Electrical | Splice 04/28/20 | A | 4/30/2020 | BERTHA | BERTHA | Added Panel S3-1 and WRANGLER. Revised power and lighting. Revised schedules. | | Electrical | 1316353 |
Electronic Plan | Splice 04/28/20 | / | 4/30/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1316344 |
Resubmittal 1 | Splice 04/28/20 | / | 4/30/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1316316 |
Electrical | Splice 04/28/20 | D | 4/28/2020 | BERTHA | BERTHA | Comply 250.122 - feeder 7
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1315130 |
Electronic Plan | Splice 04/28/20 | / | 4/28/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1315109 |
Plumbing | Splice 04/28/20 | A | 4/28/2020 | TCRIPPEN | TCRIPPEN | change floor sink to floor drain, add service sink, Add line behind fireplace | | Plumbing | 1315072 |
Electronic Plan | Splice 04/28/20 | / | 4/28/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1315047 |
City Engr | Splice 03/05/20 | A | 3/19/2020 | CSENGINEER | CSENGINEER | | csengineer | City Engr | 1299486 |
City Engr (SERT) | Splice 03/05/20 | / | 3/11/2020 | | AOSBORNE | Location = City Engr (SERT) by AOSBORNE | | City Engr (SERT) | 1296961 |
Out to Review | Splice 03/05/20 | / | 3/11/2020 | BEND | BEND | | | Out to Review | 1296950 |
Electrical | Splice 03/05/20 | A | 3/11/2020 | BEND | BEND | Revised one line, schedules, lighting and power throughout. | | Electrical | 1296949 |
Resubmittal 1 | Splice 03/05/20 | / | 3/11/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1296881 |
CO Springs Fire | Splice 03/05/20 | A | 3/11/2020 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1296868 |
Fire | Splice 03/05/20 | / | 3/6/2020 | | JANE | Location = Fire by JANE | | Fire | 1294788 |
Electrical | Splice 03/05/20 | D | 3/6/2020 | JANE | JANE | SLE (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1294782 |
CO Springs DRE | Splice 03/05/20 | A | 3/6/2020 | JANE | JANE | Per AMO | | CO Springs DRE | 1294781 |
Zoning/Planning | Splice 03/05/20 | / | 3/5/2020 | | RDCUSER | Location = Zoning/Planning by RDCUSER | | Zoning/Planning | 1294477 |
Construction | Splice 03/05/20 | N | 3/5/2020 | BPHILLIPS | BPHILLIPS | | | Construction | 1294317 |
Mechanical | Splice 03/05/20 | A | 3/5/2020 | TCRIPPEN | TCRIPPEN | okay relocate exhaust fans | | Mechanical | 1294308 |
Out to Review | Splice 03/05/20 | / | 3/5/2020 | BECKYA | BECKYA | | | Out to Review | 1294293 |
Mechanical | Splice 01/16/20 | A | 1/16/2020 | TCRIPPEN | TCRIPPEN | new splice showing new gas line up,, t-stat locations redesign isometric, revise gas system added schedule, showing kitchen equipment | | Mechanical | 1276689 |
Out to Review | Splice 01/16/20 | / | 1/16/2020 | BECKYA | BECKYA | | | Out to Review | 1276656 |
Mechanical | Splice 12/02/19 | A | 12/2/2019 | DALEH | DALEH | delta 5 clouds | | Mechanical | 1262225 |
Out to Review | Splice 12/02/19 | / | 12/2/2019 | BECKYA | BECKYA | | | Out to Review | 1262162 |
Mechanical | Splice 11/15/19 | A | 11/15/2019 | DALEH | DALEH | Revised gas and other minor changes | | Mechanical | 1257668 |
Plumbing | Splice 11/15/19 | A | 11/15/2019 | SHANEN | SHANEN | Delta 4 revisions 3/4" service line to future smoke house | | Plumbing | 1257648 |
Out to Review | Splice 11/15/19 | / | 11/15/2019 | RITA | RITA | Dan walking | | Out to Review | 1257620 |
Mechanical | Splice 10/02/19 | A | 10/2/2019 | JUSTINC | JUSTINC | Revised piping | | Mechanical | 1241715 |
