Mechanical | Splice 06/13/22 | A | 6/14/2022 | DALEH | DALEH | Clouds Ducted return | | Mechanical | 1697859 |
Mechanical | Splice 06/06/22 | A | 6/6/2022 | DALEH | DALEH | clouds | | Mechanical | 1692870 |
Electrical | Splice 05/04/22 Electrical | A | 5/5/2022 | BERTHA | BERTHA | Revised power and special systems plans. Removed junction boxes. | | Electrical | 1677314 |
Electronic Plan | Splice 05/04/22 Electrical | / | 5/5/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1677290 |
Mechanical | Splice 05/04/22 | A | 5/5/2022 | DALEH | DALEH | Duct for two new vestibule's | | Mechanical | 1677081 |
Construction | Splice 05/04/22 | A | 5/4/2022 | MICHAELA | MICHAELA | Adding doors and walls to allow for stair pressurization. | | Construction | 1676926 |
Mechanical | Splice 05/02/22 | A | 5/2/2022 | DALEH | DALEH | Fan manufacturer change | | Mechanical | 1674402 |
Electrical | Splice 04/25/22 | A | 4/25/2022 | BERTHA | BERTHA | Revised plans - added storage closet. | | Electrical | 1671028 |
Electronic Plan | Splice 04/25/22 | / | 4/25/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1670968 |
Construction | Splice 04/25/22 | A | 4/25/2022 | MICHAELA | MICHAELA | Revise layout to add storage closet. | | Construction | 1670873 |
Mechanical | Splice 04/20/22 | A | 4/21/2022 | DALEH | DALEH | Clouds Pressure sensor locations | | Mechanical | 1668857 |
CO Springs Fire | Splice 01/18/22 | A | 4/19/2022 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 1667659 |
Plumbing | Splice 04/14/22 | A | 4/14/2022 | SHANEN | SHANEN | Delta 81 revisions: Adjusted sheet PL142. | | Plumbing | 1665108 |
Construction | Splice 01/18/22 | A | 4/13/2022 | MICHAELA | MICHAELA | Add oxygen rooms | | Construction | 1664436 |
Mechanical | Splice 01/18/22 | A | 4/7/2022 | DALEH | DALEH | clouds | | Mechanical | 1661732 |
Construction | Splice 01/18/22 | D | 4/7/2022 | MICHAELA | MICHAELA | Provide listing for wall type behind fire extinguisher or add a note that the cabinet is 1-hr. rated. Missed this in my first review. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1661613 |
Resubmittal 2 | Splice 01/18/22 | / | 4/6/2022 | ANDREAL | ANDREAL | Resubmittal #2 | | Resubmittal 2 | 1661593 |
CO Springs Hazmat | Splice 01/18/22 | A | 3/23/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | DTillery94 | CO Springs Hazmat | 1654277 |
CO Springs Fire | Splice 01/18/22 | A | 3/17/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1651862 |
Mechanical | Splice 01/18/22 | D | 3/10/2022 | DALEH | DALEH | Pending fire review. If fire decides the room does not need to be rated a splice to the Architectural pages indicating such will be required. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1647896 |
Resubmittal 1 | Splice 01/18/22 | / | 3/9/2022 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1647452 |
CO Springs Fire | Splice 01/18/22 | D | 2/1/2022 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1630930 |
Electrical | Splice 01/18/22 | A | 1/19/2022 | BERTHA | BERTHA | Revised background | | Electrical | 1623129 |
Mechanical | Splice 01/18/22 | D | 1/19/2022 | DALEH | DALEH | Waiting for fire review on med gas rooms Med gas rooms on exterior walls may require exterior ventilation per fire code Can't use house system for ventilation of med gas room reference 2015 IMC section 502.9.1 Dampers are not allowed in hazardous exhaust Need to include the exception for not requiring a fire damper See plans for better clarity to comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1622959 |
Electronic Plan | Splice 01/18/22 | / | 1/19/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1622912 |
Construction | Splice 01/18/22 | A | 1/19/2022 | MICHAELA | MICHAELA | Create oxygen room - Shaft termination detail | | Construction | 1622813 |
