Construction | Splice 05/11/20 | A | 5/12/2020 | DANM | DANM | Revised partition type details | | Construction | 1320831 |
Electronic Plan | Splice 05/11/20 | / | 5/12/2020 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1320826 |
Electrical | Splice 03/05/20 | A | 3/18/2020 | SHELBY | SHELBY | | | Electrical | 1298975 |
Resubmittal 2 | Splice 03/05/20 | / | 3/17/2020 | DANM | DANM | Resubmittal #2 | | Resubmittal 2 | 1298857 |
Mechanical | Splice 03/05/20 | A | 3/11/2020 | TCRIPPEN | TCRIPPEN | okay | | Mechanical | 1296430 |
Electronic Plan | Splice 03/05/20 | / | 3/10/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1296239 |
Construction | Splice 03/05/20 | A | 3/10/2020 | DANM | DANM | Structural review for new RTU | | Construction | 1295810 |
Electronic Plan | Splice 03/05/20 | / | 3/10/2020 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1295795 |
Electrical | Splice 03/05/20 | D | 3/9/2020 | SHELBY | SHELBY | No electrical sheets in this submittal. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1295480 |
Resubmittal 1 | Splice 03/05/20 | / | 3/9/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1295461 |
Electrical | Splice 03/05/20 | D | 3/6/2020 | SHELBY | SHELBY | This plan is for STE 180 remove all STE 170 information. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1294827 |
Mechanical | Splice 03/05/20 | D | 3/6/2020 | TCRIPPEN | TCRIPPEN | Pending strucal letter for RTU (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1294641 |
Plumbing | Splice 03/05/20 | N | 3/6/2020 | SHANEN | SHANEN | No plumbing scope of work, gas piping moved to mechanical sheets. | | Plumbing | 1294635 |
Plumbing | Splice 03/05/20 | D | 3/6/2020 | SHANEN | SHANEN | Provide only pages with with clouded revisions. All gas piping related items to be on M pages. Provide descriptive narrative for plumbing revisions. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1294545 |
Electronic Plan | Splice 03/05/20 | / | 3/5/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1294517 |
Construction | Original | A | 1/9/2020 | BPHILLIPS | BPHILLIPS | | | Construction | 1274051 |
Electronic Plan | Original | / | 1/9/2020 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1274047 |
Enumeration | Original | A | 1/9/2020 | AMY | AMY | suite 180 | | Enumeration | 1274041 |
Electronic Plan | Original | / | 1/9/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1274040 |
Resubmittal 4 | Original | / | 1/8/2020 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1273787 |
Construction | Original | A | 1/7/2020 | BPHILLIPS | BPHILLIPS | No construction changes evident in resubmittal. | | Construction | 1272977 |
Electronic Plan | Original | / | 1/7/2020 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1272974 |
Enumeration | Original | D | 1/7/2020 | AMY | AMY | The secondary addressing provided does not come close to permit history that is on file. Is this what is posted on site? (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1272937 |
Resubmittal 3 | Original | / | 1/6/2020 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1272784 |
Plumbing | Original | A | 12/17/2019 | SHANEN | SHANEN | | | Plumbing | 1267688 |
Mechanical | Original | A | 12/16/2019 | TCRIPPEN | TCRIPPEN | oklay | | Mechanical | 1267619 |
Enumeration | Original | D | 12/16/2019 | AMY | AMY | See note from 12-3-19, page A0.0 still does not show this information. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1267414 |
Electronic Plan | Original | / | 12/16/2019 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1267411 |
Resubmittal 2 | Original | / | 12/13/2019 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1267206 |
Electrical | Original | A | 12/9/2019 | SHELBY | SHELBY | | | Electrical | 1265475 |
Mechanical | Original | D | 12/5/2019 | TCRIPPEN | TCRIPPEN | provide Isometric for gas piping to show connections BTUS and length, Added RBD note 12- 12- 19 see core and shell existing gas line over 1 year old need to retest and release meter if good verify sizing. Need to schedule RTU. provide roof plan showing equipment and exhaust required separations. added note 12 12- 19 roof plan not required clarify ceiling is open plenum do closed rooms need returns ? construction showing drywall and paint ?, added note 12- 12- 19 add note to plan set open ceiling wall 3/4 height not to structure.
. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1263846 |
Plumbing | Original | A | 12/5/2019 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1263799 |
Electronic Plan | Original | / | 12/5/2019 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1263622 |
Construction | Original | A | 12/4/2019 | BPHILLIPS | BPHILLIPS | | | Construction | 1263226 |
Electronic Plan | Original | / | 12/4/2019 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1263146 |
Enumeration | Original | D | 12/3/2019 | AMY | AMY | On floor plan show separation of space with all suite numbers to date on site. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1262907 |
Electronic Plan | Original | / | 12/3/2019 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1262902 |
Resubmittal 1 | Original | / | 12/3/2019 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1262831 |
Hazmat | Original | N | 10/25/2019 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1249816 |
CO Springs Fire | Original | N | 10/24/2019 | CSFIRE | CSFIRE | no fire final (see full review) | csfdit | CO Springs Fire | 1249581 |
CO Springs DRE | Original | A | 10/15/2019 | RLOZANO | RLOZANO | Interior finish only - use is permitted per DP/zone, parking okay. Note: This project will be okay for CO when it comes time for the final inspection. (see full review) | | CO Springs DRE | 1246240 |
Zoning/Planning | Original | / | 10/15/2019 | RLOZANO | RLOZANO | In Current Review by RLOZANO | | Zoning/Planning | 1245791 |
Plumbing | Original | D | 10/14/2019 | SHANEN | SHANEN | Provide water pipe size analysis data. See 2015 IPC appendix E. Provide water piping isometric. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1245490 |
Electrical | Original | A | 10/14/2019 | SHELBY | SHELBY | | | Electrical | 1245357 |
Mechanical | Original | D | 10/11/2019 | TCRIPPEN | TCRIPPEN | Need to provide complete mechanical this is a tenant finish provide ventilation table to the 2015 IMC is duct work complete (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1245059 |
Water Division | Original | A | 10/11/2019 | CSUREVIEW | CSUREVIEW | Backflow okay. MLW | mlwilliams | Water Division | 1244944 |
Water Division | Original | A | 10/11/2019 | CSUREVIEW | CSUREVIEW | Backflow okay. MLW | mlwilliams | Water Division | 1244943 |
Waste Water Div | Original | N | 10/11/2019 | CSUREVIEW | CSUREVIEW | No external utility work proposed. MLW | mlwilliams | Waste Water Div | 1244941 |
Construction | Original | A | 10/10/2019 | BPHILLIPS | BPHILLIPS | | | Construction | 1244739 |
Electronic Plan | Original | / | 10/10/2019 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1244709 |
Enumeration | Original | D | 10/10/2019 | AMY | AMY | This should be an interior finish to create a new suite. 180 is not a current suite with permit history. Correct code study form to interior finish. On floor plan show separation of space with all suite numbers to date on site. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1244377 |
Electronic Plan | Original | / | 10/10/2019 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1244371 |
Floodplain | Original | N | 10/9/2019 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6217203036) | | Floodplain | 1243932 |