Plumbing | Splice 08/19/19 | A | 8/21/2019 | SHANEN | SHANEN | Delta 3 revisions P1.00 adjusted fixture schedule, P2.01 changed to trough lavs and added drinking fountains and piping | | Plumbing | 1226447 |
Construction | Splice 08/19/19 | A | 8/21/2019 | BPHILLIPS | BPHILLIPS | Replaced lavs in restrooms with troughs. | | Construction | 1226434 |
Resubmittal 1 | Splice 08/19/19 | / | 8/21/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1226408 |
Plumbing | Splice 08/19/19 | D | 8/19/2019 | SHANEN | SHANEN | Provide matching backgrounds. Provide accessibility detail for trough lavatories. Trough lavs shall comply with section 402. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1225477 |
Out to Review | Splice 08/19/19 | / | 8/19/2019 | BECKYA | BECKYA | | | Out to Review | 1225462 |
Construction | Splice 07/26/19 | A | 7/26/2019 | BPHILLIPS | BPHILLIPS | | | Construction | 1217357 |
Construction | Splice 07/26/19 | A | 7/26/2019 | BPHILLIPS | BPHILLIPS | Revised top of footing elevation. | | Construction | 1217353 |
Out to Review | Splice 07/26/19 | / | 7/26/2019 | BECKYA | BECKYA | | | Out to Review | 1217345 |
Scanned/Finished Bin | Original | / | 7/19/2019 | AMY | AMY | In Current Review by AMY | | Scanned/Finished Bin | 1214934 |
Scanned/Finished Bin | Original | / | 6/5/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1198883 |
To Be Scanned Bin | Original | / | 6/5/2019 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 1198623 |
Health Dept. | Original | A | 6/4/2019 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | taylornaiman | Health Dept. | 1198417 |
Hazmat | Original | N | 6/4/2019 | CSFIRE | CSFIRE | Not more than 100# of CO2 on system at any one time. No issues. Plans given back to contractor. (see full review) | smitty91 | Hazmat | 1198022 |
City Engr | Original | A | 5/31/2019 | CSENGINEER | CSENGINEER | Walk thru. jad | csengineer | City Engr | 1196898 |
Gas/Elec. Utils | Original | A | 5/30/2019 | CSUREVIEW | CSUREVIEW | Comments addressed per Bill Davis. KDS | kschelhaas | Gas/Elec. Utils | 1196303 |
CSU Contract Admin. | Original | A | 5/29/2019 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved & all applicable Development fees/charges paid. AG | aguerin | CSU Contract Admin. | 1196081 |
Plumbing | Original | A | 5/21/2019 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1192938 |
Mechanical | Original | A | 5/21/2019 | DALEH | DALEH | | | Mechanical | 1192908 |
Out to Review | Original | / | 5/20/2019 | NELIDA | NELIDA | Micah 719-306-3131 | | Out to Review | 1192544 |
Finished Bin | Original | / | 5/20/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1192521 |
Health Dept. | Original | D | 5/20/2019 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions contact Environmental Health at 719-578-3199 option 3. | taylornaiman | Health Dept. | 1192419 |
Health Dept. | Original | / | 5/17/2019 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1192149 |
City Engr | Original | D | 5/17/2019 | CSENGINEER | CSENGINEER | See previous comment - Include a copy of the approved Grading & Erosion Control Plan by the Water Resources Engineering Division in the building permit set. Plan set routed to RBD. jad | csengineer | City Engr | 1192136 |
City Engr | Original | / | 5/13/2019 | | CSUAPPSPRM | Location = City Engr by CSUAPPSPRM | lmpope | City Engr | 1190150 |
