Mechanical | Splice 08/13/19 | A | 8/13/2019 | DALEH | DALEH | adding press regs | | Mechanical | 1223449 |
Mechanical | Splice 07/11/19 | A | 7/11/2019 | SHANEN | SHANEN | Revised to show gas regs | | Mechanical | 1212034 |
Health Dept. | Original | A | 5/3/2019 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | abrannon | Health Dept. | 1186452 |
Health Dept. | Original | / | 5/3/2019 | HEALTHDEPT | HEALTHDEPT | | abrannon | Health Dept. | 1186451 |
Health Dept. | Original | D | 5/2/2019 | HEALTHDEPT | HEALTHDEPT | Health department plan review is in process and not yet approved. For questions please contact 719-578-3199 option 3. | abrannon | Health Dept. | 1185948 |
Construction | Original | A | 5/1/2019 | MICHAELA | MICHAELA | | | Construction | 1185431 |
Plumbing | Original | A | 5/1/2019 | SHANEN | SHANEN | OK | | Plumbing | 1185376 |
Electronic Plan | Original | / | 5/1/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1185358 |
Resubmittal 3 | Original | / | 5/1/2019 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1185239 |
CO Springs DRE | Original | A | 4/30/2019 | SDALSING | SDALSING | APPROVED:
USE ALLOWED - NO EXTERIOR WORK PERMITTED AT THIS TIME (see full review) | | CO Springs DRE | 1184912 |
Zoning/Planning | Original | / | 4/30/2019 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1184911 |
Electrical | Original | A | 4/30/2019 | BERTHA | BERTHA | | | Electrical | 1184838 |
Plumbing | Original | D | 4/30/2019 | SHANEN | SHANEN | Gas piping related items to be on "M" pages per PPRBD web site. CSU variance letter for indoor grease interceptor received but location not shown on plans. Schedule grease interceptor if to be installed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1184574 |
Health Dept. | Original | D | 4/30/2019 | HEALTHDEPT | HEALTHDEPT | Health department plan review is in process and not yet approved. For questions please contact 719-578-3199 option 3. | abrannon | Health Dept. | 1184525 |
Electronic Plan | Original | / | 4/29/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1184486 |
Waste Water Div | Original | A | 4/29/2019 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | Waste Water Div | 1184474 |
Construction | Original | A | 4/29/2019 | MICHAELA | MICHAELA | | | Construction | 1184431 |
Resubmittal 2 | Original | / | 4/29/2019 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1184313 |
Waste Water Div | Original | D | 4/12/2019 | CSUREVIEW | CSUREVIEW | Provide copy of variance letter with plan set. JPN | jnoble | Waste Water Div | 1177977 |
Waste Water Div | Original | / | 4/10/2019 | CSUREVIEW | CSUREVIEW | | kschelhaas | Waste Water Div | 1176869 |
CO Springs Fire | Original | A | 4/8/2019 | CSFIRE | CSFIRE | http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp | rpeterson | CO Springs Fire | 1175516 |
CO Springs DRE | Original | A | 4/5/2019 | SDALSING | SDALSING | INTERIOR FINISH - NO EXTERIOR WORK PERMITTED AT THIS TIME.
USE ALLOWED - PARKING IS MET (see full review) | | CO Springs DRE | 1175250 |
Health Dept. | Original | D | 4/2/2019 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions contact Environmental Health at 719-578-3278. | abrannon | Health Dept. | 1173585 |
Waste Water Div | Original | D | 4/1/2019 | CSUREVIEW | CSUREVIEW | Provide copy of variance letter with plan set. MLW | mlwilliams | Waste Water Div | 1173341 |
Electrical | Original | D | 4/1/2019 | BERTHA | BERTHA | Service depicted incorrectly.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1173244 |
Electronic Plan | Original | / | 4/1/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1173177 |
Zoning/Planning | Original | / | 4/1/2019 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1173168 |
Mechanical | Original | A | 4/1/2019 | TCRIPPEN | TCRIPPEN | okay | | Mechanical | 1173087 |
Plumbing | Original | D | 4/1/2019 | SHANEN | SHANEN | CSU variance letter required for indoor grease trap. Rest Ok (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1173038 |
Electronic Plan | Original | / | 4/1/2019 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1173022 |
Construction | Original | A | 4/1/2019 | SHELLEY | SHELLEY | No apparent changes. Please do not resubmit any documents in which changes do not occur. | | Construction | 1173008 |
Enumeration | Original | A | 4/1/2019 | BRENT | BRENT | | | Enumeration | 1172949 |
Electronic Plan | Original | / | 4/1/2019 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1172948 |
Resubmittal 1 | Original | / | 4/1/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1172938 |
Electrical | Original | D | 3/1/2019 | BERTHA | BERTHA | 1. Provide conduit/wire size, type and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work - existing service lateral 2. Provide service load summary 3. Provide 2015 IECC. 4. Provide compliance with 408.3.2 - 2015 IECC - add note - "Documentation per 408.3.2 - 2015 IECC will be provided."
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1164203 |
CO Springs Fire | Original | D | 2/27/2019 | CSFIRE | CSFIRE | Reference CSFD review report online for details: http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp | dwithee | CO Springs Fire | 1163340 |
Hazmat | Original | N | 2/27/2019 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1163338 |
Water Division | Original | A | 2/25/2019 | CSUREVIEW | CSUREVIEW | Backflow okay. MLW | mlwilliams | Water Division | 1162443 |
Waste Water Div | Original | D | 2/25/2019 | CSUREVIEW | CSUREVIEW | Grease interceptors must be located within 50' of nearest kitchen plumbing fixture. Additional grease interceptor (new approved Utility Service Plan) is required on this site. Please call Carolyn Winfrey at 719.668.4506 to discuss regulations pertaining to FOG treatment for food establishments. MLW | mlwilliams | Waste Water Div | 1162440 |
CO Springs DRE | Original | A | 2/25/2019 | SDALSING | SDALSING | INTERIOR FINISH - NO EXTERIOR WORK PERMITTED AT THIS TIME.
USE ALLOWED - PARKING IS MET (see full review) | | CO Springs DRE | 1162324 |
Health Dept. | Original | D | 2/25/2019 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions contact Environmental Health at 719-578-3278. | Aparikh | Health Dept. | 1162183 |
Mechanical | Original | D | 2/25/2019 | TCRIPPEN | TCRIPPEN | Provide the allowable amounts of refrigeration and type for the walk in freezers per table 1103.1 of the 2015 gas pipe and related items to be on the M pages per our web site. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1162075 |
Zoning/Planning | Original | / | 2/25/2019 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1162038 |
Plumbing | Original | D | 2/25/2019 | SHANEN | SHANEN | All gas piping related items to be on "M" pages per PPRBD web site. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1162024 |
Construction | Original | A | 2/22/2019 | MICHAELA | MICHAELA | | | Construction | 1161989 |
Electronic Plan | Original | / | 2/22/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1161898 |
Enumeration | Original | D | 2/19/2019 | BRENT | BRENT | Include a site plan showing all tenant spaces in the building with addressing and area of work highlighted. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1160206 |
Electronic Plan | Original | / | 2/19/2019 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1160195 |
Floodplain | Original | N | 2/14/2019 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5318220018) | | Floodplain | 1159406 |