Canceled Plans | Splice 04/09/20 | / | 10/29/2020 | ADMIN | ADMIN | Electronic Plan automatically cancelled due to inactivity. | | Canceled Plans | 1405087 | Electrical | Splice 04/09/20 | D | 5/1/2020 | SHELBY | SHELBY | Please address original review comments 1,2,3,4,5,and 6. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1316920 | Electronic Plan | Splice 04/09/20 | / | 5/1/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1316903 | Resubmittal 4 | Splice 04/09/20 | / | 4/29/2020 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1315634 | Electrical | Splice 04/09/20 | D | 4/28/2020 | BERTHA | BERTHA | See previous review comment.
The entire Electrical Plan set is not resubmitted. Please submit all E sheets.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1315386 | Electronic Plan | Splice 04/09/20 | / | 4/28/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1315365 | Resubmittal 3 | Splice 04/09/20 | / | 4/27/2020 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1314780 | Electrical | Splice 04/09/20 | D | 4/24/2020 | BERTHA | BERTHA | Review stopped - Please comply with previous review comment - ALL electrical sheets must be resubmitted. Please submit entire electrical plan set.
Please contact Rebekah Allen for assistance with re-submittal process. Beckya@pprbd.org
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1314324 | Electronic Plan | Splice 04/09/20 | / | 4/24/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1314316 | Resubmittal 2 | Splice 04/09/20 | / | 4/24/2020 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1313881 | Electrical | Splice 04/09/20 | D | 4/15/2020 | BERTHA | BERTHA | Review stopped - all electrical sheets must be resubmitted.
Comply with previous review comment #2 - Provide feeder over current size on the one-line for all new service gear or service gear used in the scope of work.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1309872 | Electronic Plan | Splice 04/09/20 | / | 4/15/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1309865 | Resubmittal 1 | Splice 04/09/20 | / | 4/15/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1309729 | Electrical | Splice 04/09/20 | D | 4/10/2020 | SHELBY | SHELBY | 1. Show GEC size for new transformers on one line. 2. Show feeder over current size for new gear on one line( R205D, R205E etc.). 3. Show SCA and AIC for all new gear on one line. 4. Clearly identify new equipment and conductors on one line ( See dark line weights for DP29 feeder, DPBA feeder etc.). 5. Please provide DP29 load summary. 6. Please provide 2015 IECC calculation. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1307678 | Plumbing | Splice 04/09/20 | A | 4/9/2020 | TCRIPPEN | TCRIPPEN | okay | | Plumbing | 1307288 | Electronic Plan | Splice 04/09/20 | / | 4/9/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1307261 |
|
| |
|