Electrical | Splice 04/20/21 | A | 5/3/2021 | BERTHA | BERTHA | Added Kitchen Load Centers. | | Electrical | 1494366 |
Electronic Plan | Splice 04/20/21 | / | 5/3/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1494365 |
Resubmittal 3 | Splice 04/20/21 | / | 4/29/2021 | ANDREAL | ANDREAL | Resubmittal #3 | | Resubmittal 3 | 1493129 |
Electrical | Splice 04/20/21 | D | 4/28/2021 | BERTHA | BERTHA | All splice sheets must be resubmitted. I spoke with Gary at GE Johnson.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1492200 |
Resubmittal 2 | Splice 04/20/21 | / | 4/27/2021 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1491959 |
Electrical | Splice 04/20/21 | D | 4/26/2021 | BERTHA | BERTHA | Please address previous review comments. Revised load justifications were not provided. Please verify that current revisions were submitted.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1491201 |
Electronic Plan | Splice 04/20/21 | / | 4/26/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1491114 |
Resubmittal 1 | Splice 04/20/21 | / | 4/26/2021 | SHELLEY | SHELLEY | Resubmittal #1 | | Resubmittal 1 | 1491054 |
Electrical | Splice 04/20/21 | D | 4/21/2021 | BERTHA | BERTHA | Please provide revised Load Justification Panel NHGA and Panel NHSDB-H1 reflecting the load added with the new load centers. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1488911 |
Electronic Plan | Splice 04/20/21 | / | 4/21/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1488879 |
Construction | Splice 04/19/21 | A | 4/20/2021 | MICHAELA | MICHAELA | EJ for column protection | | Construction | 1488008 |
Construction | Splice 04/15/21 | A | 4/16/2021 | MICHAELA | MICHAELA | Hilti EJ for top of wall | | Construction | 1486376 |
Mechanical | Splice 04/07/21 | A | 4/15/2021 | JUSTINC | JUSTINC | Minor revisions to CFM and layout | | Mechanical | 1485856 |
Electronic Plan | Splice 04/07/21 | / | 4/15/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1485791 |
Construction | Splice 04/07/21 | A | 4/14/2021 | MICHAELA | MICHAELA | EJ for penetrations. | | Construction | 1485467 |
Resubmittal 1 | Splice 04/07/21 | / | 4/14/2021 | SAVANNAHT | SAVANNAHT | Resubmittal #1 | | Resubmittal 1 | 1485243 |
Construction | Splice 04/07/21 | D | 4/8/2021 | MICHAELA | MICHAELA | Locate where this occurs on a floor plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1481979 |
Mechanical | Splice 03/18/21 | A | 3/19/2021 | JUSTINC | JUSTINC | Revised 10" supply at G108 | | Mechanical | 1472471 |
Electronic Plan | Splice 03/18/21 | / | 3/19/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1472468 |
Mechanical | Splice 02/23/21 | A | 2/23/2021 | JUSTINC | JUSTINC | Revised for grease duct drain | | Mechanical | 1460629 |
Electrical | Splice 01/21/21 | A | 1/22/2021 | BERTHA | BERTHA | Revised for background changes. Utility Closet removed. | | Electrical | 1443976 |
Mechanical | Splice 01/21/21 | A | 1/22/2021 | JUSTINC | JUSTINC | Revised dampers, layout, and gas | | Mechanical | 1443931 |
Electronic Plan | Splice 01/21/21 | / | 1/22/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1443919 |
Electronic Plan | Splice 01/21/21 | / | 1/22/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1443913 |
Construction | Splice 01/21/21 | A | 1/22/2021 | MICHAELA | MICHAELA | Revise assemblies - floorplan | | Construction | 1443844 |
Plumbing | Splice 01/06/21 | A | 1/6/2021 | SHANEN | SHANEN | Delta 37 revisions: 1 revised sheet provided - PL002B adjusted garden level- kitchen area B waste and vent plan | | Plumbing | 1435556 |
Mechanical | Splice 12/22/20 | A | 12/23/2020 | JUSTINC | JUSTINC | Splice is to show removal of balancing dampers from grease ducts | | Mechanical | 1431607 |
Electronic Plan | Splice 12/22/20 | / | 12/23/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1431591 |
Mechanical | Original | A | 10/6/2020 | DALEH | DALEH | Approved as noted | | Mechanical | 1394653 |
Resubmittal 2 | Original | / | 10/6/2020 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1394393 |
Health Dept. | Original | A | 4/29/2020 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. CM | cmille96 | Health Dept. | 1315559 |
Health Dept. | Original | / | 4/29/2020 | HEALTHDEPT | HEALTHDEPT | | cmille96 | Health Dept. | 1315558 |
CO Springs Fire | Original | A | 3/23/2020 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1300364 |
Health Dept. | Original | D | 3/23/2020 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1300316 |
Mechanical | Original | D | 3/23/2020 | DALEH | DALEH | Need to provide oven specs as noted in key note 4,, Please label what hood this is Hood specs show hoods 1,2,3,4,5,6,7 Fans on roof are showing fans 1,3,4,5,6 where is fan 2 ? Fan specs only show fans 1,2,4,5 Floor plans only show Hoods 4,5,6,7 Show all hoods on plans existing and new, all new hoods to be labeled new Label freezers/coolers new or existing, If new provide refrigeration calculations Respond to all comments on plans not just response letter (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1300195 |
Electronic Plan | Original | / | 3/23/2020 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1300155 |
Electrical | Original | A | 3/23/2020 | BERTHA | BERTHA | | | Electrical | 1300134 |
Electronic Plan | Original | / | 3/22/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1300129 |
Plumbing | Original | A | 3/20/2020 | SHANEN | SHANEN | | | Plumbing | 1300092 |
Electronic Plan | Original | / | 3/20/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1300056 |
