Mechanical | Splice 06/30/22 | A | 7/7/2022 | TCRIPPEN | TCRIPPEN | Approved : New splice pages for duct sizes. HVAC piping, Condensation drain lines, Gas lines, And Exhaust Venting. | | Mechanical | 1709342 |
Construction | Splice 03/10/22 | A | 3/28/2022 | SHELLEY | SHELLEY | Fire extinguisher locations | | Construction | 1656467 |
Resubmittal 1 | Splice 03/10/22 | / | 3/28/2022 | SHELLEY | SHELLEY | Resubmittal #1 | | Resubmittal 1 | 1656240 |
CO Springs Fire | Splice 03/10/22 | A | 3/17/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1651927 |
Construction | Splice 03/10/22 | D | 3/10/2022 | SHELLEY | SHELLEY | Provide details for fire extinguisher cabinets in rated construction. Are cabinets rated? If not, rating must be met behind cabinets in their recesses. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1648080 |
CO Springs Fire | Splice 02/14/22 | A | 3/1/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! | csfdit | CO Springs Fire | 1643250 |
Construction | Splice 02/14/22 | A | 2/14/2022 | LBENNETT | LBENNETT | Added beam and column listings to stair b | | Construction | 1636519 |
Electronic Plan | Splice 02/14/22 | / | 2/14/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1636503 |
Mechanical | Splice 10/20/21 | A | 10/20/2021 | TCRIPPEN | TCRIPPEN | Approved. | | Mechanical | 1581879 |
City Engr | Splice 10/05/21 | A | 10/13/2021 | PMORRIS | PMORRIS | | | City Engr | 1578004 |
CO Springs DRE | Splice 10/05/21 | A | 10/8/2021 | ACOOPER | ACOOPER | No change to building footprint or parking spaces | | CO Springs DRE | 1575950 |
Zoning/Planning | Splice 10/05/21 | / | 10/5/2021 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1574349 |
Zoning/Planning | Splice 08/23/21 | / | 10/5/2021 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1574183 |
Plumbing | Splice 10/05/21 | A | 10/5/2021 | SHANEN | SHANEN | Delta 84, 111 revisions: adjusted sheet 2P-110A, 2P-111A and 2P-114A. | | Plumbing | 1573916 |
Electronic Plan | Splice 10/05/21 | / | 10/5/2021 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1573900 |
Construction | Splice 10/05/21 | A | 10/5/2021 | LBENNETT | LBENNETT | Roof assembly RA4 @ connector; rated wall assembly R443 @ shaft adjacent to stair A: add rated ceiling assembly @ elev machine room and LDF; other revisions | | Construction | 1573894 |
Electronic Plan | Splice 10/05/21 | / | 10/5/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1573649 |
Plumbing | Splice 08/23/21 | A | 9/27/2021 | SHANEN | SHANEN | Delta 126 revisions: adjusted sheet 2P-101B. | | Plumbing | 1569241 |
Construction | Splice 08/23/21 | A | 9/27/2021 | LBENNETT | LBENNETT | Removed guard shack foundation; minor layout revisions; see AM&M for accessibility @ back to back doors | | Construction | 1569226 |
Electronic Plan | Splice 08/23/21 | / | 9/27/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1568998 |
Resubmittal 1 | Splice 08/23/21 | / | 9/27/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1568850 |
City Engr | Splice 08/23/21 | A | 8/30/2021 | PMORRIS | PMORRIS | | | City Engr | 1554440 |
CO Springs DRE | Splice 08/23/21 | A | 8/25/2021 | ACOOPER | ACOOPER | Changes approved as shown | | CO Springs DRE | 1552998 |
Electrical | Splice 08/23/21 | A | 8/25/2021 | BERTHA | BERTHA | Power and lighting revisions throughout. Revised panel schedules. | | Electrical | 1552614 |
Electronic Plan | Splice 08/23/21 | / | 8/25/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1552541 |
Mechanical | Splice 08/23/21 | A | 8/24/2021 | TCRIPPEN | TCRIPPEN | Approved new splice see clouded changes | | Mechanical | 1552159 |
Electronic Plan | Splice 08/23/21 | / | 8/24/2021 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1552064 |
Zoning/Planning | Splice 08/23/21 | / | 8/24/2021 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1552054 |
Plumbing | Splice 08/23/21 | D | 8/24/2021 | SHANEN | SHANEN | 2P-101B: Per narrative there are revisions to this sheet. Cloud all revisions that pertain to this splice request. 2P-110B: Sheet not listed in narrative.Provide only revised sheets. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1552049 |
