Electrical | Original | A | 6/25/2020 | SHELBY | SHELBY | | | Electrical | 1341554 |
Electrical | Original | D | 6/25/2020 | SHELBY | SHELBY | Plan is incomplete. Consultation is available after design professional review of requirements. 719 203 8943 or 719 659 1182 | | Electrical | 1341370 |
Electronic Plan | Original | / | 6/25/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1341362 |
Resubmittal 3 | Original | / | 6/23/2020 | GITA | GITA | Resubmittal #3 | | Resubmittal 3 | 1340442 |
Electrical | Original | D | 6/22/2020 | SHELBY | SHELBY | 1. Show location of new panel L2A. 2. Label all new and relocated electrical equipment/devices with panel and circuit number ( Relocated lights etc.). 3. Review and address all required items. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1339725 |
Resubmittal 2 | Original | / | 6/17/2020 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1337733 |
Electrical | Original | D | 6/10/2020 | SHELBY | SHELBY | No changes made (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1334282 |
Electronic Plan | Original | / | 6/10/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1334278 |
Mechanical | Original | N | 6/8/2020 | JUSTINC | JUSTINC | | | Mechanical | 1333086 |
Electronic Plan | Original | / | 6/8/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1333084 |
Resubmittal 1 | Original | / | 6/8/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1333075 |
Hazmat | Original | N | 6/4/2020 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1331454 |
CO Springs Fire | Original | N | 6/4/2020 | CSFIRE | CSFIRE | no fire final (see full review) | csfdit | CO Springs Fire | 1331452 |
CO Springs DRE | Original | N | 5/29/2020 | AODOM | AODOM | Interior Remodel, no exterior work. no change of use. (see full review) | | CO Springs DRE | 1328935 |
Electrical | Original | D | 5/27/2020 | SHELBY | SHELBY | Please review link for requirements https://www.pprbd.org/Downloads/CommercialHandout/Com%20Elect%20reqs.pdf (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1327850 |
Plumbing | Original | N | 5/27/2020 | SHANEN | SHANEN | No plumbing plans provided. No plumbing scope of work, issue no permit. | | Plumbing | 1327577 |
Electronic Plan | Original | / | 5/27/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1327566 |
Water Division | Original | N | 5/27/2020 | CSUREVIEW | CSUREVIEW | No new water service outside of building. MLW | mlwilliams | Water Division | 1327352 |
Waste Water Div | Original | N | 5/27/2020 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | Waste Water Div | 1327348 |
Zoning/Planning | Original | / | 5/27/2020 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1327297 |
Mechanical | Original | D | 5/26/2020 | DALEH | DALEH | Remove Electrical scope of work from Mechanical sheets and only label as M-sheets (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1327053 |
Construction | Original | A | 5/26/2020 | BPHILLIPS | BPHILLIPS | | | Construction | 1327031 |
Electronic Plan | Original | / | 5/26/2020 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1326572 |
Enumeration | Original | A | 5/18/2020 | AMY | AMY | Single tenant building | | Enumeration | 1323926 |
Electronic Plan | Original | / | 5/18/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1323920 |
Floodplain | Original | N | 5/13/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6318107003) | | Floodplain | 1322151 |