Scanned/Finished Bin | Original | / | 2/27/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1163062 |
To Be Scanned Bin | Original | / | 2/26/2019 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 1162856 |
Construction | Original | A | 2/26/2019 | DANM | DANM | | | Construction | 1162848 |
Out to Review | Original | / | 2/26/2019 | RITA | RITA | John 719-651-5642 | | Out to Review | 1162579 |
Finished Bin | Original | / | 2/26/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1162526 |
Plan Coordinator | Original | / | 2/25/2019 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1162507 |
Construction | Original | D | 2/25/2019 | DANM | DANM | Allowable area calculations do not accurately reflect 2015 IBC equations - revise & resubmit Walk-through review OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1162506 |
Construction | Original | / | 2/25/2019 | DANM | DANM | In Current Review by DANM | | Construction | 1162471 |
Health Dept. | Original | A | 2/25/2019 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | Aparikh | Health Dept. | 1162090 |
Construction | Original | / | 2/22/2019 | | JANE | Location = Construction by JANE | | Construction | 1161987 |
Resubmittal 1 | Original | / | 2/22/2019 | JANE | JANE | Resubmittal #1 | | Resubmittal 1 | 1161986 |
Mechanical | Original | A | 2/22/2019 | TCRIPPEN | TCRIPPEN | okay | | Mechanical | 1161960 |
Plumbing | Original | A | 2/22/2019 | SHANEN | SHANEN | OK | | Plumbing | 1161894 |
Electrical | Original | A | 2/22/2019 | SHELBY | SHELBY | | | Electrical | 1161888 |
CO Springs Fire | Original | A | 2/11/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1158138 |
Hazmat | Original | N | 2/11/2019 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1158137 |
Electrical | Original | D | 2/11/2019 | BERTHA | BERTHA | Provide model # for breakers in series rated combinations.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1158112 |
Plumbing | Original | A | 2/11/2019 | SHANEN | SHANEN | OK | | Plumbing | 1158101 |
Construction | Original | D | 2/11/2019 | LBENNETT | LBENNETT | Clarify allowable area (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1158082 |
Mechanical | Original | D | 2/11/2019 | JUSTINC | JUSTINC | Mechanical sheet backgrounds must match (A) sheets. CO2 tanks appear to be located in the storage room over the allowable amounts. Verify how ventilating.
WALK OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1158073 |
Enumeration | Original | A | 2/7/2019 | BRENT | BRENT | Suite number correct | | Enumeration | 1156911 |
Out to Review | Original | / | 2/7/2019 | GITA | GITA | John | | Out to Review | 1156900 |
Finished Bin | Original | / | 2/5/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1156148 |
Out to Review | Original | / | 2/5/2019 | RITA | RITA | John 719-651-5642 | | Out to Review | 1156005 |
Health Dept. | Original | D | 2/5/2019 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions contact Environmental Health at 719-578-3278. | abrannon | Health Dept. | 1155952 |
Health Dept. | Original | / | 2/4/2019 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1155797 |
Water Division | Original | N | 2/4/2019 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | Water Division | 1155721 |
Waste Water Div | Original | N | 2/4/2019 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | Waste Water Div | 1155719 |
CO Springs Fire | Original | D | 2/4/2019 | CSFIRE | CSFIRE | See Disapproval Comments at: http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp (see full review) | wtaylor | CO Springs Fire | 1155439 |
Hazmat | Original | D | 2/4/2019 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1155438 |
Enumeration | Original | D | 2/4/2019 | BRENT | BRENT | verify suite number location (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1155425 |
Fire | Original | / | 2/1/2019 | | SDALSING | Location = Fire by SDALSING | | Fire | 1155271 |
CO Springs DRE | Original | A | 2/1/2019 | SDALSING | SDALSING | INT FINISH - USE ALLOWED. NO EXTERIOR WORK OR SIGNAGE APPROVED WITH THIS REVIEW. BREWERY IS LESS THAN 50% OF FOOTPRINT AREA. (see full review) | | CO Springs DRE | 1155270 |
Zoning/Planning | Original | / | 1/28/2019 | | CSUAPPSPRM | Location = Zoning/Planning by CSUAPPSPRM | mkluke | Zoning/Planning | 1153312 |
CSU Contract Admin. | Original | N | 1/28/2019 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved and applicable Development fees/charges paid - master meter configuration. MKL | mkluke | CSU Contract Admin. | 1153311 |
CSU Contract Admin. | Original | / | 1/25/2019 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 1153100 |
Plan Coordinator | Original | / | 1/25/2019 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1152958 |
Mechanical | Original | A | 1/25/2019 | JUSTINC | JUSTINC | | | Mechanical | 1152957 |
Mechanical | Original | / | 1/25/2019 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1152888 |
Mechanical | Original | / | 1/22/2019 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1151579 |
Plan Coordinator | Original | / | 1/22/2019 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1151460 |
Electrical | Original | D | 1/22/2019 | BERTHA | BERTHA | 1. Provide revised one-line indicating relocated Panel B. 2. Provide fault current calculations for all new service equipment and sub panels to include re-fed existing gear.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1151459 |
Electrical | Original | / | 1/18/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1150983 |
Electrical | Original | / | 1/15/2019 | | SHANEN | Location = Electrical by SHANEN | | Electrical | 1149631 |
Plumbing | Original | D | 1/15/2019 | SHANEN | SHANEN | Correct water pipe size analysis data for this suite. Show EWC as dual height on page P2. Schedule required re-circ. pump. Provide water heater platform detail. Hot water lines to fixtures exceeding 50' from hot water source require a pump. Show waste piping for FS-1 by walk in cooler. Food establishment is checked yes on code study. Clarify.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1149630 |
Plumbing | Original | / | 1/15/2019 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1149597 |
Electrical | Original | / | 1/15/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Electrical | 1149596 |
Electrical | Original | / | 1/14/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1149382 |
Plan Coordinator | Original | / | 1/14/2019 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1149359 |
Construction | Original | D | 1/14/2019 | DANM | DANM | Incorrect equation used from 2009 IBC for allowable area increase - use equation found in 2015 IBC 506.2.1 Walk-through review OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1149358 |
Construction | Original | / | 1/14/2019 | DANM | DANM | In Current Review by DANM | | Construction | 1149269 |
Construction | Original | / | 1/11/2019 | | SCANNING | Location = Construction by SCANNING | | Construction | 1149225 |
Plan Coordinator | Original | / | 1/11/2019 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1149218 |
Enumeration | Original | A | 1/11/2019 | BRENT | BRENT | | | Enumeration | 1149217 |
Enumeration | Original | / | 1/11/2019 | BRENT | BRENT | In Current Review by BRENT | | Enumeration | 1149202 |
Floodplain | Original | N | 1/11/2019 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5317116260) | | Floodplain | 1148919 |