Construction | Splice 08/23/21 | D | 8/24/2021 | LBENNETT | LBENNETT | 2S305: Please clarify whether guard shack is conditioned 2A101A: Please clarify wall location and wall type @ room 1802 2I102-2I103: Please clarify compliance with ANSI requirements at back to back doors
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1551924 |
Electronic Plan | Splice 08/23/21 | / | 8/24/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1551800 |
Construction | Splice 08/06/21 | A | 8/6/2021 | LBENNETT | LBENNETT | COS-2/G206 revised fastening details | | Construction | 1543408 |
Electronic Plan | Splice 08/06/21 | / | 8/6/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1543385 |
CO Springs DRE | Splice 06/21/21 | A | 6/22/2021 | ACOOPER | ACOOPER | Changes approved as shown | | CO Springs DRE | 1520471 |
Electrical | Splice 06/21/21 | A | 6/22/2021 | BERTHA | BERTHA | Revisions throughout - revised power, lighting, schedules and one-line. | | Electrical | 1520276 |
Zoning/Planning | Splice 06/21/21 | / | 6/22/2021 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1520230 |
Mechanical | Splice 06/21/21 | A | 6/22/2021 | TCRIPPEN | TCRIPPEN | Approved New splice see individual pages for changes, | | Mechanical | 1520195 |
Electronic Plan | Splice 06/21/21 | / | 6/22/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1520173 |
Plumbing | Splice 06/21/21 | A | 6/22/2021 | SHANEN | SHANEN | Delta 60, 74, 86, 87 revisions: Adjusted sheet 1P-002, 2P-101A, 2P-111A and 2P-114A. | | Plumbing | 1520157 |
Construction | Splice 06/21/21 | A | 6/22/2021 | LBENNETT | LBENNETT | New UL assemblies V455 & I501; other misc revisions | | Construction | 1520115 |
Electronic Plan | Splice 06/21/21 | / | 6/21/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1519939 |
Electrical | Splice 03/18/21 | A | 5/18/2021 | BERTHA | BERTHA | Revisions throughout. | | Electrical | 1502178 |
Electrical | Splice 03/18/21 | D | 5/3/2021 | BERTHA | BERTHA | 1. Provide number of poles for new ATS 2. Provide location of all electrical equipment - NLGS, 60A disconnect, T-NLGS, 30A disconnect, etc.
4 hours review time.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1494675 |
Electronic Plan | Splice 03/18/21 | / | 5/3/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1494370 |
CO Springs DRE | Splice 03/18/21 | A | 4/30/2021 | ACOOPER | ACOOPER | Changes are approved as shown | | CO Springs DRE | 1493972 |
CO Springs Fire | Splice 03/18/21 | A | 4/30/2021 | CSFIRE | CSFIRE | | csfdit | CO Springs Fire | 1493856 |
Zoning/Planning | Splice 03/18/21 | / | 4/28/2021 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1492582 |
Construction | Splice 03/18/21 | A | 4/27/2021 | LBENNETT | LBENNETT | New beam listing; misc revisions | | Construction | 1491633 |
Electronic Plan | Splice 03/18/21 | / | 4/27/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1491460 |
Resubmittal 1 | Splice 03/18/21 | / | 4/26/2021 | SHELLEY | SHELLEY | Resubmittal #1 | | Resubmittal 1 | 1491008 |
CO Springs DRE | Splice 03/18/21 | D | 3/24/2021 | DFOXX | DFOXX | Please provide further information regarding the scope of work, any exterior changes, change of use or intended use. Please provide code study form or email me at drew.foxx@coloradosprings.gov providing the aforementioned information. | | CO Springs DRE | 1474975 |
City Engr | Splice 03/18/21 | N | 3/23/2021 | PMORRIS | PMORRIS | | | City Engr | 1474173 |
Electrical | Splice 03/18/21 | D | 3/23/2021 | BERTHA | BERTHA | Provide all conductor size, type and quantity - see red line on one-line Cloud specific revisions only, not entire sheets/schedules - see lighting and panel schedules Remove clouds from previous revisions.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1473879 |
CO Springs Fire | Splice 03/18/21 | D | 3/22/2021 | CSFIRE | CSFIRE | scope of changes is unclear - identify revisions for this specific splice to make scope of work clear. | dwithee | CO Springs Fire | 1473579 |
Zoning/Planning | Splice 03/18/21 | / | 3/22/2021 | DFOXX | DFOXX | In Current Review by DFOXX | | Zoning/Planning | 1473229 |
Electronic Plan | Splice 03/18/21 | / | 3/22/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1473145 |
Mechanical | Splice 03/18/21 | A | 3/22/2021 | TCRIPPEN | TCRIPPEN | okay: See all pages for changes | | Mechanical | 1473131 |
Electronic Plan | Splice 03/18/21 | / | 3/22/2021 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1473069 |