Construction | Splice 12/29/21 | A | 12/29/2021 | MICHAELA | MICHAELA | Add hoistway beam | | Construction | 1614206 |
Mechanical | Splice 12/16/21 | A | 12/17/2021 | DALEH | DALEH | Removal of dampers | | Mechanical | 1609698 |
Construction | Splice 12/13/21 | A | 12/14/2021 | MICHAELA | MICHAELA | Replacing listed assembly | | Construction | 1607483 |
Mechanical | Splice 12/06/21 | A | 12/8/2021 | DALEH | DALEH | | | Mechanical | 1604553 |
Resubmittal 1 | Splice 12/06/21 | / | 12/7/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1604087 |
Mechanical | Splice 12/06/21 | D | 12/7/2021 | DALEH | DALEH | What happened to all the previous notes that were shown on plan splice dated 11/11/21 ? The new splice changes need to be revised using the previous approved splice. Typical all new splice sheets. Always make changes from the most recent approved plan. No review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1603903 |
Electronic Plan | Splice 12/06/21 | / | 12/7/2021 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1603866 |
Construction | Splice 11/22/21 | A | 11/30/2021 | MICHAELA | MICHAELA | Modifications to comply with FAA regulations. | | Construction | 1599919 |
Resubmittal 1 | Splice 11/22/21 | / | 11/29/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1599329 |
Construction | Splice 11/22/21 | D | 11/23/2021 | MICHAELA | MICHAELA | Clarify the purpose of removing guards citing NFPA 418 and FAA AC150/5390-2C. Indicate the alternative fall protection that will be installed below the FATO in place of the guards. (Safety nets) (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1598307 |
Construction | Splice 11/22/21 | D | 11/22/2021 | MICHAELA | MICHAELA | Provide a code path to remove handrails from ramps and fall protection at helipad. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1597427 |
Mechanical | Splice 11/11/21 | A | 11/12/2021 | DALEH | DALEH | clouds | | Mechanical | 1592888 |
Electrical | Splice 11/09/21 | A | 11/10/2021 | BERTHA | BERTHA | Revised to indicate 125HP fire pump | | Electrical | 1592074 |
Electronic Plan | Splice 11/09/21 | / | 11/10/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1592031 |
Electrical | Splice 11/02/21 | A | 11/2/2021 | BERTHA | BERTHA | Revised Nourish Room. | | Electrical | 1588011 |
Electronic Plan | Splice 11/02/21 | / | 11/2/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1587949 |
Mechanical | Splice 11/02/21 | A | 11/2/2021 | DALEH | DALEH | clouds | | Mechanical | 1587849 |
Mechanical | Splice 10/21/21 | A | 10/21/2021 | DALEH | DALEH | cloud | | Mechanical | 1582328 |
Construction | Splice 10/07/21 | A | 10/8/2021 | MICHAELA | MICHAELA | Clarify wall types - location of protection | | Construction | 1575844 |
Mechanical | Splice 09/08/21 | A | 10/6/2021 | DALEH | DALEH | clouds | | Mechanical | 1574521 |
Plumbing | Splice 09/08/21 | A | 10/6/2021 | SHANEN | SHANEN | Delta 62R1 revisions: adjusted sheet PL142. | | Plumbing | 1574487 |
Electronic Plan | Splice 09/08/21 | / | 10/6/2021 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1574484 |
Construction | Splice 09/08/21 | A | 10/6/2021 | MICHAELA | MICHAELA | Rated penetration | | Construction | 1574474 |
Resubmittal 2 | Splice 09/08/21 | / | 10/5/2021 | ANDREAL | ANDREAL | Resubmittal #2 | | Resubmittal 2 | 1574402 |
Construction | Splice 09/08/21 | D | 9/24/2021 | MICHAELA | MICHAELA | Provide the plan page where the penetration will occur and add the penetration detail to the assemblies page. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1568131 |