Electronic Plan | Original | / | 3/20/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1300052 |
Construction | Original | A | 3/20/2020 | MICHAELA | MICHAELA | | | Construction | 1300034 |
Electronic Plan | Original | / | 3/20/2020 | NANCY | NANCY | In Current Review by NANCY | | Electronic Plan | 1300022 |
Construction | Original | D | 3/20/2020 | MICHAELA | MICHAELA | Sign and date code study (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1300018 |
Electronic Plan | Original | / | 3/20/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1299949 |
Resubmittal 1 | Original | / | 3/20/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1299874 |
Out to Review | Original | / | 2/14/2020 | RITA | RITA | Bill 719-867-7034 | | Out to Review | 1286627 |
Finished Bin | Original | / | 2/13/2020 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1286222 |
Health Dept. | Original | D | 2/13/2020 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions, contact Environmental Health at 719-578-3199 option 3. KM | kmaldonado | Health Dept. | 1286190 |
Health Dept. | Original | / | 2/10/2020 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1284826 |
Water Division | Original | N | 2/10/2020 | CSUREVIEW | CSUREVIEW | No new water service outside of building. RDS | rsolberg | Water Division | 1284795 |
Waste Water Div | Original | N | 2/10/2020 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. RDS | rsolberg | Waste Water Div | 1284794 |
CSU Utilities | Original | / | 2/10/2020 | | CSFIRE | Location = CSU Utilities by CSFIRE | wtaylor | CSU Utilities | 1284392 |
Hazmat | Original | N | 2/10/2020 | CSFIRE | CSFIRE | | wtaylor | Hazmat | 1284391 |
CO Springs Fire | Original | A | 2/10/2020 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L (see full review) | csfdit | CO Springs Fire | 1284390 |
Fire | Original | / | 2/6/2020 | | CWEBB | Location = Fire by CWEBB | | Fire | 1283920 |
CO Springs DRE | Original | N | 2/6/2020 | CWEBB | CWEBB | Interior Remodel, no change of use (see full review) | | CO Springs DRE | 1283919 |
Zoning/Planning | Original | / | 2/5/2020 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1283406 |
Plan Coordinator | Original | / | 2/5/2020 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1283345 |
Plumbing | Original | D | 2/5/2020 | SHANEN | SHANEN | Provide piping materials schedule. All mechanical equipment condensate piping to be on M pages. All gas piping related items to be on M pages. Per section 802.1.1 Food handling. Each well of a multi-compartment sink shall discharge independently to a waste receptor. No walk.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1283344 |
Plumbing | Original | / | 2/5/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1283275 |
Plumbing | Original | / | 2/5/2020 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1283182 |
Plan Coordinator | Original | / | 2/5/2020 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1283175 |
Mechanical | Original | D | 2/5/2020 | DALEH | DALEH | THIS IS A PRELIMINARY REVIEW Label all rooms similar to sheet G100 How protecting penetrations through rated walls Show roof access See comments on sheet M200 about manufactured hood drawings on M-sheets No walk
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1283174 |
Mechanical | Original | / | 2/5/2020 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1283116 |
Mechanical | Original | / | 2/4/2020 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1282872 |
Plan Coordinator | Original | / | 2/4/2020 | | BERTHA | Location = Plan Coordinator by BERTHA | | Plan Coordinator | 1282826 |
Electrical | Original | D | 2/4/2020 | BERTHA | BERTHA | 1. Provide withstand rating for Panel EHGKA 2. Provide all panel schedules revised with scope of work (Panel NHGA1)
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1282823 |
Electrical | Original | / | 1/31/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electrical | 1282150 |
Electrical | Original | / | 1/30/2020 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1281556 |
Plan Coordinator | Original | / | 1/30/2020 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1281533 |
Construction | Original | D | 1/30/2020 | MICHAELA | MICHAELA | Please indicate all wall ratings that are for other than IBC Clarify purpose of all rated construction Correct inconsistencies and inaccuracies in wall types, hatches No walk-through (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1281532 |
Construction | Original | / | 1/30/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1281473 |
Construction | Original | / | 1/30/2020 | | SCANNING | Location = Construction by SCANNING | | Construction | 1281429 |
Plan Coordinator | Original | / | 1/30/2020 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1281409 |
Floodplain | Original | N | 1/30/2020 | AMY | AMY | | | Floodplain | 1281408 |
Enumeration | Original | N | 1/30/2020 | AMY | AMY | | | Enumeration | 1281406 |
Enumeration | Original | / | 1/30/2020 | | NELIDA | Location = Enumeration by NELIDA | | Enumeration | 1281329 |
Plan Coordinator | Original | / | 1/28/2020 | | AMY | Location = Plan Coordinator by AMY | | Plan Coordinator | 1280611 |
Enumeration | Original | / | 1/28/2020 | AMY | AMY | In Current Review by AMY | | Enumeration | 1280608 |
Enumeration | Original | / | 1/27/2020 | JAY | JAY | In Current Review by JAY | | Enumeration | 1279679 |
Floodplain | Original | N | 1/24/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5307003003) | | Floodplain | 1279605 |