Elevators | Original | A | 8/20/2019 | ERIC | ERIC | | | Elevators | 1226066 | Electrical | Original | A | 8/20/2019 | SHELBY | SHELBY | | | Electrical | 1226059 | Electrical | Original | D | 8/6/2019 | BERTHA | BERTHA | Provide SCCR for elevator controller.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1221022 | Electrical | Original | D | 8/2/2019 | BERTHA | BERTHA | 1. Comply 409.22(B) - SCA and SCCR must be shown on the one-line for all Industrial Control Panels - Elevator Controllers. 2. Provide all conductor size type and quantity for the scope of work - from elevator disconnect to elevator controller.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1219718 | Enumeration | Original | A | 8/2/2019 | BRENT | BRENT | | | Enumeration | 1219696 | Out to Review | Original | / | 8/2/2019 | NELIDA | NELIDA | John 719-649-0141 | | Out to Review | 1219676 | Floodplain | Original | N | 8/2/2019 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6327120001) | | Floodplain | 1219675 |
|
| |
|