CSU Contract Admin. | Original | D | 5/13/2019 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved. Requires payment of development charges/fees. LMP | lmpope | CSU Contract Admin. | 1190148 |
Gas/Elec. Utils | Original | D | 5/13/2019 | CSUREVIEW | CSUREVIEW | Need documentation of easements for gas and electric. Contact Bill Davis at 719-668-8254. KDS | kschelhaas | Gas/Elec. Utils | 1190091 |
Water Division | Original | A | 5/13/2019 | CSUREVIEW | CSUREVIEW | Comments addressed. KDS | kschelhaas | Water Division | 1190085 |
Waste Water Div | Original | A | 5/13/2019 | CSUREVIEW | CSUREVIEW | Comments addressed. KDS | kschelhaas | Waste Water Div | 1190084 |
CSU Utilities | Original | / | 5/13/2019 | | SCANNING | Location = CSU Utilities by SCANNING | | CSU Utilities | 1190079 |
Water Division | Original | D | 5/10/2019 | CSUREVIEW | CSUREVIEW | Approved Development Plan, Utility Service Plan (USP), and CSU-approved Construction Drawings must be attached to the permit set prior to our approval on Water Division and Wastewater Div. Contact Utilities Development Services at 719-668-8267 with any questions. RDS | rsolberg | Water Division | 1189276 |
Waste Water Div | Original | D | 5/10/2019 | CSUREVIEW | CSUREVIEW | Approved Development Plan, Utility Service Plan (USP), and CSU-approved Construction Drawings must be attached to the permit set prior to our approval on Water Division and Wastewater Div. Contact Utilities Development Services at 719-668-8267 with any questions. RDS | rsolberg | Waste Water Div | 1189275 |
Gas/Elec. Utils | Original | D | 5/10/2019 | CSUREVIEW | CSUREVIEW | Approved Development Plan, Utility Service Plan (USP), and CSU-approved Construction Drawings must be attached to the permit set prior to our approval on Water Division and Wastewater Div. Contact Utilities Development Services at 719-668-8267 with any questions. RDS | rsolberg | Gas/Elec. Utils | 1189274 |
Hazmat | Original | D | 5/10/2019 | CSFIRE | CSFIRE | Plans disapproved. Please read disapproval comments. Plans forwarded to utilities. (see full review) | smanning | Hazmat | 1189239 |
CO Springs Fire | Original | A | 5/9/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1189152 |
Hazmat | Original | / | 5/9/2019 | | CSFIRE | Location = Hazmat by CSFIRE | rpeterson | Hazmat | 1189151 |
Fire | Original | / | 5/8/2019 | | SCANNING | Location = Fire by SCANNING | | Fire | 1188156 |
Plan Coordinator | Original | / | 5/8/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1188152 |
Plumbing | Original | D | 5/8/2019 | SHANEN | SHANEN | P2.01 uncovered exterior fixtures (TD & FD) cannot discharge to sanitary sewer. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1188151 |
Plumbing | Original | / | 5/7/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1187960 |
Plumbing | Original | / | 5/7/2019 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1187954 |
Plan Coordinator | Original | / | 5/7/2019 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1187922 |
Mechanical | Original | D | 5/7/2019 | JUSTINC | JUSTINC | MECHANICAL REVIEW COMMENTS HAVE NOT BEEN ADDRESSED FROM LAST REVIEW
Hood sheets are to be located with (M) sheets. These are part of the mechanical scope and are to be with the mechanical drawings. (TYP.) for ALL PPRBD submittals.
(M) sheets are to indicate roof access. Either provide note on sheet indicating location or show on floor plan.
