Plumbing | Original | A | 4/27/2020 | SHANEN | SHANEN | | | Plumbing | 1314774 |
Electronic Plan | Original | / | 4/27/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1314771 |
Resubmittal 6 | Original | / | 4/27/2020 | BECKYA | BECKYA | Resubmittal #6 | | Resubmittal 6 | 1314644 |
Plumbing | Original | D | 4/24/2020 | SHANEN | SHANEN | P1.00 Isometric A does not comply with section 1002.1 Fixture traps. Each plumbing fixture shall be separately trapped by a liquid seal trap. Correct isometric to show compliance. Providing a separate stand pipe is an option. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1313884 |
Electronic Plan | Original | / | 4/24/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1313879 |
Resubmittal 5 | Original | / | 4/23/2020 | BECKYA | BECKYA | Resubmittal #5 | | Resubmittal 5 | 1313651 |
Plumbing | Original | D | 4/23/2020 | SHANEN | SHANEN | Per section 504.7.1 Pan size and drain. The pan shall be drained by an indirect waste pipe having a diameter of not less than 3/4". Revise waste and vent piping isometric to show water heater pan discharging indirectly as current detail reflects a direct waste connection. Providing a separate stand pipe is one option. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1313377 |
Electronic Plan | Original | / | 4/23/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1313364 |
Resubmittal 4 | Original | / | 4/23/2020 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1313361 |
Plumbing | Original | D | 4/16/2020 | SHANEN | SHANEN | 1/2" water heater pan drain undersized and shall be connected by an indirect waste pipe. Per section 504.7.1 Pan size and drain. The pan shall be drained by an indirect waste pipe having a diameter of not less than 3/4". Revise waste and vent piping isometric and suspended electric water heater detail to show water heater pan discharging indirectly to an approved waste receptor. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1310237 |
Electronic Plan | Original | / | 4/16/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1310209 |
Resubmittal 3 | Original | / | 4/16/2020 | GITA | GITA | Resubmittal #3 | | Resubmittal 3 | 1310099 |
Electrical | Original | A | 4/14/2020 | BERTHA | BERTHA | | | Electrical | 1309231 |
Electronic Plan | Original | / | 4/14/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1309223 |
Plumbing | Original | D | 4/14/2020 | TCRIPPEN | TCRIPPEN | Clarify where T&P will drain to if not on this plan set a field splice will have to be done if work is done in other suite a separate permit is required hub drain and trap primer under sink is an ideal also provide a material schedule as to what can be used on this job, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1309063 |
Electronic Plan | Original | / | 4/14/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1309048 |
Mechanical | Original | A | 4/14/2020 | JUSTINC | JUSTINC | | | Mechanical | 1308963 |
Electronic Plan | Original | / | 4/14/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1308942 |
Resubmittal 2 | Original | / | 4/13/2020 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1308795 |
Hazmat | Original | N | 3/27/2020 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1302155 |
CO Springs Fire | Original | A | 3/27/2020 | CSFIRE | CSFIRE | Reference CSFD review report online for inspection information. (see full review) | csfdit | CO Springs Fire | 1302152 |
CO Springs DRE | Original | N | 3/27/2020 | RTEFERTILLER | RTEFERTILLER | (see full review) | | CO Springs DRE | 1301977 |
Zoning/Planning | Original | / | 3/26/2020 | RTEFERTILLER | RTEFERTILLER | In Current Review by RTEFERTILLER | | Zoning/Planning | 1301924 |
Electrical | Original | D | 3/23/2020 | BEND | BEND | Please provide electrical plans.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1300390 |
Water Division | Original | A | 3/23/2020 | CSUREVIEW | CSUREVIEW | No apparent conflicts. RDS | rsolberg | Water Division | 1300207 |
Waste Water Div | Original | N | 3/23/2020 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. RDS | rsolberg | Waste Water Div | 1300204 |
Mechanical | Original | D | 3/23/2020 | JUSTINC | JUSTINC | Mechanical review incomplete
Provide stamped mechanical plans showing how how heating,cooling,ventilating Appears a new mini-split will be added at server room? If so indicate on (M) sheets condensate routing and termination, provide refrigeration calculation for mini-split per 2015 IMC 1103.1. Indicate on plan if within allowable limits or over. If over also indicate on plan how protecting. Provide ventilation schedule per 2015 IMC 403.3.1.1 for all space associated with this permit.
No further review at this time.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1300176 |
Plumbing | Original | D | 3/23/2020 | SHANEN | SHANEN | A0.50 includes a plumbing schedule referencing MEP pages. No plumbing plans provided with this submittal. Provide MEP plans, if applicable, that comply with PPRBD commercial plan review requirements, Provide floor plan showing existing drinking fountains and service sink. Note: Drinking fountains shall be within a travel distance of 500 feet and not more than one floor above or below the level containing this tenant space per section 403.5.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1300168 |
Electronic Plan | Original | / | 3/23/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1300149 |
Electronic Plan | Original | / | 3/23/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1300136 |
Construction | Original | A | 3/20/2020 | MICHAELA | MICHAELA | | | Construction | 1300073 |
Electronic Plan | Original | / | 3/20/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1300066 |
Enumeration | Original | A | 3/20/2020 | BRENT | BRENT | | | Enumeration | 1299922 |
Electronic Plan | Original | / | 3/20/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1299917 |
Resubmittal 1 | Original | / | 3/20/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1299875 |
Electronic Plan | Original | / | 3/20/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1299868 |
Electrical | Original | A | 3/6/2020 | BEND | BEND | | | Electrical | 1294712 |
Enumeration | Original | D | 3/6/2020 | BRENT | BRENT | No permit history for Suite 350. Last interior remodel plan for 3rd floor shows this area as Suite 380. Show separation of all tenant spaces on the 3rd floor with suite numbers on the site plan with area of work highlighted. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1294689 |
Out to Review | Original | / | 3/6/2020 | RITA | RITA | David walking | | Out to Review | 1294653 |
Floodplain | Original | N | 3/6/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418215018) | | Floodplain | 1294651 |