Plumbing | Splice 03/18/21 | A | 3/19/2021 | SHANEN | SHANEN | Delta 43 revisions: 2P-102, 2P-111A, 2P-111B, 2P-112, 2P-113, 2P-114A, 2P-114B, 3P-202 adjusted plumbing plans. Delta 42 revisions: 4P-401 adjusted elevator sump detail | | Plumbing | 1472791 |
Elevators | Splice 03/18/21 | A | 3/19/2021 | ERIC | ERIC | No apparent changes to elevators | | Elevators | 1472750 |
CSU Water | Splice 03/18/21 | N | 3/19/2021 | CSUREVIEW | CSUREVIEW | No apparent conflicts. mjg | mgackle | CSU Water | 1472677 |
CSU Waste Water | Splice 03/18/21 | N | 3/19/2021 | CSUREVIEW | CSUREVIEW | No apparent conflicts. mjg | mgackle | CSU Waste Water | 1472676 |
Gas/Elec. Utils | Splice 03/18/21 | N | 3/19/2021 | CSUREVIEW | CSUREVIEW | No apparent conflicts. mjg | mgackle | Gas/Elec. Utils | 1472675 |
Construction | Splice 03/18/21 | D | 3/19/2021 | LBENNETT | LBENNETT | Please cloud only revisions for this splice - clearly identifying the change Remove all clouds for previously approved splices Remove sheets without revisions
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1472658 |
Enumeration | Splice 03/18/21 | A | 3/19/2021 | BRENT | BRENT | | | Enumeration | 1472449 |
Electronic Plan | Splice 03/18/21 | / | 3/19/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1472442 |
- Not Set - | 11/13/20 underground plumbing N01021 | / | 3/3/2021 | | VERONIKAP | Location = - Not Set - by VERONIKAP | | - Not Set - | 1465230 |
Mechanical | Splice 02/26/21 | A | 3/1/2021 | TCRIPPEN | TCRIPPEN | okay new splice exhaust fans | | Mechanical | 1463403 |
Construction | Splice 02/26/21 | A | 2/27/2021 | LBENNETT | LBENNETT | New roof openings in COS-1 | | Construction | 1463243 |
Electronic Plan | Splice 02/26/21 | / | 2/27/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1463242 |
CO Springs Fire | Splice 02/17/21 | N | 2/23/2021 | CSFIRE | CSFIRE | changes to fire sprinkler system must be submitted as deferred submittal by fire sprinkler contractor | csfdit | CO Springs Fire | 1460893 |
Electrical | Splice 02/17/21 | A | 2/22/2021 | BERTHA | BERTHA | Revised power and schedules. | | Electrical | 1460080 |
Electronic Plan | Splice 02/17/21 | / | 2/22/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1459967 |
Mechanical | Splice 02/17/21 | A | 2/18/2021 | TCRIPPEN | TCRIPPEN | Added Fire Dampers | | Mechanical | 1458185 |
Electronic Plan | Splice 02/17/21 | / | 2/18/2021 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1458139 |
Construction | Splice 02/17/21 | A | 2/18/2021 | LBENNETT | LBENNETT | Wall type revisions @ rooms E1120 & E1902A | | Construction | 1458095 |
Electronic Plan | Splice 02/17/21 | / | 2/18/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1458085 |
Electronic Plan | Splice 02/17/21 | / | 2/18/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1457885 |
Electronic Plan | Original | / | 11/17/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1413744 |
Electrical | Original | A | 11/13/2020 | BERTHA | BERTHA | | | Electrical | 1412500 |
Electronic Plan | Original | / | 11/13/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1412469 |
Plumbing | 11/13/20 underground plumbing N01021 | A | 11/13/2020 | TCRIPPEN | TCRIPPEN | Approved added plumbing to foundation permit | | Plumbing | 1412206 |
Enumeration | Original | A | 11/12/2020 | BRENT | BRENT | | | Enumeration | 1411391 |
Electronic Plan | Original | / | 11/12/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1411387 |
Resubmittal 7 | Original | / | 11/11/2020 | BECKYA | BECKYA | Resubmittal #7 | | Resubmittal 7 | 1411323 |
Mechanical | Original | A | 11/10/2020 | TCRIPPEN | TCRIPPEN | okay | | Mechanical | 1410675 |
Mechanical | Original | D | 11/10/2020 | TCRIPPEN | TCRIPPEN | Provide refrigeration calculations for allowable amounts for IT room E1902A , Section 606.2.2 how complying with smoke detectors when over 2000 cfm in returns, need shaft detail how protecting. NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1410425 |
Electronic Plan | Original | / | 11/10/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1410269 |
Electronic Plan | Original | / | 11/9/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1409538 |
City Engr | Original | A | 11/5/2020 | JDAGNILLO | JDAGNILLO | | | City Engr | 1408463 |