Remove extra layers from floor plan for clarity
Provide note indicating wall backing hoods to be constructed of non-combustible construction
REVIEW STOPPED WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1187921 |
Mechanical | Original | / | 5/7/2019 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1187777 |
Mechanical | Original | / | 5/6/2019 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1187305 |
Plan Coordinator | Original | / | 5/6/2019 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1187253 |
Electrical | Original | A | 5/6/2019 | SHELBY | SHELBY | | | Electrical | 1187252 |
Electrical | Original | / | 5/6/2019 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1187214 |
Electrical | Original | / | 5/6/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1186989 |
Plan Coordinator | Original | / | 5/6/2019 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1186950 |
Construction | Original | A | 5/6/2019 | BPHILLIPS | BPHILLIPS | | | Construction | 1186949 |
Construction | Original | / | 5/3/2019 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1186693 |
Construction | Original | / | 5/3/2019 | | NELIDA | Location = Construction by NELIDA | | Construction | 1186691 |
Resubmittal 1 | Original | / | 5/3/2019 | NELIDA | NELIDA | Resubmittal #1 5/3/19 | | Resubmittal 1 | 1186662 |
Out to Review | Original | / | 4/23/2019 | GITA | GITA | Ralph 7196323384 | | Out to Review | 1181801 |
Finished Bin | Original | / | 4/23/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1181687 |
Health Dept. | Original | D | 4/23/2019 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions contact Environmental Health at 719-578-3199 option 3. | taylornaiman | Health Dept. | 1181615 |
Health Dept. | Original | / | 4/22/2019 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1181501 |
City Engr | Original | D | 4/22/2019 | CSENGINEER | CSENGINEER | Include a copy of the approved Grading & Erosion Control Plan approved by the Water Resources Engineering Division in the building permit set. Plan set route to RBD. pvm | csengineer | City Engr | 1181403 |
CO Springs Fire | Original | D | 4/22/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1181137 |
Hazmat | Original | D | 4/22/2019 | CSFIRE | CSFIRE | Provide CO2 Questionnaire. | rpeterson | Hazmat | 1181136 |
City Engr | Original | / | 4/22/2019 | | CSFIRE | Location = City Engr by CSFIRE | rpeterson | City Engr | 1181135 |
Fire | Original | / | 4/19/2019 | | MSCHULTZ | Location = Fire by MSCHULTZ | | Fire | 1180997 |
CO Springs DRE | Original | A | 4/19/2019 | MSCHULTZ | MSCHULTZ | Plan set matches stamped approved DP; this reviewer advises that owner to re-evaluate ADA parking and accessible route from the parking to the building as there may be issues if the surface type is suitable for travel. (see full review) | | CO Springs DRE | 1180996 |
Zoning/Planning | Original | / | 4/18/2019 | | CSUAPPSPRM | Location = Zoning/Planning by CSUAPPSPRM | cquinn | Zoning/Planning | 1180332 |
CSU Contract Admin. | Original | D | 4/18/2019 | CSUAPPSPRM | CSUAPPSPRM | Requires submittal and approval of Commercial Water Meter Sizing Form and payment of development charges/fees. LMP
Form can be found at https://www.csu.org/Pages/development-files-forms.aspx | cquinn | CSU Contract Admin. | 1180331 |
Gas/Elec. Utils | Original | D | 4/18/2019 | CSUREVIEW | CSUREVIEW | The gas regulator vent must be at least 3ft away from any electric meter socket, ct cabinet (not including cables in riser pipe or gutter) and openings like windows, doors, and garage doors. Show and label gas and electric meter locations on the elevations. KDS | kschelhaas | Gas/Elec. Utils | 1180265 |
Water Division | Original | D | 4/18/2019 | CSUREVIEW | CSUREVIEW | Water Mainline Construction Drawings must be approved by Utilities Development Services and included in the plan set. KDS | kschelhaas | Water Division | 1180262 |
Waste Water Div | Original | D | 4/18/2019 | CSUREVIEW | CSUREVIEW | Wastewater Mainline Construction Drawings must be approved by Utilities Development Services and included in the plan set. KDS | kschelhaas | Waste Water Div | 1180261 |
CSU Contract Admin. | Original | / | 4/17/2019 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 1179962 |
Plan Coordinator | Original | / | 4/17/2019 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1179942 |
