Construction | Splice 08/26/20 | A | 8/27/2020 | LBENNETT | LBENNETT | Removed 2-hour fire barrier (not required) | | Construction | 1373657 |
Electronic Plan | Splice 08/26/20 | / | 8/27/2020 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1373646 |
Mechanical | Splice 03/05/20 | A | 3/5/2020 | TCRIPPEN | TCRIPPEN | new splice revised gas piping | | Mechanical | 1294327 |
Out to Review | Splice 03/05/20 | / | 3/5/2020 | BECKYA | BECKYA | | | Out to Review | 1294303 |
CO Springs Fire | Splice 02/05/20 | A | 2/11/2020 | GITA | GITA | approved per splice label - 2-11-20 | | CO Springs Fire | 1285136 |
Construction | Splice 02/05/20 | A | 2/11/2020 | LBENNETT | LBENNETT | New 2-hr fire barrier between utility room and Pho restaurant | | Construction | 1285072 |
Out to Review | Splice 02/05/20 | / | 2/5/2020 | JANE | JANE | Walking | | Out to Review | 1283304 |
Mechanical | Splice 01/22/20 | A | 1/22/2020 | TCRIPPEN | TCRIPPEN | Revised grease duct sizes and changed from square to round. Adjusted velocity | | Mechanical | 1278476 |
Out to Review | Splice 01/22/20 | / | 1/22/2020 | BECKYA | BECKYA | | | Out to Review | 1278472 |
Electrical | Splice 01/06/20 | A | 1/6/2020 | SHELBY | SHELBY | | | Electrical | 1272763 |
Out to Review | Splice 01/06/20 | / | 1/6/2020 | BECKYA | BECKYA | | | Out to Review | 1272719 |
Mechanical | Splice 12/09/19 | A | 12/9/2019 | TCRIPPEN | TCRIPPEN | new splice revised gas piping | | Mechanical | 1265203 |
Out to Review | Splice 12/09/19 | / | 12/9/2019 | BECKYA | BECKYA | | | Out to Review | 1265192 |
Electrical | Original | A | 6/19/2019 | BERTHA | BERTHA | | | Electrical | 1204272 |
Electronic Plan | Original | / | 6/19/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1204267 |
Mechanical | Original | A | 6/19/2019 | DALEH | DALEH | | | Mechanical | 1204180 |
Resubmittal 4 | Original | / | 6/19/2019 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1204110 |
CO Springs DRE | Original | A | 6/17/2019 | SDALSING | SDALSING | INTERIOR FINISH - NO EXTERIOR WORK PERMITTED AT THIS TIME. USE ALLOWED - PARKING IS MET (see full review) | | CO Springs DRE | 1202999 |
Electrical | Original | A | 6/14/2019 | BERTHA | BERTHA | Re-approved again. No new sheets provided. | | Electrical | 1202850 |
Electronic Plan | Original | / | 6/14/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1202846 |
Mechanical | Original | D | 6/14/2019 | DALEH | DALEH | still have not responded to comments dated back to 5/16 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1202725 |
Zoning/Planning | Original | / | 6/14/2019 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1202457 |
Construction | Original | A | 6/12/2019 | DANM | DANM | Minor revisions to ceiling plan | | Construction | 1201582 |
Electronic Plan | Original | / | 6/12/2019 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1201570 |
Enumeration | Original | A | 6/12/2019 | AMY | AMY | | | Enumeration | 1201091 |
Electronic Plan | Original | / | 6/12/2019 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1201087 |
Resubmittal 3 | Original | / | 6/10/2019 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1200238 |
CO Springs Fire | Original | A | 6/5/2019 | CSFIRE | CSFIRE | REFERENCE CSFD REVIEW REPORT FOR INSPECTIONS RELATED INFORMATION - http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp | dwithee | CO Springs Fire | 1198803 |
Hazmat | Original | N | 6/5/2019 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1198788 |
Mechanical | Original | D | 5/29/2019 | DALEH | DALEH | hood drawings now uploaded into mechanical upload, however the mechanical floor plans have now been left out. Please resubmit complete mechanical submittal. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1195980 |
CO Springs DRE | Original | A | 5/29/2019 | SDALSING | SDALSING | INTERIOR FINISH - NO EXTERIOR WORK PERMITTED AT THIS TIME. USE ALLOWED - PARKING IS MET (see full review) | | CO Springs DRE | 1195612 |
Electrical | Original | A | 5/28/2019 | BERTHA | BERTHA | Re-approved. No new sheets provided. | | Electrical | 1195162 |
Zoning/Planning | Original | / | 5/28/2019 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1195050 |
Resubmittal 2 | Original | / | 5/28/2019 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1195028 |
CO Springs Fire | Original | D | 5/24/2019 | CSFIRE | CSFIRE | See CSFD Disapproval Comments at: http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp | wtaylor | CO Springs Fire | 1194748 |
