Mechanical | Splice 01/25/21 | A | 1/25/2021 | JUSTINC | JUSTINC | Added transfer grills | | Mechanical | 1444979 |
Electronic Plan | Splice 01/25/21 | / | 1/25/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1444971 |
Mechanical | Splice 12/07/20 | A | 12/8/2020 | JUSTINC | JUSTINC | Revised VAV | | Mechanical | 1423706 |
Electronic Plan | Splice 12/07/20 | / | 12/8/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1423700 |
Out to Review | Original | / | 3/2/2020 | GITA | GITA | eric | | Out to Review | 1292725 |
Scanned/Finished Bin | Original | / | 10/28/2019 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1250372 |
To Be Scanned Bin | Original | / | 10/28/2019 | | SCANNING | Location = To Be Scanned Bin by SCANNING | | To Be Scanned Bin | 1250301 |
Plan Coordinator | Original | / | 10/25/2019 | | AODOM | Location = Plan Coordinator by AODOM | | Plan Coordinator | 1250014 |
CO Springs DRE | Original | N | 10/25/2019 | AODOM | AODOM | Interior Finish, no exterior work. no change of use.AMO per MPF | | CO Springs DRE | 1250013 |
Plan Coordinator | Original | / | 10/25/2019 | | MPFITZSIMMONS | Location = Plan Coordinator by MPFITZSIMMONS | | Plan Coordinator | 1250010 |
CO Springs DRE | Original | N | 10/25/2019 | MPFITZSIMMONS | MPFITZSIMMONS | (see full review) | | CO Springs DRE | 1250009 |
Out to Review | Original | / | 10/25/2019 | | MPFITZSIMMONS | Location = Out to Review by MPFITZSIMMONS | | Out to Review | 1250008 |
CO Springs DRE | Original | N | 10/25/2019 | MPFITZSIMMONS | MPFITZSIMMONS | | | CO Springs DRE | 1250007 |
Electrical | Original | A | 10/24/2019 | BERTHA | BERTHA | | | Electrical | 1249570 |
Hazmat | Original | N | 10/24/2019 | CSFIRE | CSFIRE | | fdjah74 | Hazmat | 1249275 |
CO Springs Fire | Original | A | 10/24/2019 | CSFIRE | CSFIRE | Submitted By: Hanenberg, Jeffry A,Submitted By: Hanenberg, Jeffry A (see full review) | csfdit | CO Springs Fire | 1249274 |
Mechanical | Original | A | 10/2/2019 | JUSTINC | JUSTINC | | | Mechanical | 1241803 |
Electrical | Original | D | 10/2/2019 | BERTHA | BERTHA | Provide compliance with 240.24 2017 NEC
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1241789 |
Construction | Original | A | 10/1/2019 | LBENNETT | LBENNETT | | | Construction | 1241444 |
Plumbing | Original | A | 10/1/2019 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1241425 |
Plumbing | Original | D | 9/25/2019 | SHANEN | SHANEN | Design professional stamp and signature required. Provide piping materials schedule on P page not M page. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1239392 |
Mechanical | Original | D | 9/11/2019 | DALEH | DALEH | need clarification on wall height (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1233802 |
Plumbing | Original | D | 9/11/2019 | SHANEN | SHANEN | Provide water heater platform detail and show pan drain discharge location. Provide piping materials schedule on plumbing plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1233789 |
Water Division | Original | N | 9/11/2019 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | Water Division | 1233771 |
Waste Water Div | Original | N | 9/11/2019 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | Waste Water Div | 1233770 |
Construction | Original | D | 9/11/2019 | SHELLEY | SHELLEY | Provide wall height for "dirt" furniture. If over 5'9", provide all standard wall details. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1233714 |
Enumeration | Original | A | 9/11/2019 | AMY | AMY | create new suite | | Enumeration | 1233707 |
Out to Review | Original | / | 9/11/2019 | JANE | JANE | Spencer walking | | Out to Review | 1233687 |
Floodplain | Original | N | 9/11/2019 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418215018) | | Floodplain | 1233685 |