Mechanical | Splice 08/14/20 | A | 8/27/2020 | JUSTINC | JUSTINC | Layout revisions | | Mechanical | 1373966 |
Electronic Plan | Splice 08/14/20 | / | 8/27/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1373923 |
Resubmittal 1 | Splice 08/14/20 | / | 8/27/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1373879 |
Mechanical | Splice 08/14/20 | D | 8/14/2020 | JUSTINC | JUSTINC | Appears the revisions will revise the OSA calculation?
Why providing (2) OSA ducts?
How complying with 2015 IECC C403.2.4.3?
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1366667 |
Electronic Plan | Splice 08/14/20 | / | 8/14/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1366662 |
Electrical | Splice 07/29/20 | A | 8/6/2020 | BERTHA | BERTHA | Splice to address inspector's comments. Revisions throughout. | | Electrical | 1361850 |
Electronic Plan | Splice 07/29/20 | / | 8/6/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1361823 |
Resubmittal 1 | Splice 07/29/20 | / | 8/4/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1360810 |
Electrical | Splice 07/29/20 | D | 7/30/2020 | BERTHA | BERTHA | Provide complete revisions - provide location of new panels A1 and A2, provide circuit numbers referencing A1 and A2, provide panel schedules A1 and A2, site plan indicating service gear and disconnects, etc.
Cloud all revisions.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1357857 |
Electronic Plan | Splice 07/29/20 | / | 7/30/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1357837 |
Mechanical | Splice 06/30/20 | A | 6/30/2020 | JUSTINC | JUSTINC | | | Mechanical | 1343348 |
Electronic Plan | Splice 06/30/20 | / | 6/30/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1343318 |
Hazmat | Original | N | 3/31/2020 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1303269 |
CO Springs Fire | Original | A | 3/31/2020 | CSFIRE | CSFIRE | Refernce CSFD review report online for inspection related details. (see full review) | csfdit | CO Springs Fire | 1303268 |
CO Springs DRE | Original | N | 3/27/2020 | AOSBORNE | AOSBORNE | Creation of ADA ramp on west side of building is so minor zoning finds applications not necessary. Creation of suite meets parking and permitted use (see full review) | | CO Springs DRE | 1302265 |
Zoning/Planning | Original | / | 3/26/2020 | AOSBORNE | AOSBORNE | In Current Review by AOSBORNE | | Zoning/Planning | 1301850 |
Plumbing | Original | A | 3/26/2020 | SHANEN | SHANEN | | | Plumbing | 1301670 |
Electrical | Original | A | 3/26/2020 | BERTHA | BERTHA | Re-approved | | Electrical | 1301653 |
Waste Water Div | Original | N | 3/26/2020 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | Waste Water Div | 1301514 |
Water Division | Original | N | 3/26/2020 | CSUREVIEW | CSUREVIEW | No new water service outside of building. DMM | dmakings | Water Division | 1301513 |
Mechanical | Original | A | 3/25/2020 | JUSTINC | JUSTINC | Plan switched from paper to electronic submittal. Electronic release for permit stamps applied | | Mechanical | 1301447 |
Electronic Plan | Original | / | 3/25/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1301444 |
Construction | Original | A | 3/25/2020 | MICHAELA | MICHAELA | | | Construction | 1301423 |
Electronic Plan | Original | / | 3/25/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1301422 |
Enumeration | Original | A | 3/25/2020 | AMY | AMY | | | Enumeration | 1301337 |
Electronic Plan | Original | / | 3/25/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1301328 |
Resubmittal 3 | Original | / | 3/25/2020 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1301088 |
Out to Review | Original | / | 3/13/2020 | GITA | GITA | 7194840480 BY CHRIS | | Out to Review | 1297937 |
Fire | Original | / | 3/10/2020 | | SCANNING | Location = Fire by SCANNING | | Fire | 1295978 |
Plan Coordinator | Original | / | 3/10/2020 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1295910 |
Construction | Original | D | 3/10/2020 | MICHAELA | MICHAELA | Some original comments still not addressed Correct Code Study Locate structural repairs on construction pages Correct fire barrier in section view Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1295909 |
Construction | Original | / | 3/6/2020 | | JANE | Location = Construction by JANE | | Construction | 1294850 |
Resubmittal 2 | Original | / | 3/6/2020 | JANE | JANE | Resubmittal #2 | | Resubmittal 2 | 1294848 |
Out to Review | Original | / | 2/21/2020 | | CSFIRE | Location = Out to Review by CSFIRE | dwithee | Out to Review | 1289063 |
Fire | Original | / | 2/13/2020 | | SCANNING | Location = Fire by SCANNING | | Fire | 1286274 |
Plan Coordinator | Original | / | 2/13/2020 | | SHELLEY | Location = Plan Coordinator by SHELLEY | | Plan Coordinator | 1286237 |