Electrical | Original | D | 11/4/2020 | BERTHA | BERTHA | COS-1
1. Comply with previous review comment 1 - Provide all fault current information on one-line sheet. 2. Comply with previous review comment 4 - RU2A is indicated as overloaded - see panel schedule on sheet COS-1 3E-310
COS-2
1. Comply with previous review comment 1 - Provide all fault current information on one-line sheet. 2. Comply with previous review comment 4 - Provide all conductor size, type and quantity on one-line - provide all feeder schedules on one-line diagram sheet. 3. Comply with previous review comment 8 - Provide elevator pit details in compliance with Art 620 - 2017 NEC on the electrical plan set. 4. Comply with previous review comment 9 - Provide UL Raised Floor Modular Wiring System listing as part of the electrical plan set.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1407740 |
Electronic Plan | Original | / | 11/4/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1407679 |
Mechanical | Original | / | 11/4/2020 | WEBSITE | WEBSITE | Overtime Authorized for Mechanical by JEFF SPLINTER | Jsplinter | Mechanical | 1407652 |
Electrical | Original | / | 11/4/2020 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by JEFF SPLINTER | Jsplinter | Electrical | 1407651 |
CO Springs DRE | Original | A | 11/3/2020 | LTHELEN | LTHELEN | ok to permit per - AR DP 06-00282-A2MN20 | | CO Springs DRE | 1407586 |
Zoning/Planning | Original | / | 11/2/2020 | LTHELEN | LTHELEN | In Current Review by LTHELEN | | Zoning/Planning | 1406896 |
CSU Water | Original | A | 11/2/2020 | CSUREVIEW | CSUREVIEW | Comments addressed. RDS | rsolberg | CSU Water | 1406679 |
CSU Waste Water | Original | A | 11/2/2020 | CSUREVIEW | CSUREVIEW | Comments addressed. RDS | rsolberg | CSU Waste Water | 1406678 |
Gas/Elec. Utils | Original | A | 11/2/2020 | CSUREVIEW | CSUREVIEW | Comments addressed. RDS | rsolberg | Gas/Elec. Utils | 1406677 |
Enumeration | Original | A | 11/2/2020 | BRENT | BRENT | | | Enumeration | 1406653 |
Electronic Plan | Original | / | 11/2/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1406648 |
Resubmittal 6 | Original | / | 11/2/2020 | BECKYA | BECKYA | Resubmittal #6 | | Resubmittal 6 | 1406435 |
City Engr | Original | D | 10/27/2020 | PMORRIS | PMORRIS | Upload a copy of the approved Development Plan into the building permit set. | | City Engr | 1403901 |
CO Springs Fire | Original | A | 10/23/2020 | CSFIRE | CSFIRE | you are responsible for reading the comments on the CSFD website as they contain inspection infomration: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
All approvals subject to final inspection | csfdit | CO Springs Fire | 1402864 |
CO Springs Fire | Original | A | 10/23/2020 | CSFIRE | CSFIRE | you are responsible for reading the comments on the CSFD website as they contain inspection infomration: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
All approvals subject to final inspection | csfdit | CO Springs Fire | 1402863 |
Mechanical | Original | D | 10/23/2020 | TCRIPPEN | TCRIPPEN | Provide refrigeration calculations for allowable amounts for IT room, Section 606.2.2 how complying with smoke detectors when over 2000 cfm in returns, Only fire dampers are required for green rated walls not fire / smoke just a heads up Shaft ends at floor level of second floor how protecting shaft at second level, How protecting rated wall room 3700C, (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1402756 |
Electrical | Original | D | 10/23/2020 | BERTHA | BERTHA | COS - 1
1. Provide SCA and SCCR or AIC at all of the following locations as they pertain to the project - please add SCCR to Short Circuit Schedule. a. All new panelboards and switchboards b. All new transfer equipment c. All new industrial control panels d. All new air conditioning and refrigeration equipment e. At any of the above locations when refedfor tap conductors. 2. Homogenize new ATS labeling - ATS-EM on on-line vs ATS-HEM in Short Circuit Schedule. 3. Clarify New (N) or existing - ATS-SB 4. Panel RU2A is overloaded. 5. Provide revised schedules for all panels revised in the scope of work. Include volt amps on all branch circuits and calculated load of panel. Panels RT1D, M1A, SDPR2A, SDPR2B, etc.
