Mechanical | Splice 05/06/20 | A | 5/27/2020 | TCRIPPEN | TCRIPPEN | New splice remove exhaust fan, | | Mechanical | 1327494 |
Electronic Plan | Splice 05/06/20 | / | 5/27/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1327486 |
Resubmittal 2 | Splice 05/06/20 | / | 5/27/2020 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1327472 |
Mechanical | Splice 05/06/20 | D | 5/11/2020 | TCRIPPEN | TCRIPPEN | Provide the plan page that you are removing the fan from ' (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1320589 |
Electronic Plan | Splice 05/06/20 | / | 5/11/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1320575 |
Resubmittal 1 | Splice 05/06/20 | / | 5/11/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1320224 |
Mechanical | Splice 05/06/20 | D | 5/6/2020 | TCRIPPEN | TCRIPPEN | provide floor plan for splice no bathroom removed that I can see all so provide an occupant load to fixture count. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1318387 |
Electronic Plan | Splice 05/06/20 | / | 5/6/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1318371 |
Plumbing | Splice 05/06/20 | N | 5/6/2020 | SHANEN | SHANEN | No revised plumbing plans submitted for this splice request. | | Plumbing | 1318266 |
Electronic Plan | Splice 05/06/20 | / | 5/6/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1318259 |
Plumbing | Splice 04/16/20 | A | 4/17/2020 | SHANEN | SHANEN | Delta 3 revisions: P3.0 adjusted level 2 plumbing plan | | Plumbing | 1310817 |
Electronic Plan | Splice 04/16/20 | / | 4/17/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1310718 |
Plumbing | Splice 04/09/20 | A | 4/9/2020 | SHANEN | SHANEN | Delta 2 revisions: P1.2 adjusted plumbing fixture schedule and sink with dishwasher standpipe diagram, P3.0 adjusted level 2 plumbing plan and drawing note 9 | | Plumbing | 1307334 |
Electronic Plan | Splice 04/09/20 | / | 4/9/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1307298 |
Out to Review | Original | / | 3/12/2020 | RITA | RITA | Fred | | Out to Review | 1297667 |
Scanned/Finished Bin | Original | / | 3/11/2020 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1296469 |
To Be Scanned Bin | Original | / | 3/10/2020 | | GITA | Location = To Be Scanned Bin by GITA | | To Be Scanned Bin | 1296215 |
Plumbing | Original | A | 3/10/2020 | SHANEN | SHANEN | | | Plumbing | 1296213 |
Mechanical | Original | A | 3/10/2020 | TCRIPPEN | TCRIPPEN | okay | | Mechanical | 1296055 |
Plumbing | Original | D | 3/6/2020 | SHANEN | SHANEN | Provide alternate materials and methods application form to use accessible height drinking fountain with bottle filler in lieu of required high/low drinking fountain. Embolden backgrounds throughout. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1294979 |
CO Springs Fire | Original | A | 3/6/2020 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1294831 |
Hazmat | Original | N | 3/6/2020 | CSFIRE | CSFIRE | | rpeterson | Hazmat | 1294830 |
Construction | Original | A | 3/6/2020 | DANM | DANM | | | Construction | 1294809 |
Out to Review | Original | / | 3/6/2020 | GITA | GITA | Spencer 7194758133 | | Out to Review | 1294778 |
Plumbing | Original | / | 3/6/2020 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1294742 |
Plan Coordinator | Original | / | 3/6/2020 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1294679 |
Mechanical | Original | D | 3/6/2020 | DALEH | DALEH | Darken up backgrounds Protect from physical damage as required for outdoor units Show all routing, sizes and material for all condensate See plans for complete comments walk OK (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1294678 |
Mechanical | Original | / | 3/6/2020 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1294646 |
Mechanical | Original | / | 3/5/2020 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1294010 |
Plan Coordinator | Original | / | 3/5/2020 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1293987 |
Construction | Original | D | 3/5/2020 | DANM | DANM | (Updated) Provide allowable area calculations for entire building due to partial change of occupancy Walk -through review OK
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1293984 |
Construction | Original | / | 3/2/2020 | DANM | DANM | In Current Review by DANM | | Construction | 1292780 |
Construction | Original | / | 3/2/2020 | | GITA | Location = Construction by GITA | | Construction | 1292567 |
Resubmittal 1 | Original | / | 3/2/2020 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1292565 |
Out to Review | Original | / | 2/25/2020 | GITA | GITA | Spencer 7194758133 | | Out to Review | 1290356 |
Plan Coordinator | Original | / | 2/25/2020 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1290289 |
Mechanical | Original | D | 2/25/2020 | DALEH | DALEH | Need Construction comments addressed before an accurate Mechanical review can be accomplished. No review No walk (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1290288 |
Mechanical | Original | / | 2/25/2020 | DALEH | DALEH | In Current Review by DALEH | | Mechanical | 1290267 |
Mechanical | Original | / | 2/24/2020 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1289994 |
Plan Coordinator | Original | / | 2/24/2020 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1289955 |
Construction | Original | D | 2/24/2020 | DANM | DANM | Skills Training room considered A-3 occupancy - calculate load using 1 occ/20 sf (> 50 occupants) Recalculate occupant load Provide allowable area calculations for A-3/B occupancies Exit sign issues on Life Safety Plan Remodel is affecting lower level by removing stairs and separating lower form upper - show Life Safety Plan for lower level showing it is still code compliant for egress Separate submittal(s) and permit(s) required before lower level space(s) can be occupied (new addresses required) Clarify if walls and windows are new at mezzanine Floor infill configurations on Sheet S1.1 do not match demolished stair locations on architectural - clarify No walk-through review allowed (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1289954 |
Construction | Original | / | 2/24/2020 | DANM | DANM | In Current Review by DANM | | Construction | 1289633 |
Construction | Original | / | 2/13/2020 | | RITA | Location = Construction by RITA | | Construction | 1286356 |
Electrical | Original | A | 2/12/2020 | SHELBY | SHELBY | | | Electrical | 1285977 |
Water Division | Original | N | 2/12/2020 | CSUREVIEW | CSUREVIEW | No new water service outside of building. Backflow OK. KDS | kschelhaas | Water Division | 1285849 |
Waste Water Div | Original | N | 2/12/2020 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. KDS | kschelhaas | Waste Water Div | 1285847 |
Enumeration | Original | N | 2/12/2020 | BRENT | BRENT | | | Enumeration | 1285635 |
Out to Review | Original | / | 2/12/2020 | RDCUSER | RDCUSER | out to applicant | | Out to Review | 1285614 |
CO Springs DRE | Original | N | 2/12/2020 | RDCUSER | RDCUSER | Interior work only. Creation of human service which is permitted in C5. Parking meets requirements for whole site. (see full review) | | CO Springs DRE | 1285613 |
Out to Review | Original | / | 2/12/2020 | NELIDA | NELIDA | Spencer 719-475-8133 | | Out to Review | 1285593 |
Floodplain | Original | N | 2/12/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6316311006) | | Floodplain | 1285592 |