
Mechanical | Original | / | 12/31/2018 | SHANEN | SHANEN | In Current Review by SHANEN | | Mechanical | 1145775 |
Mechanical | Original | / | 12/31/2018 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1145744 |
Plan Coordinator | Original | / | 12/31/2018 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1145726 |
Electrical | Original | D | 12/31/2018 | SHELBY | SHELBY | 1. Provide manufacturers information listing series rated components. 2. Add the following note to the construction documents " Documentation per 408.3.2 2015 IECC will be provided". 3. Panel A location violates 110.26 NEC. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1145725 |
Electrical | Original | / | 12/28/2018 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1145400 |
Electrical | Original | / | 12/28/2018 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1145381 |
Plan Coordinator | Original | / | 12/28/2018 | | ERIC | Location = Plan Coordinator by ERIC | | Plan Coordinator | 1145376 |
Elevators | Original | N | 12/28/2018 | ERIC | ERIC | No Elevator | | Elevators | 1145375 |
Elevators | Original | / | 12/27/2018 | | SCANNING | Location = Elevators by SCANNING | | Elevators | 1145332 |
Plan Coordinator | Original | / | 12/27/2018 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1145276 |
Construction | Original | D | 12/27/2018 | MICHAELA | MICHAELA | Revise Code Data Hall door to kitchen is not ANSI compliant Why a pass-through to adjacent suite? Walk OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1145275 |
Construction | Original | / | 12/26/2018 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1144857 |
Construction | Original | / | 12/20/2018 | | SCANNING | Location = Construction by SCANNING | | Construction | 1143636 |
Plan Coordinator | Original | / | 12/20/2018 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1143626 |
Enumeration | Original | D | 12/20/2018 | AMY | AMY | LEGAL DESCRIPTION IS REQUIRED TO BE ON THE CODE STUDY FROM. TAX SCHEDULE NUMBER IS INCORRECT. ZIP CODE IS 80923. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1143625 |
Enumeration | Original | / | 12/20/2018 | AMY | AMY | In Current Review by AMY | | Enumeration | 1143601 |
Floodplain | Original | N | 12/19/2018 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5317116260) | | Floodplain | 1143465 |