COS - 2
1. Provide SCA and SCCR or AIC at all of the following locations as they pertain to the project - please add SCCR to Short Circuit Schedule. a. All new panelboards and switchboards b. All new transfer equipment c. All new industrial control panels d. All new air conditioning and refrigeration equipment e. At any of the above locations when refedfor tap conductors. 2. Comply 250.102(C)(1) - T15 3. Comply 250.66 - T15 4. Provide all conductor size, type and quantity on the one-line diagram. 5. Provide MTS amps. 6. Clarify if MTS or ATS. See one-line vs West Gate Enlarged Plan 7. Provide compliance with 250.66 on the one-line diagram. 8. Provide elevator pit details. 9. Provide Raised Floor Modular Wiring System listing (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1402704 |
CO Springs DRE | Original | D | 10/22/2020 | LTHELEN | LTHELEN | Include approved development plan in building permit set. | | CO Springs DRE | 1401929 |
Zoning/Planning | Original | / | 10/21/2020 | LTHELEN | LTHELEN | In Current Review by LTHELEN | | Zoning/Planning | 1401762 |
CSU Water | Original | D | 10/21/2020 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Water | 1401734 |
CSU Waste Water | Original | D | 10/21/2020 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Waste Water | 1401733 |
Gas/Elec. Utils | Original | D | 10/21/2020 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | Gas/Elec. Utils | 1401732 |
Electronic Plan | Original | / | 10/21/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1401581 |
Electronic Plan | Original | / | 10/21/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1401356 |
Plumbing | Original | A | 10/20/2020 | SHANEN | SHANEN | | | Plumbing | 1401145 |
Construction | Original | A | 10/20/2020 | LBENNETT | LBENNETT | | | Construction | 1400988 |
Enumeration | Original | A | 10/19/2020 | BRENT | BRENT | | | Enumeration | 1400452 |
Electronic Plan | Original | / | 10/19/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1400448 |
Elevators | Original | A | 10/19/2020 | ERIC | ERIC | 2 ThyssenKrupp conventional machineroom type hydraulic elevators, no generator | | Elevators | 1400265 |
Electronic Plan | Original | / | 10/19/2020 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1400228 |
Resubmittal 5 | Original | / | 10/18/2020 | BECKYA | BECKYA | Resubmittal #5 | | Resubmittal 5 | 1399961 |
CSU Contract Admin. | Original | A | 10/8/2020 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved & all applicable Development fees/charges paid. AG | aguerin | CSU Contract Admin. | 1396095 |
CSU Contract Admin. | Original | / | 10/8/2020 | CSUAPPSPRM | CSUAPPSPRM | | aguerin | CSU Contract Admin. | 1396094 |
CSU Contract Admin. | Original | D | 10/6/2020 | CSUAPPSPRM | CSUAPPSPRM | Commercial Water Meter Sizing Form approved 10/6/2020 - Requires payment of applicable development fees/charges. Please contact our office at 719-668-8249 for additional information. AG | aguerin | CSU Contract Admin. | 1394471 |
Mechanical | Original | D | 10/1/2020 | TCRIPPEN | TCRIPPEN | Remove all colored from walls, Rated walls will colored by our team review stopped (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1392322 |
Electrical | Original | D | 10/1/2020 | BERTHA | BERTHA | Review stopped.