Mechanical | Original | D | 4/17/2019 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Remove extra layers from floor plan drawing for clarity. Add note to sheet M2.02 to provide thermal barrier per 2015 IMC 1209.5 Provide detail showing how roof access will comply with 2015 IMC 304.11 and 306.5.1 Provide kitchen makeup air interlock schedule. Cannot be "By others" Relocate ALL ACCUREX sheets to (M) sheets
NO WALK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1179941 |
Mechanical | Original | / | 4/17/2019 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1179925 |
Mechanical | Original | / | 4/15/2019 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1178400 |
Plan Coordinator | Original | / | 4/15/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1178320 |
Plumbing | Original | D | 4/15/2019 | SHANEN | SHANEN | See construction reviewer notes regarding occupancy load. Toilet rooms shall not open directly into a room used for the preparation of food for service to the public per section 403.3.2. Exterior uncovered trench and floor drains to not discharge into sanitary sewer. All food prep and kitchen area drains (floor drains, floor sinks, hand sinks, food prep sinks, and any fixtures that allow fats, oils, and grease to be discharged) shall discharge through grease interceptor. Where a food waste disposer connects to a grease interceptor a solids interceptor is required per section 1003.3.2. Combination waste and vent shall not receive the discharge of a food waste disposer per section 915.1. Provide detail for scupper, gutter and downspout sizing include square footage and/or GPM served by each component. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1178319 |
Plumbing | Original | / | 4/11/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1177521 |
Plumbing | Original | / | 4/11/2019 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1177366 |
Mechanical | Original | / | 4/10/2019 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1176615 |
Plan Coordinator | Original | / | 4/10/2019 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1176577 |
Electrical | Original | D | 4/10/2019 | SHELBY | SHELBY | 1. 800 amp feeder for MDP requires an equipment ground. 2. Indicate SCA and SCCR at refrigeration equipment. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1176574 |
Electrical | Original | / | 4/10/2019 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1176535 |
Electrical | Original | / | 4/9/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1176358 |
Plan Coordinator | Original | / | 4/9/2019 | | ERIC | Location = Plan Coordinator by ERIC | | Plan Coordinator | 1176313 |
Elevators | Original | N | 4/9/2019 | ERIC | ERIC | No Elevator or VPL shown | | Elevators | 1176310 |
Elevators | Original | / | 4/9/2019 | | SCANNING | Location = Elevators by SCANNING | | Elevators | 1176268 |
Plan Coordinator | Original | / | 4/9/2019 | | BPHILLIPS | Location = Plan Coordinator by BPHILLIPS | | Plan Coordinator | 1176157 |
Construction | Original | D | 4/9/2019 | BPHILLIPS | BPHILLIPS | Provide ambulatory toilet stalls in both restrooms, in addition to the provided accessible stalls. How are you complying with IECC C402.5.7 regarding vestibules? Relabel stage as 'platform.' Clarify occupant load/ use of porch space per note on plan. Remove Comcheck from mechanical submittal and relocate in architectural pages or as its own 8.5 x 11 document. No walk.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1176153 |
Construction | Original | / | 4/8/2019 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Construction | 1175671 |
Construction | Original | / | 4/3/2019 | | SCANNING | Location = Construction by SCANNING | | Construction | 1174314 |
Enumeration | Original | A | 4/3/2019 | BRENT | BRENT | | | Enumeration | 1174293 |
Plan Coordinator | Original | / | 4/3/2019 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1174292 |
Floodplain | Original | N | 4/3/2019 | BRENT | BRENT | | | Floodplain | 1174291 |
Enumeration | Original | / | 4/3/2019 | BRENT | BRENT | In Current Review by BRENT | | Enumeration | 1174282 |
Enumeration | Original | / | 3/28/2019 | | RITA | Location = Enumeration by RITA | | Enumeration | 1171999 |
- Not Set - | Original | / | 3/28/2019 | | RITA | Location = - Not Set - by RITA. Spec book in the bin | | - Not Set - | 1171979 |
Floodplain | Original | / | 3/28/2019 | RBD GIS | RBD GIS | Autogenerated Review: Floodplain status unknown. (Parcel: 7300000059) | | Floodplain | 1171970 |