Plumbing | Splice 09/08/21 | D | 9/24/2021 | SHANEN | SHANEN | Horizontal dry vent as described in key note 2 does not comply with section 905 VENT CONNECTIONS AND GRADES.905.4 Vertical rise of vent. Every dry vent shall rise vertically to a point not less than 6-inches above the flood level rim of the highest trap or trapped fixture being vented. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1568102 |
Mechanical | Splice 09/08/21 | D | 9/24/2021 | DALEH | DALEH | Remove all of the hilti penetration details from mechanical upload. Upload hilti details to a construction upload under this splice Relocate note to the side, so it is not covering up the floor plan image Show on the floor plan what size the square duct will be at each location this occurs (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1568083 |
Resubmittal 1 | Splice 09/08/21 | / | 9/24/2021 | SAVANNAHT | SAVANNAHT | Resubmittal #1 | | Resubmittal 1 | 1568004 |
Mechanical | Splice 09/08/21 | D | 9/9/2021 | DALEH | DALEH | Why is this sheet being submitted under this plan ? This scope of work under this plan number is for the addition 5th and 6th floor It does not appear that RBD even has a plan submitted for this area of work (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1559599 |
Construction | Splice 08/09/21 | A | 8/10/2021 | MICHAELA | MICHAELA | Introduce new listed assemblies | | Construction | 1544279 |
Mechanical | Splice 07/02/21 | A | 7/2/2021 | DALEH | DALEH | Clouds | | Mechanical | 1525488 |
Electrical | Splice 06/29/21 | A | 7/1/2021 | BERTHA | BERTHA | Added cameras, relocated patient lift, revised security plans. | | Electrical | 1524698 |
Mechanical | Splice 06/29/21 | A | 6/29/2021 | DALEH | DALEH | Clouds | | Mechanical | 1523822 |
Construction | Splice 06/29/21 | A | 6/29/2021 | MICHAELA | MICHAELA | | | Construction | 1523794 |
Plumbing | Splice 06/29/21 | A | 6/29/2021 | SHANEN | SHANEN | Delta 50 revisions: Adjusted sheet PL162 and PL171. | | Plumbing | 1523675 |
Construction | Splice 05/23/21 | A | 5/24/2021 | MICHAELA | MICHAELA | New rated top of wall detail | | Construction | 1504862 |
Elevators | Splice 02/23/21 | A | 2/24/2021 | ROBERTV | ROBERTV | Final Drawings for Alterations of Elevators | | Elevators | 1461546 |
Electrical | Splice 01/27/21 | A | 1/29/2021 | SHELBY | SHELBY | | | Electrical | 1448545 |
Electronic Plan | Splice 01/27/21 | / | 1/29/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1448346 |
Mechanical | Splice 01/27/21 | A | 1/28/2021 | DALEH | DALEH | clouds | | Mechanical | 1447560 |
Plumbing | Splice 01/27/21 | A | 1/28/2021 | SHANEN | SHANEN | Delta 039 revisions: P201 adjusted water service entry piping detail, PL142, PL152, PL162 adjusted waste & vent plan, PP151, PP152, PP161, PP162 adjusted domestic water plan | | Plumbing | 1447416 |
CSU Water | Splice 01/27/21 | N | 1/28/2021 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | CSU Water | 1447402 |
Construction | Splice 01/27/21 | A | 1/27/2021 | MICHAELA | MICHAELA | Revise listed assemblies - revise layout - additional details - structural revisions | | Construction | 1446978 |
CO Springs DRE | Original | A | 1/14/2021 | MALCURAN | MALCURAN | Approved. Added DRE stamp.MDA. | | CO Springs DRE | 1440067 |
Electrical | Original | A | 1/12/2021 | SHELBY | SHELBY | | | Electrical | 1438556 |
Resubmittal 5 | Original | / | 1/8/2021 | SHELLEY | SHELLEY | Resubmittal #5 | | Resubmittal 5 | 1437050 |
CO Springs Hazmat | Original | A | 1/6/2021 | CSFIRE | CSFIRE | Plans now acceptable. Fees to be paid through PBD. They include 3rd and 4th subsequent review fees. (see full review) | smitty91 | CO Springs Hazmat | 1435881 |
CO Springs Hazmat | Original | A | 1/6/2021 | CSFIRE | CSFIRE | | smitty91 | CO Springs Hazmat | 1435888 |
Mechanical | Original | A | 12/18/2020 | DALEH | DALEH | | | Mechanical | 1429495 |