Clarify scope of work.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1392047 |
Electronic Plan | Original | / | 10/1/2020 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1392030 |
City Engr | Original | D | 9/30/2020 | PMORRIS | PMORRIS | Upload a copy of the approved Development Plan. | | City Engr | 1391179 |
CO Springs DRE | Original | D | 9/29/2020 | LTHELEN | LTHELEN | Recieve approval of the development plan and include the approved development plan in the building permit set. | | CO Springs DRE | 1390778 |
Electronic Plan | Original | / | 9/29/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1390351 |
Electronic Plan | Original | / | 9/29/2020 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1390350 |
Electronic Plan | Original | / | 9/29/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1390349 |
CO Springs Hazmat | Original | N | 9/29/2020 | CSFIRE | CSFIRE | | wtaylor | CO Springs Hazmat | 1390202 |
CO Springs Fire | Original | D | 9/29/2020 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L
See CSFD Disapproval Comments at: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp | csfdit | CO Springs Fire | 1390200 |
Zoning/Planning | Original | / | 9/28/2020 | LTHELEN | LTHELEN | In Current Review by LTHELEN | | Zoning/Planning | 1390102 |
Plumbing | Original | D | 9/28/2020 | SHANEN | SHANEN | Provide piping materials schedule. Provide water pipe size analysis data, see 2015 IPC appendix E. All condensate piping to be on mechanical plans.Remove all references to condensate piping from plumbing plans and provide on mechanical plans. Provide gpm and/or square footage served by components of the roof drain system. All gas piping related items to be on mechanical plans.Remove all references to gas piping from plumbing plans and provide on mechanical plans. Provide sizing on isometric/ riser diagrams. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1390050 |
Gas/Elec. Utils | Original | D | 9/28/2020 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set prior to our approval on Water Division and Wastewater Div. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | Gas/Elec. Utils | 1389974 |
CSU Waste Water | Original | D | 9/28/2020 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set prior to our approval on Water Division and Wastewater Div. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Waste Water | 1389973 |
CSU Water | Original | D | 9/28/2020 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set prior to our approval on Water Division and Wastewater Div. Contact Utilities Development Services at 719-668-8259 with any questions. DMM | dmakings | CSU Water | 1389971 |
Health Dept. | Original | N | 9/28/2020 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT0042875 is valid from 07/20/2020-01/20/2021. CM | cmille96 | Health Dept. | 1389955 |
Elevators | Original | D | 9/28/2020 | ERIC | ERIC | 2 ThyssenKrupp conventional hydraulic elevators 1-2500#, 1-4000#, no generator power, battery lowering only
Page 2E-111A Elevator pit gfci outlets and pit lighting must be on separate circuits for each elevator
Page 2E-121A Elevator machineroom only requires smoke detector and elevator pits only require heat detectors
Page 2E-123 Smoke and heat detectors are not required at top of elevator hoistways
Ensure that elevator machineroom FCU is not located above elevator hydraulic tank units or controllers . (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1389872 |
Construction | Original | D | 9/25/2020 | LBENNETT | LBENNETT | CSF: Specify whether remodel of COS-1 is in scope; specify area of scope; clarify whether rated horizontal assemblies will be used (code data indicates no, code study form indicates yes); indicate reason for building sprinklers G101:Please show compliance with 506.2.3 for each story; show accessory occupancy calculations, per story; Update code references to 2015 IBC; clarify whether new building contains horizontal assemblies and where they are located (not required for construction type or separation); Clarify location of 2-hr shaft enclosures, 1-hour shaft enclosures, and walls that resist the passage of smoke; Clarify whether auditorium is in scope – if so, please specify egress sizing, aisle width, travel distance and common path of travel per 1029 and update occupant load per 1004.4 for fixed seating G104: 1-hour fire barriers required for stair and elevator shafts; 1-hour fire barrier or walls that resist the passage of smoke required for incidental boiler room use; provide missing egress door tag; update occupant load of auditorium per 1004.4 for areas of fixed seating if auditorium is in scope; clarify whether using rated or unrated floor assemblies, providing listing or code path for rating if using G104-G106: Provide 1-hour fire barrier type G201: Please provide a 1-hour