Scanned/Finished Bin | Splice 09/18/19 | / | 9/18/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1236795 |
To Be Scanned Bin | Splice 09/18/19 | / | 9/18/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1236763 |
Plan Coordinator | Splice 09/18/19 | / | 9/18/2019 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1236735 |
Construction | Splice 09/18/19 | A | 9/18/2019 | DANM | DANM | Listed assemblies provided for 1-hr fire-resistance-rated exterior wall | | Construction | 1236734 |
Construction | Splice 09/18/19 | / | 9/18/2019 | DANM | DANM | In Current Review by DANM | | Construction | 1236543 |
Construction | Splice 09/18/19 | / | 9/18/2019 | | BECKYA | Location = Construction by BECKYA | | Construction | 1236402 |
Out to Review | Splice 09/18/19 | / | 9/18/2019 | BECKYA | BECKYA | | | Out to Review | 1236397 |
Mechanical | Splice 08/29/19 | A | 8/29/2019 | TCRIPPEN | TCRIPPEN | new splice see sheet notes using CSST gas pipe | | Mechanical | 1229338 |
Plumbing | Splice 08/29/19 | A | 8/29/2019 | SHANEN | SHANEN | Delta 1 revisions reroute 3" drain to outside POC | | Plumbing | 1229317 |
Electrical | Splice 08/29/19 | A | 8/29/2019 | BERTHA | BERTHA | Revised plans to reflect change in service. | | Electrical | 1229289 |
To Be Scanned Bin | Original | / | 7/15/2019 | | NELIDA | Location = To Be Scanned Bin by NELIDA | | To Be Scanned Bin | 1212765 |
Woodmoor Waste Water | Original | A | 7/15/2019 | NELIDA | NELIDA | s | | Woodmoor Waste Water | 1212764 |
Woodmoor Water | Original | A | 7/15/2019 | NELIDA | NELIDA | | | Woodmoor Water | 1212763 |
Electrical | Original | A | 7/9/2019 | BERTHA | BERTHA | | | Electrical | 1210855 |
County Zoning | Original | A | 7/8/2019 | DSDYOUNGER | DSDYOUNGER | COM19-23 APPROVED IN EDARP PER KP FOR GS | | County Zoning | 1210386 |
Construction | Original | A | 7/8/2019 | DANM | DANM | | | Construction | 1210376 |
Mechanical | Original | A | 7/8/2019 | DALEH | DALEH | | | Mechanical | 1210369 |
Electrical | Original | D | 7/8/2019 | SHELBY | SHELBY | Please address previous review comments 3, 5, and 6. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1210344 |
Out to Review | Original | / | 6/27/2019 | RITA | RITA | Glen 719-637-0522 | | Out to Review | 1207216 |
Tri-Lakes Fire (CSFD) | Original | A | 6/27/2019 | CSFIRE | CSFIRE | See CSFD Review comments at: http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp
Plans are being held at CSFD pending payment of review fees. | wtaylor | Tri-Lakes Fire (CSFD) | 1206977 |
Fire | Original | / | 6/11/2019 | | SCANNING | Location = Fire by SCANNING | | Fire | 1200918 |
County Zoning | Original | D | 6/11/2019 | DSDARCHULETA | DSDARCHULETA | pending additional process (per GS) | | County Zoning | 1200793 |
Zoning/Planning | Original | / | 6/10/2019 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1200291 |
Plan Coordinator | Original | / | 6/10/2019 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1200133 |
Mechanical | Original | D | 6/10/2019 | JUSTINC | JUSTINC | See redlines on plan set
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1200123 |
Mechanical | Original | / | 6/10/2019 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1200025 |
Mechanical | Original | / | 6/7/2019 | | SHANEN | Location = Mechanical by SHANEN | | Mechanical | 1199425 |
Plumbing | Original | A | 6/7/2019 | SHANEN | SHANEN | OK | | Plumbing | 1199424 |
Plumbing | Original | / | 6/7/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1199334 |
Plumbing | Original | / | 6/7/2019 | | SHANEN | Location = Plumbing by SHANEN | | Plumbing | 1199333 |
Mechanical | Original | / | 6/6/2019 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1199261 |
Plan Coordinator | Original | / | 6/5/2019 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1198721 |
Electrical | Original | D | 6/5/2019 | SHELBY | SHELBY | 1. One line is inaccurate ( C/T on 200 amp service). 2. IECC is wrong year. 3. Comply 250.122(B) NEC. 4. Comply 440.10 NEC. 5. GFCI devices may not be located behind appliances. 6. Label all electrical devices/equipment with panel and circuit number ( locker room lights etc). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1198718 |
Electrical | Original | / | 6/5/2019 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1198696 |
Electrical | Original | / | 5/17/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1192152 |
Plan Coordinator | Original | / | 5/17/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1192116 |
Construction | Original | D | 5/17/2019 | MICHAELA | MICHAELA | Provide IECC certificate for addition Provide details for ANSI compliant bench Clarify attic access Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1192115 |
Construction | Original | / | 5/17/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1192055 |
Construction | Original | / | 5/3/2019 | | NELIDA | Location = Construction by NELIDA | | Construction | 1186638 |
Enumeration | Original | N | 5/3/2019 | BRENT | BRENT | | | Enumeration | 1186615 |
Floodplain | Original | N | 5/3/2019 | BRENT | BRENT | Structure is out of floodplain | | Floodplain | 1186614 |
Out to Review | Original | / | 5/3/2019 | NELIDA | NELIDA | Glenn walking to zoning, enumerations and floodplain 637-0522 | | Out to Review | 1186596 |
Floodplain | Original | / | 5/3/2019 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7111406004) | | Floodplain | 1186589 |