Mechanical | Splice 03/27/20 | A | 3/27/2020 | TCRIPPEN | TCRIPPEN | new splice removing hot and cold from VAV | | Mechanical | 1302299 |
Plumbing | Splice 03/27/20 | N | 3/27/2020 | SHANEN | SHANEN | Hydronics to be on mechanical plans. No plumbing in this splice request. | | Plumbing | 1302269 |
Electronic Plan | Splice 03/27/20 | / | 3/27/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1302264 |
Scanned/Finished Bin | Splice 02/18/20 | / | 2/19/2020 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1288188 |
To Be Scanned Bin | Splice 02/18/20 | / | 2/19/2020 | | RITA | Location = To Be Scanned Bin by RITA | | To Be Scanned Bin | 1287989 |
CO Springs Fire | Splice 02/18/20 | A | 2/19/2020 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1287974 |
Mechanical | Splice 02/18/20 | A | 2/19/2020 | TCRIPPEN | TCRIPPEN | okay new splice relocate doors and FSD | | Mechanical | 1287814 |
Construction | Splice 02/18/20 | A | 2/19/2020 | SHELLEY | SHELLEY | Revise smoke barrier location. | | Construction | 1287781 |
Out to Review | Splice 02/18/20 | / | 2/18/2020 | BECKYA | BECKYA | | | Out to Review | 1287233 |
Mechanical | Splice 01/17/20 | A | 1/17/2020 | TCRIPPEN | TCRIPPEN | new splice re route HWR and HWS lines, re route ducts changed a Damper type Adjusted schedules | | Mechanical | 1277192 |
CO Springs Fire | Splice 01/17/20 | A | 1/17/2020 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1277096 |
Mechanical | Splice 01/17/20 | D | 1/17/2020 | TCRIPPEN | TCRIPPEN | Missing MP121 not in our system ? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1277086 |
Out to Review | Splice 01/17/20 | / | 1/17/2020 | BECKYA | BECKYA | | | Out to Review | 1277053 |
Out to Review | Original | / | 1/13/2020 | SHELBY | SHELBY | Set to out to review to correct erroneous re submittal to electrical | | Out to Review | 1275080 |
Mechanical | Splice 12/20/19 | A | 12/23/2019 | TCRIPPEN | TCRIPPEN | new splice added unit heater added fire/smoke dampers | | Mechanical | 1269767 |
CO Springs Fire | Splice 12/20/19 | A | 12/23/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1269731 |
Mechanical | Splice 11/14/19 | A | 11/14/2019 | TCRIPPEN | TCRIPPEN | relocate duct and Fire Damper | | Mechanical | 1256810 |
Out to Review | Splice 11/14/19 | / | 11/14/2019 | BECKYA | BECKYA | | | Out to Review | 1256758 |
Out to Review | Splice 11/01/19 | / | 11/5/2019 | SCANNING | SCANNING | Confirmed with Nellida that the contractor has their own approved copy and the copy we scanned they do not need back. | | Out to Review | 1253376 |
Scanned/Finished Bin | Splice 11/01/19 | / | 11/5/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1253364 |
To Be Scanned Bin | Splice 11/01/19 | / | 11/4/2019 | | NELIDA | Location = To Be Scanned Bin by NELIDA | | To Be Scanned Bin | 1253101 |
CO Springs Fire | Splice 11/01/19 | A | 11/4/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1253036 |
Electrical | Splice 11/01/19 | A | 11/1/2019 | SHELBY | SHELBY | | | Electrical | 1252583 |
Mechanical | Splice 11/01/19 | A | 11/1/2019 | DALEH | DALEH | clouds | | Mechanical | 1252562 |
Construction | Splice 11/01/19 | A | 11/1/2019 | MICHAELA | MICHAELA | Steel platform | | Construction | 1252547 |
Plumbing | Splice 11/01/19 | A | 11/1/2019 | SHANEN | SHANEN | Delta ASI-19 revisions PP111 piping to FS-1, PP121 adjusted floor plan for FS-1 | | Plumbing | 1252540 |
Out to Review | Splice 11/01/19 | / | 11/1/2019 | BECKYA | BECKYA | | | Out to Review | 1252530 |
Out to Review | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 10/31/2019 | RITA | RITA | Jorge | | Out to Review | 1251676 |
Out to Review | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | / | 10/31/2019 | RITA | RITA | Jorge | | Out to Review | 1251673 |
Out to Review | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | / | 10/31/2019 | RITA | RITA | Jorge | | Out to Review | 1251671 |
Scanned/Finished Bin | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | / | 10/22/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1248330 |
Scanned/Finished Bin | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 10/22/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1248316 |
Scanned/Finished Bin | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | / | 10/22/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1248314 |
To Be Scanned Bin | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | / | 10/22/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1248224 |
To Be Scanned Bin | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 10/22/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1248218 |
To Be Scanned Bin | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | / | 10/22/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1248217 |
CO Springs Fire | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | A | 10/21/2019 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L ,Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1247653 |