wall assembly for the stair and elevator enclosures G202: Please clarify location of rated floor and provide a listed assembly or code path for the rating G206: Clarify wall labels; detail A4 doesn’t match listing; specify compliance with 711.2.3 for the horizontal assemblies G600B: Provide listing or code path for each assembly used G604: Please update listings 2A101-2A103: Please show 1-hour fire barriers on floor plans and legend 2A301-2A305: Specify rated wall and floor/ceiling types on section views 2A401: 1-hour fire barriers required for shaft walls; 1-hour horizontal assembly required to comply with 713 as noted; show compliance with 707.5.1 as noted 2A402: 1-hour fire barriers required for shaft walls 2A403: Please clarify riser height 2A405: Specify rated wall types 2A406: Is security booth unheated? 2I401 & 2I402: Locate coat hooks within accessible reach range; Provide vertical grab bar per 604.5.1 See plans for all comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1389490 |
Electronic Plan | Original | / | 9/22/2020 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1386726 |
Enumeration | Original | A | 9/22/2020 | BRENT | BRENT | | | Enumeration | 1386500 |
Electronic Plan | Original | / | 9/22/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1386489 |
Triage | Original | / | 9/21/2020 | BECKYA | BECKYA | Phased submittal upgraded to PHASED COMMERCIAL BLDG (THRU FINISH). All required departments reset to pending. | | Triage | 1386295 |
Resubmittal 4 | Original | / | 9/21/2020 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1386294 |
CO Springs DRE | Original | A | 8/13/2020 | LTHELEN | LTHELEN | ok to permit. Final Landscape Plan and Irrigation plan must be submitted directly to Daniel Gould - City Landscape Architect. | | CO Springs DRE | 1365927 |
Zoning/Planning | Original | / | 8/11/2020 | LTHELEN | LTHELEN | In Current Review by LTHELEN | | Zoning/Planning | 1364067 |
Resubmittal 3 | Original | / | 8/10/2020 | JAY | JAY | Resubmittal #3 | | Resubmittal 3 | 1363584 |
City Engr | Original | A | 8/10/2020 | PMORRIS | PMORRIS | Foundation only | | City Engr | 1363282 |
Plan Coordinator | Original | D | 8/6/2020 | LBENNETT | LBENNETT | Disapprove all remaining departments to allow plan to be resubmitted (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1361949 |
City Engr | Original | D | 8/6/2020 | PMORRIS | PMORRIS | Upload the Stormwater Enterprise (SWENT) approved Grading, Erosion and Stormwater Quality Control Plan into the building permit. | | City Engr | 1361782 |
Enumeration | Original | A | 8/5/2020 | BRENT | BRENT | | | Enumeration | 1360902 |
Electronic Plan | Original | / | 8/5/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1360881 |
Resubmittal 2 | Original | / | 8/4/2020 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1360811 |
CO Springs DRE | Original | D | 7/15/2020 | LTHELEN | LTHELEN | Receive approval of the development plan and include approved development plan in the set. | | CO Springs DRE | 1349842 |
City Engr | Original | D | 7/15/2020 | PMORRIS | PMORRIS | The foundation only permit requires the Stormwater Enterprise (SWENT) approved Grading and Erosion Control Plan (GECP) Upload the SWENT approved GECP | | City Engr | 1349774 |
Zoning/Planning | Original | / | 7/14/2020 | LTHELEN | LTHELEN | In Current Review by LTHELEN | | Zoning/Planning | 1349427 |
CO Springs Fire | Original | A | 7/13/2020 | CSFIRE | CSFIRE | FOUNDATION ONLY | csfdit | CO Springs Fire | 1348625 |
Construction | Original | A | 7/10/2020 | LBENNETT | LBENNETT | | | Construction | 1347977 |
Electronic Plan | Original | / | 7/10/2020 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1347743 |
Enumeration | Original | A | 7/10/2020 | BRENT | BRENT | | | Enumeration | 1347600 |
Electronic Plan | Original | / | 7/10/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1347589 |
Resubmittal 1 | Original | / | 7/10/2020 | GITA | GITA | Resubmittal #1 | | Resubmittal 1 | 1347548 |
Health Dept. | Original | N | 7/7/2020 | HEALTHDEPT | HEALTHDEPT | Construction activity permit PT0042875 is valid from 7/20/2020-1/20/2021. - MR | MelissaLovato | Health Dept. | 1345870 |
Water Division | Original | A | 6/30/2020 | CSUREVIEW | CSUREVIEW | Approved for Foundation Only. mjg | mgackle | Water Division | 1342920 |
Waste Water Div | Original | A | 6/30/2020 | CSUREVIEW | CSUREVIEW | Approved for Foundation Only. mjg | mgackle | Waste Water Div | 1342919 |
Gas/Elec. Utils | Original | A | 6/30/2020 | CSUREVIEW | CSUREVIEW | Approved for Foundation Only. mjg | mgackle | Gas/Elec. Utils | 1342918 |
Water Division | Original | / | 6/30/2020 | CSUREVIEW | CSUREVIEW | | mgackle | Water Division | 1342915 |
CSU Contract Admin. | Original | N | 6/29/2020 | CSUAPPSPRM | CSUAPPSPRM | ** FOUNDATION ONLY - NO SERVICES THIS PLAN/PERMIT.
