Mechanical | Splice 10/31/19 | A | 11/14/2019 | TCRIPPEN | TCRIPPEN | new splice pages changed room names removed exhaust system for nails | | Mechanical | 1256765 |
Electrical | Splice 10/31/19 | A | 11/6/2019 | SHELBY | SHELBY | | | Electrical | 1254060 |
Plumbing | Splice 10/31/19 | A | 11/6/2019 | SHANEN | SHANEN | Delta R1 revisions P1 revised plumbing plan, P3 revised water isometric | | Plumbing | 1254050 |
Resubmittal 1 | Splice 10/31/19 | / | 11/5/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1253438 |
Plumbing | Splice 10/31/19 | D | 11/1/2019 | SHANEN | SHANEN | Cloud revisions on P1 Show adequate freeze protection or drain down for water line to swamp cooler on P3
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1252112 |
Electrical | Splice 10/31/19 | D | 11/1/2019 | BERTHA | BERTHA | Provide SCA and SCCR for MAU.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1252097 |
Mechanical | Splice 10/31/19 | D | 11/1/2019 | TCRIPPEN | TCRIPPEN | remove old clouds cloud only new work remove nail from ventilation table What is ED diffuser ? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1252080 |
Out to Review | Splice 10/31/19 | / | 11/1/2019 | BECKYA | BECKYA | | | Out to Review | 1252046 |
Electrical | Original | A | 8/6/2019 | BERTHA | BERTHA | Re-approved for revisions prior to permitting. | | Electrical | 1221177 |
Mechanical | Original | A | 8/6/2019 | DALEH | DALEH | | | Mechanical | 1221150 |
Resubmittal 3 | Original | / | 8/6/2019 | JANE | JANE | Resubmittal #3 | | Resubmittal 3 | 1221132 |
Out to Review | Original | / | 8/6/2019 | JANE | JANE | Erik | | Out to Review | 1220834 |
Finished Bin | Original | / | 8/5/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1220322 |
Plan Coordinator | Original | / | 8/5/2019 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1220234 |
Mechanical | Original | D | 8/5/2019 | DALEH | DALEH | need to show existing RTU and all ducting for that unit appears there will be a conflict between the existing and the new MUA unit gas piping for new MUA unit ? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1220231 |
Mechanical | Original | / | 8/2/2019 | | JANE | Location = Mechanical by JANE | | Mechanical | 1220007 |
Resubmittal 2 | Original | / | 8/2/2019 | JANE | JANE | Resubmittal #2 | | Resubmittal 2 | 1220006 |
Out to Review | Original | / | 7/18/2019 | NELIDA | NELIDA | Erik 303-349-3540 | | Out to Review | 1214493 |
Finished Bin | Original | / | 7/18/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1214305 |
Plan Coordinator | Original | / | 7/18/2019 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1214210 |
Mechanical | Original | D | 7/18/2019 | DALEH | DALEH | no response to previous comments please respond to ALL comments and resubmit no review no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1214208 |
Mechanical | Original | / | 7/18/2019 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1214181 |
Mechanical | Original | / | 7/17/2019 | | GITA | Location = Mechanical by GITA | | Mechanical | 1213986 |
Resubmittal 1 | Original | / | 7/17/2019 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1213985 |
Electrical | Original | A | 7/3/2019 | BERTHA | BERTHA | | | Electrical | 1209551 |
Out to Review | Original | / | 6/21/2019 | NELIDA | NELIDA | Erik Miller 480-406-1116 | | Out to Review | 1205057 |
Finished Bin | Original | / | 6/17/2019 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1203407 |
Water Division | Original | N | 6/17/2019 | CSUREVIEW | CSUREVIEW | No new water service outside of building. Backflow OK. KDS | kschelhaas | Water Division | 1203318 |
Waste Water Div | Original | N | 6/17/2019 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. KDS | kschelhaas | Waste Water Div | 1203317 |