CO Springs Fire | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | A | 10/21/2019 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L ,Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1247648 |
CO Springs Fire | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | A | 10/21/2019 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L ,Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1247636 |
Fire | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | / | 10/4/2019 | | SCANNING | Location = Fire by SCANNING | | Fire | 1242712 |
Fire | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | / | 10/4/2019 | | SCANNING | Location = Fire by SCANNING | | Fire | 1242711 |
Fire | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 10/4/2019 | | SCANNING | Location = Fire by SCANNING | | Fire | 1242705 |
Electrical | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | A | 10/4/2019 | SHELBY | SHELBY | Phasing | | Electrical | 1242576 |
Electrical | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | A | 10/4/2019 | SHELBY | SHELBY | | | Electrical | 1242573 |
Plan Coordinator | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 10/4/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1242569 |
Plan Coordinator | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | / | 10/4/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1242568 |
Plan Coordinator | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | / | 10/4/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1242567 |
Plumbing | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | A | 10/4/2019 | SHANEN | SHANEN | Plan approval is for phasing only. See previously approved plan for all plumbing work. | | Plumbing | 1242564 |
Plumbing | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | A | 10/4/2019 | SHANEN | SHANEN | Plan approval is for phasing only. See previously approved plan for all plumbing work. | | Plumbing | 1242559 |
Plumbing | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | N | 10/4/2019 | SHANEN | SHANEN | No revised plumbing pages submitted. | | Plumbing | 1242553 |
Plumbing | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 10/3/2019 | | SHELBY | Location = Plumbing by SHELBY | | Plumbing | 1242382 |
Electrical | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | A | 10/3/2019 | SHELBY | SHELBY | | | Electrical | 1242381 |
Electrical | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 9/30/2019 | | JUSTINC | Location = Electrical by JUSTINC | | Electrical | 1240571 |
Electrical | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | / | 9/30/2019 | | JUSTINC | Location = Electrical by JUSTINC | | Electrical | 1240564 |
Mechanical | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | A | 9/30/2019 | JUSTINC | JUSTINC | Plan approval is for phasing only. See previously approved plan for all mechanical work. | | Mechanical | 1240563 |
Electrical | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | / | 9/30/2019 | | JUSTINC | Location = Electrical by JUSTINC | | Electrical | 1240559 |
Mechanical | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | A | 9/30/2019 | JUSTINC | JUSTINC | Plan approval is for phasing only. See previously approved plan for all mechanical work. | | Mechanical | 1240558 |
Mechanical | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | A | 9/30/2019 | JUSTINC | JUSTINC | Plan approval is for phasing only. See previously approved plan for all mechanical work. | | Mechanical | 1240555 |
Mechanical | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 9/30/2019 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1240503 |
Mechanical | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 9/30/2019 | | MICHAELA | Location = Mechanical by MICHAELA | | Mechanical | 1240502 |
Mechanical | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | / | 9/30/2019 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1240501 |
Mechanical | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | / | 9/30/2019 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1240500 |
Mechanical | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | / | 9/30/2019 | | MICHAELA | Location = Mechanical by MICHAELA | | Mechanical | 1240498 |
Construction | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | N | 9/30/2019 | MICHAELA | MICHAELA | | | Construction | 1240497 |
Mechanical | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | / | 9/30/2019 | | MICHAELA | Location = Mechanical by MICHAELA | | Mechanical | 1240495 |
Construction | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | N | 9/30/2019 | MICHAELA | MICHAELA | | | Construction | 1240494 |
Plan Coordinator | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 9/30/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1240489 |
Construction | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | N | 9/30/2019 | MICHAELA | MICHAELA | | | Construction | 1240488 |
Construction | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | / | 9/30/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1240486 |