Construction | Original | D | 2/13/2020 | SHELLEY | SHELLEY | ES report ESL-1162 is for columns, plans do not indicate paint on columns. ESL - 1191 is a one sided wall assembly and N/A to this project; Added ESL-1190, which is the only ES report for beams - building does not meet requirements for assembly; Plans indicate gyp board column wrap - provide assembly; columns in wall still require individual encasement - verify; if using paint on columns, specify on plans; fire barrier continuity requires both sides of the fire barrier membranes to extend through the F/C assembly and terminate at deck above; see plans. No walk. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1286236 |
Construction | Original | / | 2/13/2020 | SHELLEY | SHELLEY | In Current Review by SHELLEY | | Construction | 1286117 |
Construction | Original | / | 2/12/2020 | | RITA | Location = Construction by RITA | | Construction | 1285807 |
Resubmittal 1 | Original | / | 2/12/2020 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 1285806 |
Out to Review | Original | / | 1/15/2020 | RDCUSER | RDCUSER | out to applicant | | Out to Review | 1276376 |
CO Springs DRE | Original | A | 1/15/2020 | RDCUSER | RDCUSER | Conditional use approval for Kids on Pikes - City File No. CPC CU 19-00122 per RBT (see full review) | | CO Springs DRE | 1276375 |
Plumbing | Original | A | 1/15/2020 | SHANEN | SHANEN | | | Plumbing | 1276371 |
Out to Review | Original | / | 1/15/2020 | GITA | GITA | Chris | | Out to Review | 1276326 |
Finished Bin | Original | / | 1/15/2020 | | GITA | Location = Finished Bin by GITA | | Finished Bin | 1276295 |
CO Springs Fire | Original | D | 12/23/2019 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1269847 |
Hazmat | Original | N | 12/23/2019 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1269846 |
Out to Review | Original | / | 12/23/2019 | | CSFIRE | Location = Out to Review by CSFIRE | rpeterson | Out to Review | 1269845 |
Fire | Original | / | 12/4/2019 | | AOSBORNE | Location = Fire by AOSBORNE | | Fire | 1263526 |
CO Springs DRE | Original | D | 12/4/2019 | AOSBORNE | AOSBORNE | SITE IS ZONED M1-UV, GENERAL RETAIL IS A CONDITIONAL USE SO A CONDITIONAL USE APPLICATION IS NEEDED. PLEASE SPECIFY WHICH "RETAIL" USE IS BEING PROPOSED TO SEE IF CONDITIONAL USE APPLICATION IS NEEDED OR NOT. PLEASE SITE PLAN AND PROVIDE PARKING CALCULATIONS TO ENSURE PARKING MEETS REQUIREMENTS. (see full review) | | CO Springs DRE | 1263525 |
Zoning/Planning | Original | / | 12/4/2019 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1263105 |
Plan Coordinator | Original | / | 12/4/2019 | | TCRIPPEN | Location = Plan Coordinator by TCRIPPEN | | Plan Coordinator | 1263095 |
Plumbing | Original | D | 12/4/2019 | TCRIPPEN | TCRIPPEN | A pages call for drinking fountain with bottle filler Alternate method variance (see web site you call Tim at 719- 327- 2947) required before plan can be approved,, plumbing pages scheduled high - low drinking but showing just one fountain. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1263094 |
Plumbing | Original | / | 11/27/2019 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1261663 |
Plan Coordinator | Original | / | 11/27/2019 | | JUSTINC | Location = Plan Coordinator by JUSTINC | | Plan Coordinator | 1261434 |
Mechanical | Original | A | 11/27/2019 | JUSTINC | JUSTINC | | | Mechanical | 1261433 |
Mechanical | Original | / | 11/27/2019 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Mechanical | 1261346 |
Mechanical | Original | / | 11/25/2019 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1260686 |
Plan Coordinator | Original | / | 11/23/2019 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1260572 |
Electrical | Original | A | 11/23/2019 | SHELBY | SHELBY | | | Electrical | 1260571 |
Electrical | Original | / | 11/19/2019 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1258797 |
Plan Coordinator | Original | / | 11/19/2019 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1258718 |
Construction | Original | D | 11/19/2019 | MICHAELA | MICHAELA | Is this a 2-story building? Sink in break room and bench in changing room must be ANSI compliant - add all notes. Locte all strucutral repairs/changes on architectural page Walk-through OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1258717 |
Construction | Original | / | 11/19/2019 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1258466 |
Construction | Original | / | 11/13/2019 | | SCANNING | Location = Construction by SCANNING | | Construction | 1256167 |
Plan Coordinator | Original | / | 11/13/2019 | | NELIDA | Location = Plan Coordinator by NELIDA | | Plan Coordinator | 1256135 |
Enumeration | Original | A | 11/12/2019 | AMY | AMY | New address assigned to west side of building. East end is 2250 Bott Ave. | | Enumeration | 1256080 |
Floodplain | Original | N | 11/12/2019 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7411328026) | | Floodplain | 1256062 |