Mechanical | Original | D | 12/18/2020 | DALEH | DALEH | Upload the previous approved Mechanical plans with next review It appears there are no new Mechanical changes since previous approval (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1429462 |
Electrical | Original | D | 12/17/2020 | SHELBY | SHELBY | Fire pump service lateral is under sized. Please call for consultation 719 203 8943. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1429282 |
Resubmittal 4 | Original | / | 12/17/2020 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1429280 |
CO Springs Hazmat | Original | D | 12/9/2020 | CSFIRE | CSFIRE | Sheet MP151 indicates a "NEW 4" CONDENSATE PUMP VENT UP THROUGH ROOF." This vent is approximately 16 feet from the location of the existing Medical Air Compressor Intake piping as shown on Sheet PG151. Per 18th edition of NFPA 99, Section 5.1.3.6.3.11(B): "The medical air intake shall be located a minimum of 7.6 m (25 ft) from ventilating system exhausts, fuel storage vents, combustion vents, plumbing vents, vacuum and WAGD discharges, or areas that can collect vehicular exhausts or other noxious fumes."
Please relocate the new condensate pump vent or provide a new location for the medical air compressor intake pipe. (see full review) | smitty91 | CO Springs Hazmat | 1424363 |
CSU Contract Admin. | Original | A | 11/30/2020 | CSUAPPSPRM | CSUAPPSPRM | Applicable development charges and fees paid 11/30/2020 MKL | mkluke | CSU Contract Admin. | 1419939 |
Electrical | Original | D | 11/25/2020 | SHELBY | SHELBY | An examination of the feeder schedule, per comment response letter, failed to yield the ampacity of the fire pump service ( See previous review comment 1). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1418863 |
Electronic Plan | Original | / | 11/25/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1418851 |
CO Springs Fire | Original | A | 11/25/2020 | CSFIRE | CSFIRE | You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1418776 |
CSU Contract Admin. | Original | D | 11/24/2020 | CSUAPPSPRM | CSUAPPSPRM | Requires payment of applicable development charges and fees. MKL | mkluke | CSU Contract Admin. | 1417917 |
Plumbing | Original | A | 11/24/2020 | SHANEN | SHANEN | | | Plumbing | 1417882 |
Construction | Original | A | 11/24/2020 | MICHAELA | MICHAELA | | | Construction | 1417721 |
Resubmittal 3 | Original | / | 11/23/2020 | ANDREAL | ANDREAL | Resubmittal #3 | | Resubmittal 3 | 1417245 |
CSU Contract Admin. | Original | D | 10/20/2020 | CSUAPPSPRM | CSUAPPSPRM | Requires payment of applicable development charges and fees. MKL | mkluke | CSU Contract Admin. | 1400716 |
CO Springs Hazmat | Original | D | 10/16/2020 | CSFIRE | CSFIRE | View plan review report here: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp Allow up to an hour for the reports to load to the servers. | smanning | CO Springs Hazmat | 1399258 |
CO Springs Fire | Original | D | 10/16/2020 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L
See CSFD Disapproval Comments at: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp (see full review) | csfdit | CO Springs Fire | 1399207 |
Electrical | Original | D | 10/12/2020 | SHELBY | SHELBY | 1. Show ampacity of fire pump service on one line. 2. Fire pump feeder disconnect ( 1000 amp) violates 695.4(B)(2)(b) NEC. 3. Please note on drawings the installation will comply 695.6 NEC (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1397267 |
CO Springs DRE | Original | A | 10/9/2020 | MALCURAN | MALCURAN | Approved per plans date stamped Oct 8, 2019 under AR DP 06-00145-A6MN19.MDA. | | CO Springs DRE | 1396359 |
Electronic Plan | Original | / | 10/8/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1396065 |
Mechanical | Original | A | 10/8/2020 | DALEH | DALEH | AS NOTED FOR FIRE DAMPERS | | Mechanical | 1395811 |
