Construction | Splice 06/13/22 | A | 7/8/2022 | LBENNETT | LBENNETT | Revised roorm TG019 use to clean supply; revised adjacent wall type | | Construction | 1710789 |
Electronic Plan | Splice 06/13/22 | / | 7/8/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1710769 |
Resubmittal 2 | Splice 06/13/22 | / | 7/8/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #2 | | Resubmittal 2 | 1710579 |
Mechanical | Splice 06/13/22 | A | 7/6/2022 | JUSTINC | JUSTINC | | | Mechanical | 1709100 |
Construction | Splice 06/13/22 | D | 7/6/2022 | LBENNETT | LBENNETT | 1. Include all courtesy notes from the approved plan/splice in the resubmittal; 2. G100: Please clarify how the wall (double purple line) is changing and compliance with 509.4.2; 3. A101: Specify the wall type that was revised on G100 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1708901 |
Electronic Plan | Splice 06/13/22 | / | 7/6/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1708591 |
Resubmittal 1 | Splice 06/13/22 | / | 7/5/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #1 | | Resubmittal 1 | 1708143 |
Mechanical | Splice 06/13/22 | D | 6/13/2022 | JUSTINC | JUSTINC | Provide revised (A) sheets showing that the wall rating was revised.
MECHANICAL REVIEW INCOMPLETE
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1697643 |
Electronic Plan | Splice 06/13/22 | / | 6/13/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1697632 |
Mechanical | Splice 05/11/22 | A | 5/13/2022 | JUSTINC | JUSTINC | Layout and note revisions | | Mechanical | 1682049 |
Construction | Splice 05/11/22 | A | 5/13/2022 | LBENNETT | LBENNETT | Revised incidental use walls | | Construction | 1681980 |
Electronic Plan | Splice 05/11/22 | / | 5/13/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1681708 |
Mechanical | Splice 04/20/22 | A | 5/5/2022 | JUSTINC | JUSTINC | Layout revised | | Mechanical | 1677149 |
Electronic Plan | Splice 04/20/22 | / | 5/5/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1677143 |
Construction | Splice 04/20/22 | A | 5/2/2022 | LBENNETT | LBENNETT | Added wall types | | Construction | 1674578 |
Electronic Plan | Splice 04/20/22 | / | 5/2/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1674539 |
Resubmittal 1 | Splice 04/20/22 | / | 5/2/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #1 | | Resubmittal 1 | 1674133 |
Mechanical | Splice 04/20/22 | D | 4/21/2022 | JUSTINC | JUSTINC | Transfer air shown in soiled linen G105 is passing through a smoke partition. How will this resist the passage of smoke per 2015 IMC 607.5.6
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1668955 |
Electronic Plan | Splice 04/20/22 | / | 4/21/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1668924 |
Construction | Splice 04/20/22 | D | 4/21/2022 | LBENNETT | LBENNETT | Please clarify wall continuity for revised walls of assembly height type B (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1668871 |
Electronic Plan | Splice 04/20/22 | / | 4/21/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1668785 |
Plumbing | Splice 03/22/22 | A | 3/22/2022 | SHANEN | SHANEN | Delta 089 revisions: Adjusted sheet PLD101 and PL101. | | Plumbing | 1653869 |
Mechanical | Original | A | 3/16/2022 | JUSTINC | JUSTINC | | | Mechanical | 1651152 |
Electronic Plan | Original | / | 3/16/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1651145 |
Resubmittal 2 | Original | / | 3/16/2022 | AUSTINK | AUSTINK | Resubmittal #2 | | Resubmittal 2 | 1651116 |
CO Springs Fire | Original | A | 3/3/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1644693 |
Mechanical | Original | D | 2/28/2022 | JUSTINC | JUSTINC | Clarify return air paths with rated construction, appears air will be trapped in spaces How protecting?When ducts are indicated as penetrating a rated assembly a fire or fire/smoke damper is required. When intent is to use a code section and exception to not install a damper then a sheet note indicating code section and all exceptions used are to be provided on the plan. Tag at penetration accordingly. If dampers are existing i
ndicate on plan. See plan for clouded areas (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1642676 |
Electronic Plan | Original | / | 2/28/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1642642 |
Construction | Original | A | 2/28/2022 | LBENNETT | LBENNETT | | | Construction | 1642631 |
Electronic Plan | Original | / | 2/28/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1642336 |
Resubmittal 1 | Original | / | 2/25/2022 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1641778 |
CO Springs DRE | Original | N | 2/22/2022 | ESHAFER | ESHAFER | Interior remodel only: No change in footprint, No change to exterior, No change in parking, No change in occupancy. Remodel of loading dock area. (see full review) | | CO Springs DRE | 1640038 |
Zoning/Planning | Original | / | 2/17/2022 | ESHAFER | ESHAFER | In Current Review by ESHAFER | | Zoning/Planning | 1638650 |
CO Springs Fire | Original | D | 2/17/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1638239 |
CSU Waste Water | Original | N | 2/16/2022 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CM | CoreyM | CSU Waste Water | 1637974 |
CSU Water | Original | N | 2/16/2022 | CSUREVIEW | CSUREVIEW | No apparent conflicts. CM | CoreyM | CSU Water | 1637972 |
CO Springs Hazmat | Original | N | 2/16/2022 | CSFIRE | CSFIRE | Submitted by: Tillery, Demarcus
HazMat N/A | DTillery94 | CO Springs Hazmat | 1637961 |
Plumbing | Original | A | 12/22/2021 | SHANEN | SHANEN | | | Plumbing | 1611866 |
Mechanical | Original | D | 12/21/2021 | JUSTINC | JUSTINC | Clarify how all rated penetrations will be protected
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1611603 |
Electronic Plan | Original | / | 12/21/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1611582 |
Electrical | Original | A | 12/21/2021 | SHELBY | SHELBY | | | Electrical | 1611480 |
Electronic Plan | Original | / | 12/21/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1611475 |
Construction | Original | D | 12/21/2021 | LBENNETT | LBENNETT | G100/A101: Please clarify whether rooms G105, G106, & G121 are incidental uses (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1611434 |
Electronic Plan | Original | / | 12/20/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1610754 |
Enumeration | Original | N | 12/20/2021 | BRENT | BRENT | | | Enumeration | 1610658 |
Electronic Plan | Original | / | 12/20/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1610654 |
Floodplain | Original | N | 4/14/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5307003003) | | Floodplain | 1309300 |