Required Departments: 3
|
|
|
Log Entries: 5
|
|
Electrical | Original | A | 5/7/2019 | SHELBY | SHELBY | | | Electrical | 1187652 | Electrical | Original | D | 5/7/2019 | BERTHA | BERTHA | 1. Provide new panel withstand rating. 2. Provide available fault current at new panel. 3. Provide service load summary.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1187584 | Enumeration | Original | A | 5/7/2019 | AMY | AMY | suite 100 | | Enumeration | 1187541 | Out to Review | Original | / | 5/7/2019 | NELIDA | NELIDA | Peter walking (719) 6402650. | | Out to Review | 1187516 | Floodplain | Original | N | 5/7/2019 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6233201004) | | Floodplain | 1187515 |
|
| |
|