Zoning/Planning | Original | / | 10/7/2020 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1395511 |
Plumbing | Original | A | 10/7/2020 | SHANEN | SHANEN | | | Plumbing | 1395077 |
CSU Water | Original | A | 10/7/2020 | CSUREVIEW | CSUREVIEW | Comment addressed. MLW | mlwilliams | CSU Water | 1395040 |
CSU Waste Water | Original | A | 10/7/2020 | CSUREVIEW | CSUREVIEW | Comment addressed. MLW | mlwilliams | CSU Waste Water | 1395039 |
Gas/Elec. Utils | Original | A | 10/7/2020 | CSUREVIEW | CSUREVIEW | Comment addressed. MLW | mlwilliams | Gas/Elec. Utils | 1395038 |
Elevators | Original | A | 10/7/2020 | ERIC | ERIC | Need submittals for elevators 10 and 11 spliced into plans when available | | Elevators | 1394994 |
Construction | Original | A | 10/7/2020 | MICHAELA | MICHAELA | | | Construction | 1394827 |
Electronic Plan | Original | / | 10/7/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1394814 |
Resubmittal 2 | Original | / | 10/6/2020 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1394432 |
CO Springs DRE | Original | D | 9/30/2020 | MALCURAN | MALCURAN | Need Planning approved stamped plans uploaded | | CO Springs DRE | 1391551 |
CSU Contract Admin. | Original | D | 7/23/2020 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form disapproved. Additional development charges and fees due. Please contact Michelle at (719)668-7467 or mluukkonen@csu.org | mkluke | CSU Contract Admin. | 1354554 |
City Engr | Original | N | 7/22/2020 | PMORRIS | PMORRIS | | | City Engr | 1353748 |
Zoning/Planning | Original | / | 7/15/2020 | MALCURAN | MALCURAN | In Current Review by MALCURAN | | Zoning/Planning | 1350421 |
Hazmat | Original | D | 7/15/2020 | CSFIRE | CSFIRE | https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp (see full review) | smanning | Hazmat | 1350380 |
Electrical | Original | D | 7/14/2020 | SHELBY | SHELBY | No review is possible without review set. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1349526 |
Mechanical | Original | D | 7/14/2020 | DALEH | DALEH | The entire set of previous Mechanical sheets reviewed and disapproved on 1/31/2020 must be uploaded to ensure all comments have been addressed. No review of this submittal (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1349525 |
Gas/Elec. Utils | Original | D | 7/14/2020 | CSUREVIEW | CSUREVIEW | See previous comment: Please include a copy of the approved Development Plan. KDS | kschelhaas | Gas/Elec. Utils | 1349315 |
Water Division | Original | D | 7/14/2020 | CSUREVIEW | CSUREVIEW | See previous comment: Please include a copy of the approved Development Plan. KDS | kschelhaas | Water Division | 1349313 |
Waste Water Div | Original | D | 7/14/2020 | CSUREVIEW | CSUREVIEW | See previous comment: Please include a copy of the approved Development Plan. KDS | kschelhaas | Waste Water Div | 1349309 |
CO Springs Fire | Original | D | 7/13/2020 | CSFIRE | CSFIRE | Reference CSFD website for all comments: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp (see full review) | csfdit | CO Springs Fire | 1348611 |
CO Springs Fire | Original | D | 7/13/2020 | CSFIRE | CSFIRE | Reference CSFD website for all comments: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp (see full review) | csfdit | CO Springs Fire | 1348609 |
Plumbing | Original | D | 7/13/2020 | SHANEN | SHANEN | Pending construction approval (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1348291 |
Electronic Plan | Original | / | 7/13/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1348260 |
Elevators | Original | A | 7/10/2020 | ROBERTV | ROBERTV | Elevators #12 and #13 are being extended to the new finished 5th and 6th floors. New entrances, machines and suspension belts are being installed and will require all new Acceptance Testing for both elevators.