Construction | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | / | 9/30/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1240484 |
Construction | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 9/30/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1240483 |
Construction | Splice 09/27/19 Phase 3 M52951 Mech/elec/plmb/con | / | 9/27/2019 | | MATTHEWM | Location = Construction by MATTHEWM | | Construction | 1240356 |
Construction | Splice 09/27/19 Phase 2 M52947 Mech/elec/plmb/const/fire | / | 9/27/2019 | | MATTHEWM | Location = Construction by MATTHEWM | | Construction | 1240353 |
Construction | Splice 09/27/19 Phase 1 M35724 Mech/elec/plmb/const/fire | / | 9/27/2019 | | MATTHEWM | Location = Construction by MATTHEWM | | Construction | 1240349 |
Electrical | Splice 09/11/19 | A | 9/18/2019 | BERTHA | BERTHA | Added temporary mobile equipment. | | Electrical | 1236364 |
Mechanical | Splice 09/11/19 | A | 9/18/2019 | TCRIPPEN | TCRIPPEN | changed smoke Dampers to Fire /smoke Dampers | | Mechanical | 1236325 |
Mechanical | Splice 09/11/19 | D | 9/13/2019 | TCRIPPEN | TCRIPPEN | new page incomplete not all printed? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1234802 |
Plumbing | Splice 09/11/19 | A | 9/13/2019 | SHANEN | SHANEN | Delta ASI-12 revisions PP101 key notes 1 - 7, PP112 DWV up to FS-1, PP122 water piping to FS-1 | | Plumbing | 1234794 |
CO Springs Fire | Splice 09/11/19 | A | 9/11/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1233742 |
Scanned/Finished Bin | Splice 08/20/19 | / | 9/11/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1233699 |
Mechanical | Splice 09/11/19 | D | 9/11/2019 | DALEH | DALEH | see comment about dampers needing to be smoke (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1233692 |
Construction | Splice 09/11/19 | A | 9/11/2019 | SHELLEY | SHELLEY | Minor floor plan revisions | | Construction | 1233633 |
Plumbing | Splice 09/11/19 | D | 9/11/2019 | SHANEN | SHANEN | Provide back-flow protection for water lines serving SPD trailers. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1233616 |
Electrical | Splice 09/11/19 | D | 9/11/2019 | BERTHA | BERTHA | Provide load justifications for all gear (normal and emergency) affected by the addition of temporary mobile equipment.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1233597 |
To Be Scanned Bin | Splice 08/20/19 | / | 9/11/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1233519 |
Out to Review | Splice 09/11/19 | / | 9/11/2019 | BECKYA | BECKYA | | | Out to Review | 1233287 |
CO Springs Fire | Splice 08/20/19 | A | 9/10/2019 | CSFIRE | CSFIRE | Submitted By: Withee, Doreen E ,Submitted By: Withee, Doreen E (see full review) | csfdit | CO Springs Fire | 1233156 |
Fire | Splice 08/20/19 | / | 8/28/2019 | | SCANNING | Location = Fire by SCANNING | | Fire | 1229078 |
Plan Coordinator | Splice 08/20/19 | / | 8/28/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1229039 |
Plumbing | Splice 08/20/19 | A | 8/28/2019 | SHANEN | SHANEN | Delta ASI-09 revisions PP121 Reconfigure men's room, remove restroom, change women's restroom lav to L-2, P600 adjusted fixture schedule | | Plumbing | 1229038 |
Plumbing | Splice 08/20/19 | / | 8/28/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1229009 |
Plumbing | Splice 08/20/19 | / | 8/28/2019 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1228942 |
Plan Coordinator | Splice 08/20/19 | / | 8/28/2019 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1228895 |
Mechanical | Splice 08/20/19 | A | 8/28/2019 | JUSTINC | JUSTINC | Revised to change restroom into nurse station and delete supply air | | Mechanical | 1228893 |
Mechanical | Splice 08/20/19 | / | 8/28/2019 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1228874 |
Mechanical | Splice 08/20/19 | / | 8/28/2019 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1228859 |
Plan Coordinator | Splice 08/20/19 | / | 8/28/2019 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1228809 |
Electrical | Splice 08/20/19 | A | 8/28/2019 | BERTHA | BERTHA | Revised for background change. Added card readers. | | Electrical | 1228808 |
Electrical | Splice 08/20/19 | / | 8/22/2019 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1226914 |
Electrical | Splice 08/20/19 | / | 8/22/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1226876 |
Plan Coordinator | Splice 08/20/19 | / | 8/22/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1226836 |
Construction | Splice 08/20/19 | A | 8/22/2019 | MICHAELA | MICHAELA | Add wall assembly - revise layout some location - | | Construction | 1226835 |
Construction | Splice 08/20/19 | / | 8/21/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1226769 |
Construction | Splice 08/20/19 | / | 8/20/2019 | | BECKYA | Location = Construction by BECKYA | | Construction | 1225824 |
Out to Review | Original | / | 6/24/2019 | GITA | GITA | 30330150263 Derek | | Out to Review | 1205548 |