CSU Utilities | Original | / | 6/14/2019 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 1202620 |
CO Springs Fire | Original | A | 6/14/2019 | CSFIRE | CSFIRE | See CSFD Plan Review Comments at: http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp | wtaylor | CO Springs Fire | 1202618 |
Hazmat | Original | N | 6/14/2019 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1202616 |
Fire | Original | / | 6/5/2019 | | SDALSING | Location = Fire by SDALSING | | Fire | 1198583 |
CO Springs DRE | Original | A | 6/5/2019 | SDALSING | SDALSING | APPROVED:
PERSONAL CONSUMER (SALON) ALLOWED IN C5. PARKING MET. NO EXTERIOR WORK PERMITTED AT THIS TIME (see full review) | | CO Springs DRE | 1198582 |
Out to Review | Original | / | 5/31/2019 | RITA | RITA | Fedencio | | Out to Review | 1197325 |
Finished Bin | Original | / | 5/30/2019 | | DANM | Location = Finished Bin by DANM | | Finished Bin | 1196661 |
Plan Coordinator | Original | / | 5/28/2019 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1195438 |
Mechanical | Original | D | 5/28/2019 | DALEH | DALEH | SHEET M1 make up air for dryer ? mechanical equipment room does not show any mechanical equipment ? how does exhaust fan vent through roof terminate ? label rooms usage on drawings see table 403.3.1.1 for proper ventilation and exhaust rates for ALL rooms return air path ? SHEET M2 see ventilation schedule for multiple comments provide a balance schedule see plans for all red line comments no walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1195437 |
Mechanical | Original | / | 5/28/2019 | | DANM | Location = Mechanical by DANM | | Mechanical | 1195134 |
Construction | Original | / | 5/28/2019 | DANM | DANM | In Current Review by DANM | | Construction | 1195133 |
Construction | Original | / | 5/28/2019 | | SHANEN | Location = Construction by SHANEN | | Construction | 1195132 |
Plumbing | Original | A | 5/28/2019 | SHANEN | SHANEN | OK | | Plumbing | 1195131 |
Plumbing | Original | / | 5/28/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1195084 |
Plumbing | Original | / | 5/28/2019 | | DANM | Location = Plumbing by DANM | | Plumbing | 1195068 |
Construction | Original | A | 5/28/2019 | DANM | DANM | | | Construction | 1195067 |
Construction | Original | / | 5/28/2019 | DANM | DANM | In Current Review by DANM | | Construction | 1195044 |
Construction | Original | / | 5/24/2019 | | BECKYA | Location = Construction by BECKYA | | Construction | 1195002 |
Out to Review | Original | / | 5/23/2019 | NELIDA | NELIDA | Fidencio 719-473-8400 | | Out to Review | 1194475 |
Construction | Original | / | 5/23/2019 | | JANE | Location = Construction by JANE | | Construction | 1194160 |
Out to Review | Original | / | 5/22/2019 | JANE | JANE | At Jane's desk waiting for plan review fee | | Out to Review | 1193638 |
Construction | Original | / | 5/22/2019 | | JANE | Location = Construction by JANE | | Construction | 1193632 |
Enumeration | Original | N | 5/22/2019 | BRENT | BRENT | | | Enumeration | 1193619 |
Out to Review | Original | / | 5/22/2019 | NELIDA | NELIDA | Erik Miller walking to Enumerations only | | Out to Review | 1193613 |
Enumeration | Original | / | 5/22/2019 | | NELIDA | Location = Enumeration by NELIDA | | Enumeration | 1193610 |
Electrical | Original | D | 5/22/2019 | SHELBY | SHELBY | 1. Use 2015 IECC 2. Comply 210.21(B)(3) NEC (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1193550 |
Out to Review | Original | / | 5/22/2019 | NELIDA | NELIDA | Erik Miller 303-349-3540 | | Out to Review | 1193451 |
Floodplain | Original | N | 5/22/2019 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7324405008) | | Floodplain | 1193444 |