(RBD Note: 2 - Otis Gen2 Traction Elevators w/ Fire Rated Belts, both operate on Generator Power | | Elevators | 1347934 |
Electronic Plan | Original | / | 7/10/2020 | ROBERTV | ROBERTV | In Current Review by ROBERTV | | Electronic Plan | 1347914 |
Construction | Original | D | 7/10/2020 | MICHAELA | MICHAELA | I occupancies now require an Accessibility Plan A140 - Should be a 2-hr. shaft enclosure at stairs. A405 - Fire partition is required between sleeping rooms. Helistop Plan - Plans must be stamped and for construction. May not be deferred. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1347889 |
Electronic Plan | Original | / | 7/10/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1347662 |
Resubmittal 1 | Original | / | 7/10/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1347655 |
Out to Review | Original | / | 2/24/2020 | RITA | RITA | Mitchell 719-867-7050 | | Out to Review | 1289973 |
Finished Bin | Original | / | 2/24/2020 | | SCANNING | Location = Large finished bin. | | Finished Bin | 1289587 |
Health Dept. | Original | N | 2/24/2020 | HEALTHDEPT | HEALTHDEPT | Not applicable. | cmille96 | Health Dept. | 1289523 |
Health Dept. | Original | / | 2/20/2020 | | SCANNING | Location = Health Dept. by SCANNING | | Health Dept. | 1288730 |
City Engr | Original | D | 2/20/2020 | CSENGINEER | CSENGINEER | Insert a copy of the approved Development Plan in the building permit set. Plan set route to RBD. pvm | csengineer | City Engr | 1288704 |
Water Division | Original | D | 2/14/2020 | CSUREVIEW | CSUREVIEW | Same as previous comment AJ | ajuvera | Water Division | 1286664 |
Waste Water Div | Original | D | 2/14/2020 | CSUREVIEW | CSUREVIEW | Same as previous comment AJ | ajuvera | Waste Water Div | 1286663 |
Gas/Elec. Utils | Original | D | 2/14/2020 | CSUREVIEW | CSUREVIEW | Same as previous comment AJ | ajuvera | Gas/Elec. Utils | 1286661 |
Hazmat | Original | D | 2/13/2020 | CSFIRE | CSFIRE | Plans disapproved, please read disapproval comments. Plans forwarded to city engineer. (see full review) | smanning | Hazmat | 1286420 |
City Engr | Original | / | 2/13/2020 | | CSFIRE | Location = City Engr by CSFIRE | dwithee | City Engr | 1286407 |
CO Springs Fire | Original | D | 2/13/2020 | CSFIRE | CSFIRE | Refernce CSFD review report within plans for details (see full review) | csfdit | CO Springs Fire | 1286285 |
CO Springs DRE | Original | D | 2/11/2020 | MALCURAN | MALCURAN | Disapproved until one copy of the approved development plan set is submitted to the Regional Building Department in conjunction with the building permit application per the requirement on the minor amendment approval letter, date stamped October 8, 2019. | | CO Springs DRE | 1285330 |
Water Division | Original | D | 2/10/2020 | CSUREVIEW | CSUREVIEW | Provide a copy of the approved development plan (DP) in the plan set. Call UDS at 719-668-8259 with questions. RDS | rsolberg | Water Division | 1284778 |
Waste Water Div | Original | D | 2/10/2020 | CSUREVIEW | CSUREVIEW | Provide a copy of the approved development plan (DP) in the plan set. Call UDS at 719-668-8259 with questions. RDS | rsolberg | Waste Water Div | 1284776 |
Gas/Elec. Utils | Original | D | 2/10/2020 | CSUREVIEW | CSUREVIEW | Provide a copy of the approved development plan (DP) in the plan set. Call UDS at 719-668-8259 with questions. RDS | rsolberg | Gas/Elec. Utils | 1284775 |
CSU Contract Admin. | Original | / | 2/10/2020 | | CSUREVIEW | Location = CSU Contract Admin. by CSUREVIEW | rsolberg | CSU Contract Admin. | 1284687 |
CSU Utilities | Original | / | 2/10/2020 | | CSUREVIEW | Location = CSU Utilities by CSUREVIEW | rsolberg | CSU Utilities | 1284686 |
CSU Contract Admin. | Original | D | 2/10/2020 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF)showing existing and proposed load. If applicable, payment of development fees/charges will be required. Please contact our office at 719-668-8249 for additional information. AG
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf | aguerin | CSU Contract Admin. | 1284593 |