Scanned/Finished Bin | Original | / | 6/19/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1204191 |
To Be Scanned Bin | Original | / | 6/18/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1203751 |
Health Dept. | Original | N | 6/18/2019 | HEALTHDEPT | HEALTHDEPT | Not applicable. | abrannon | Health Dept. | 1203688 |
Health Dept. | Original | / | 6/17/2019 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1203526 |
Plan Coordinator | Original | / | 6/17/2019 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1203519 |
Plumbing | Original | A | 6/17/2019 | SHANEN | SHANEN | OK | | Plumbing | 1203518 |
Plumbing | Original | / | 6/17/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1203472 |
Plumbing | Original | / | 6/17/2019 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1203466 |
Plan Coordinator | Original | / | 6/17/2019 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1203451 |
Mechanical | Original | A | 6/17/2019 | JUSTINC | JUSTINC | | | Mechanical | 1203450 |
Mechanical | Original | / | 6/17/2019 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1203406 |
Plan Coordinator | Original | / | 6/17/2019 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1203364 |
Electrical | Original | A | 6/17/2019 | BERTHA | BERTHA | | | Electrical | 1203362 |
Electrical | Original | / | 6/17/2019 | | GITA | Location = Electrical by GITA | | Electrical | 1203001 |
Resubmittal 1 | Original | / | 6/17/2019 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1203000 |
Out to Review | Original | / | 6/10/2019 | JANE | JANE | MItchell 719 867 7050 | | Out to Review | 1200447 |
Health Dept. | Original | / | 6/10/2019 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1200280 |
Water Division | Original | N | 6/6/2019 | CSUREVIEW | CSUREVIEW | No apparent conflicts. KDS | kschelhaas | Water Division | 1198970 |
Waste Water Div | Original | N | 6/6/2019 | CSUREVIEW | CSUREVIEW | No apparent conflicts. KDS | kschelhaas | Waste Water Div | 1198969 |
CO Springs Fire | Original | A | 6/5/2019 | CSFIRE | CSFIRE | See CSFD Plan Review Comments at: http://springsgov.com/units/fire/Prevent/PlansReview/FPS_WebFPS.asp | wtaylor | CO Springs Fire | 1198743 |
Hazmat | Original | N | 6/5/2019 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1198741 |
Fire | Original | / | 6/4/2019 | | KHYLLESTED | Location = Fire by KHYLLESTED | | Fire | 1198428 |
CO Springs DRE | Original | N | 6/4/2019 | KHYLLESTED | KHYLLESTED | Interior remodel only. No change of use. (see full review) | | CO Springs DRE | 1198427 |
Zoning/Planning | Original | / | 6/4/2019 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1198040 |
Plan Coordinator | Original | / | 6/4/2019 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1198033 |
Mechanical | Original | D | 6/4/2019 | JUSTINC | JUSTINC | Dampers shown penetrating smoke barrier must resist passage of smoke. Provide ventilation schedules per 2015 IMC 403.3.1.1
WALK OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1198032 |
Mechanical | Original | / | 6/4/2019 | | SHANEN | Location = Mechanical by SHANEN | | Mechanical | 1198009 |
Plumbing | Original | D | 6/4/2019 | SHANEN | SHANEN | Provide water pipe size analysis data. Provide piping materials schedule. Plans in this series: 117500, 117501 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1198007 |
Plumbing | Original | / | 6/4/2019 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1197989 |
Plumbing | Original | / | 6/4/2019 | | SHANEN | Location = Plumbing by SHANEN | | Plumbing | 1197988 |
Mechanical | Original | / | 6/4/2019 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1197975 |
Plan Coordinator | Original | / | 6/3/2019 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1197822 |
Electrical | Original | D | 6/3/2019 | SHELBY | SHELBY | Please provide load justification for CHSDB-H1 and ATS-H1C Note Two plans in this series 117500, 117501 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1197820 |
Electrical | Original | / | 6/3/2019 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1197417 |
Electrical | Original | / | 5/30/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1196338 |
Plan Coordinator | Original | / | 5/30/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1196275 |
Construction | Original | A | 5/30/2019 | MICHAELA | MICHAELA | | | Construction | 1196274 |
Construction | Original | / | 5/30/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1196218 |
Construction | Original | / | 5/30/2019 | | SCANNING | Location = Construction by SCANNING | | Construction | 1196172 |
Plan Coordinator | Original | / | 5/30/2019 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1196139 |
Enumeration | Original | N | 5/30/2019 | AMY | AMY | | | Enumeration | 1196138 |
Enumeration | Original | / | 5/30/2019 | AMY | AMY | In Current Review by AMY | | Enumeration | 1196137 |
Floodplain | Original | N | 5/29/2019 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5307003003) | | Floodplain | 1196093 |