Electrical | Splice 11/23/20 | A | 12/10/2020 | BERTHA | BERTHA | Revised panel locations. | | Electrical | 1425306 |
Electronic Plan | Splice 11/23/20 | / | 12/10/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1425290 |
Resubmittal 2 | Splice 11/23/20 | / | 12/9/2020 | ANDREAL | ANDREAL | Resubmittal #2 | | Resubmittal 2 | 1424873 |
Electrical | Splice 11/23/20 | D | 12/2/2020 | BERTHA | BERTHA | Provide series rated listed combinations.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1421165 |
Electronic Plan | Splice 11/23/20 | / | 12/2/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1421159 |
Resubmittal 1 | Splice 11/23/20 | / | 12/1/2020 | JAY | JAY | Resubmittal #1 | | Resubmittal 1 | 1420894 |
Electrical | Splice 11/23/20 | D | 11/30/2020 | SHELBY | SHELBY | Changes to engineered plans must be made by the design professional. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1420034 |
Electronic Plan | Splice 11/23/20 | / | 11/30/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1420030 |
Construction | Splice 10/22/20 | A | 10/23/2020 | MICHAELA | MICHAELA | Revise counter | | Construction | 1402692 |
Mechanical | Splice 07/16/20 | A | 7/16/2020 | DALEH | DALEH | revised hood | | Mechanical | 1350738 |
Electronic Plan | Splice 07/16/20 | / | 7/16/2020 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1350712 |
CO Springs DRE | Original | A | 6/8/2020 | AODOM | AODOM | approved: Restaurant use permitted in PBC zone - parking met for commercial center | | CO Springs DRE | 1332732 |
Zoning/Planning | Original | / | 6/8/2020 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1332715 |
Health Dept. | Original | A | 6/5/2020 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. AB | abrannon | Health Dept. | 1332240 |
Health Dept. | Original | / | 6/5/2020 | HEALTHDEPT | HEALTHDEPT | | abrannon | Health Dept. | 1332226 |
Enumeration | Original | A | 6/4/2020 | BRENT | BRENT | | | Enumeration | 1331791 |
Health Dept. | Original | D | 5/7/2020 | HEALTHDEPT | HEALTHDEPT | Health department plan review is in process and not yet approved. For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1318796 |
Electrical | Original | A | 5/1/2020 | SHELBY | SHELBY | | | Electrical | 1316866 |
Mechanical | Original | A | 5/1/2020 | DALEH | DALEH | no changes previously approved by Justin | | Mechanical | 1316698 |
Plumbing | Original | A | 5/1/2020 | SHANEN | SHANEN | See P-4 for engineer's notes in regards to 4/13/20 plumbing reviewer comments about fixtures in bar area. | | Plumbing | 1316693 |
Electronic Plan | Original | / | 5/1/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1316688 |
Construction | Original | A | 5/1/2020 | MICHAELA | MICHAELA | | | Construction | 1316670 |
Mechanical | Original | D | 5/1/2020 | DALEH | DALEH | Same comments as Construction (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1316663 |
Construction | Original | D | 5/1/2020 | MICHAELA | MICHAELA | This plan has been previously approved. Cloud changes made to this submittal or resubmit the previously approved set. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1316613 |
Electronic Plan | Original | / | 5/1/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1316602 |
Enumeration | Original | D | 4/30/2020 | BRENT | BRENT | The first, second, and fifth comments from 4/9/20 were not addressed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1316428 |
Electronic Plan | Original | / | 4/30/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1316417 |
Resubmittal 1 | Original | / | 4/30/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1316296 |
Plumbing | Original | A | 4/21/2020 | SHANEN | SHANEN | See P-4 for engineer's notes in regards to 4/13/20 plumbing reviewer comments about fixtures in bar area. | | Plumbing | 1312589 |
CO Springs DRE | Original | A | 4/20/2020 | AODOM | AODOM | Interior Finish Approved - use permitted in PBC | | CO Springs DRE | 1311518 |
Hazmat | Original | N | 4/17/2020 | CSFIRE | CSFIRE | 40# CO2 declared | dwithee | Hazmat | 1310799 |
CO Springs Fire | Original | A | 4/17/2020 | CSFIRE | CSFIRE | Reference CSFD review report online for redline comments and inspection information. (see full review) | csfdit | CO Springs Fire | 1310798 |
Plumbing | Original | D | 4/13/2020 | SHANEN | SHANEN | Discharge bar area plumbing fixtures to grease waste. Hand sink in bar area shall be directly connected to the drainage system. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1308541 |
CO Springs DRE | Original | D | 4/13/2020 | AODOM | AODOM | -core and shell permit not yet approved for CO - please contact susanna.dalsing@coloradosprings.gov regarding inspection requirements | | CO Springs DRE | 1308523 |
Electronic Plan | Original | / | 4/13/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1308517 |
Water Division | Original | N | 4/10/2020 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | Water Division | 1307875 |
Waste Water Div | Original | N | 4/10/2020 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | Waste Water Div | 1307873 |
Electrical | Original | A | 4/10/2020 | SHELBY | SHELBY | | | Electrical | 1307731 |
Zoning/Planning | Original | / | 4/10/2020 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1307721 |
Mechanical | Original | A | 4/10/2020 | JUSTINC | JUSTINC | | | Mechanical | 1307716 |
Electronic Plan | Original | / | 4/10/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1307672 |
Construction | Original | A | 4/9/2020 | MICHAELA | MICHAELA | | | Construction | 1307530 |
Electronic Plan | Original | / | 4/9/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1307416 |
Enumeration | Original | D | 4/9/2020 | BRENT | BRENT | Address on code study form says "unit 148". Units are for apartments. Commercial buildings are Suites. Zip code missing from code study form. Code study shows 2 tax schedule numbers. Show only the one relevant to this project. Legal description shown on code study is incorrect. Suite number missing from address on Mechanical, Plumbing and Electrical pages. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1307137 |
Electronic Plan | Original | / | 4/9/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1307120 |
Floodplain | Original | N | 3/31/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6325106035) | | Floodplain | 1303076 |