Hazmat | Original | D | 5/24/2019 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1194746 |
Health Dept. | Original | A | 5/22/2019 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. | abrannon | Health Dept. | 1194014 |
CO Springs DRE | Original | A | 5/16/2019 | SDALSING | SDALSING | INTERIOR FINISH - NO EXTERIOR WORK PERMITTED AT THIS TIME. USE ALLOWED - PARKING IS MET (see full review) | | CO Springs DRE | 1191725 |
Mechanical | Original | D | 5/16/2019 | DALEH | DALEH | still need hood drawings uploaded into mechanical upload still need to reference co2 tanks see plans for complete second set of red lines (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1191634 |
Electrical | Original | A | 5/15/2019 | BERTHA | BERTHA | | | Electrical | 1190968 |
Electronic Plan | Original | / | 5/15/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1190886 |
Zoning/Planning | Original | / | 5/14/2019 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1190774 |
Construction | Original | A | 5/14/2019 | DANM | DANM | | | Construction | 1190440 |
Electronic Plan | Original | / | 5/14/2019 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1190433 |
Enumeration | Original | A | 5/14/2019 | AMY | AMY | | | Enumeration | 1190418 |
Electronic Plan | Original | / | 5/14/2019 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1190383 |
Resubmittal 1 | Original | / | 5/13/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1190197 |
Mechanical | Original | D | 5/9/2019 | DALEH | DALEH | see plans for red line comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1188966 |
Electronic Plan | Original | / | 5/9/2019 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1188955 |
CO Springs Fire | Original | D | 5/9/2019 | CSFIRE | CSFIRE | See CSFD Disapproval Comments at: http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp | wtaylor | CO Springs Fire | 1188737 |
Hazmat | Original | D | 5/9/2019 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1188735 |
CSU Contract Admin. | Original | N | 5/6/2019 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved and applicable Development fees/charges paid - master meter configuration. AG | aguerin | CSU Contract Admin. | 1187394 |
CO Springs DRE | Original | A | 5/3/2019 | SDALSING | SDALSING | INTERIOR FINISH - NO EXTERIOR WORK PERMITTED AT THIS TIME.
USE ALLOWED - PARKING IS MET (see full review) | | CO Springs DRE | 1186919 |
City Engr | Original | N | 5/3/2019 | PMORRIS | PMORRIS | | | City Engr | 1186744 |
Health Dept. | Original | D | 5/2/2019 | HEALTHDEPT | HEALTHDEPT | Health department plan review is in process and not yet approved. For questions please contact 719-578-3199 option 3. | abrannon | Health Dept. | 1185913 |
Water Division | Original | N | 5/1/2019 | CSUREVIEW | CSUREVIEW | No new water service outside of building. JPN | jnoble | Water Division | 1185791 |
Waste Water Div | Original | N | 5/1/2019 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. JPN | jnoble | Waste Water Div | 1185790 |
Gas/Elec. Utils | Original | N | 5/1/2019 | CSUREVIEW | CSUREVIEW | No apparent conflicts. JPN | jnoble | Gas/Elec. Utils | 1185789 |
Electrical | Original | A | 5/1/2019 | SHELBY | SHELBY | | | Electrical | 1185516 |
Plumbing | Original | A | 5/1/2019 | SHANEN | SHANEN | OK | | Plumbing | 1185399 |
Zoning/Planning | Original | / | 5/1/2019 | SDALSING | SDALSING | In Current Review by SDALSING | | Zoning/Planning | 1185283 |
Electronic Plan | Original | / | 5/1/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1185258 |
Elevators | Original | N | 5/1/2019 | ROBERTV | ROBERTV | No Conveynaces | | Elevators | 1185194 |
Construction | Original | D | 4/30/2019 | DANM | DANM | Identify type and height of outdoor seating enclosure; identify type of gate and exit hardware if any Electrical shows door to outdoor seating as having an exit sign - either remove exit sign from electrical or add second exit to outdoor enclosure
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1185136 |
Electronic Plan | Original | / | 4/30/2019 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1184928 |
Enumeration | Original | A | 4/30/2019 | AMY | AMY | | | Enumeration | 1184508 |
Electronic Plan | Original | / | 4/30/2019 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1184506 |
Floodplain | Original | N | 4/23/2019 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6325113006) | | Floodplain | 1181577 |