CSU Contract Admin. | Original | / | 2/6/2020 | | SCANNING | Location = CSU Contract Admin. by SCANNING | | CSU Contract Admin. | 1284166 |
Plan Coordinator | Original | / | 2/6/2020 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1284163 |
Plumbing | Original | D | 2/6/2020 | SHANEN | SHANEN | See construction reviewer comments regarding R-2 ANSI compliance at showers.as backgrounds may change. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1284161 |
Plumbing | Original | A | 2/6/2020 | SHANEN | SHANEN | | | Plumbing | 1284159 |
Plumbing | Original | / | 2/6/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1283933 |
Plumbing | Original | / | 2/6/2020 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1283846 |
Plan Coordinator | Original | / | 2/6/2020 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1283820 |
Electrical | Original | D | 2/6/2020 | SHELBY | SHELBY | Note: Electrical approval is not possible without Elevator comments successfully addressed. 1. Show location of fire pump controller relative to fire pump ( 695.12(A) NEC). 2. Remove equipment ground from fire pump service lateral. 3. Add grounded conductor ( Neutral) to fire pump service lateral. 4. Show method of compliance with 695.6(A)(2) NEC. 5. Indicate compliance with 695.7 NEC. 6. Include feeder 250A4G to feeder schedule ( See sheet E204). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1283819 |
Electrical | Original | / | 2/6/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1283707 |
Electrical | Original | / | 2/3/2020 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1282321 |
Plan Coordinator | Original | / | 2/3/2020 | | ROBERTV | Location = Plan Coordinator by ROBERTV | | Plan Coordinator | 1282308 |
Elevators | Original | D | 2/3/2020 | ROBERTV | ROBERTV | Need scope of work documents from Elevator Contractor
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1282306 |
Elevators | Original | / | 1/31/2020 | | DALEH | Location = Elevators by DALEH | | Elevators | 1282085 |
Mechanical | Original | D | 1/31/2020 | DALEH | DALEH | See extensive comments on sheet MH141 need clarification on supply fan serving stairwell See sheet MH142 for comment about room name and wall ratings around room Indicate on drawings how resisting the passage of smoke through smoke partitions See comments about where some ducts may need to have dampers See plans for all comments Return red lines with next review No walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1282083 |
Mechanical | Original | / | 1/30/2020 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1281466 |
Floodplain | Original | N | 1/30/2020 | AMY | AMY | | | Floodplain | 1281413 |
Enumeration | Original | N | 1/30/2020 | AMY | AMY | | | Enumeration | 1281412 |
Mechanical | Original | / | 1/30/2020 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1281366 |
Elevators | Original | / | 1/30/2020 | | SCANNING | Location = Elevators by SCANNING | | Elevators | 1281276 |
Plan Coordinator | Original | / | 1/30/2020 | | MICHAELA | Location = Plan Coordinator by MICHAELA | | Plan Coordinator | 1281261 |
Construction | Original | D | 1/30/2020 | MICHAELA | MICHAELA | Provide an IECC certificate for the addition Provide a listed assembly for the rated pre-cast walls On call sleeping rooms are accessory R-2 - separate accordingly Revise door schedule for R-2 occupancy Address R-2 ANSI compliance at showers. Page AC140 is out of order
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1281259 |
Construction | Original | / | 1/29/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Construction | 1280681 |
Enumeration | Original | N | 1/28/2020 | SCANNING | SCANNING | AV per sign off on label (ng) | | Enumeration | 1280624 |
Construction | Original | / | 1/28/2020 | | SCANNING | Location = Construction by SCANNING | | Construction | 1280622 |
Floodplain | Original | N | 1/28/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5307003003) | | Floodplain | 1280506 |