NOTE: Approved Commercial Water Meter Sizing Form and paid utility receipt required at time of finish Plan. AG | aguerin | CSU Contract Admin. | 1342574 |
CSU Contract Admin. | Original | / | 6/29/2020 | CSUAPPSPRM | CSUAPPSPRM | | aguerin | CSU Contract Admin. | 1342573 |
CSU Contract Admin. | Original | D | 6/25/2020 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable development fees/charges. Please contact our office at aguerin@csu.org for additional information and to request an estimate. AG
CWMSF available online at: https://www.csu.org/CSUDocuments/commercialwatermetersizingform.pdf | aguerin | CSU Contract Admin. | 1341820 |
CO Springs DRE | Original | D | 6/24/2020 | LTHELEN | LTHELEN | Receive approval of the development plan and include approved development plan in the set. | | CO Springs DRE | 1340601 |
Hazmat | Original | N | 6/23/2020 | CSFIRE | CSFIRE | NA for Foundation Only | wtaylor | Hazmat | 1340364 |
CO Springs Fire | Original | D | 6/23/2020 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L
See CSFD Plan Review Comments at: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp | csfdit | CO Springs Fire | 1340363 |
Zoning/Planning | Original | / | 6/23/2020 | LTHELEN | LTHELEN | In Current Review by LTHELEN | | Zoning/Planning | 1340189 |
Health Dept. | Original | D | 6/23/2020 | HEALTHDEPT | HEALTHDEPT | Construction activity permit required for projects earthmoving > 1 acre. Information and application may be accessed online at: https://www.elpasocountyhealth.org/service/air-quality/construction-activity-application For questions, contact Environmental Health at 719-578-3199 option 3. CM | cmille96 | Health Dept. | 1340012 |
City Engr | Original | D | 6/23/2020 | PMORRIS | PMORRIS | Insert a copy of the approved Development Plan. Insert a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP). | | City Engr | 1339957 |
Water Division | Original | D | 6/22/2020 | CSUREVIEW | CSUREVIEW | Approved CSU Construction Drawings must be attached to the permit set prior to our approval on Water Division and Wastewater Div. Contact Utilities Development Services at 719-668-8259 with any questions. KDS | kschelhaas | Water Division | 1339909 |
Waste Water Div | Original | D | 6/22/2020 | CSUREVIEW | CSUREVIEW | Approved CSU Construction Drawings must be attached to the permit set prior to our approval on Water Division and Wastewater Div. Contact Utilities Development Services at 719-668-8259 with any questions. KDS | kschelhaas | Waste Water Div | 1339908 |
Gas/Elec. Utils | Original | D | 6/22/2020 | CSUREVIEW | CSUREVIEW | Approved CSU Construction Drawings must be attached to the permit set prior to our approval on Water Division and Wastewater Div. Contact Utilities Development Services at 719-668-8259 with any questions. KDS | kschelhaas | Gas/Elec. Utils | 1339907 |
Mechanical | Original | A | 6/22/2020 | TCRIPPEN | TCRIPPEN | approved for underground only, | | Mechanical | 1339826 |
Electrical | Original | A | 6/22/2020 | BERTHA | BERTHA | APPROVED FOR UNG ONLY | | Electrical | 1339743 |
Plumbing | Original | N | 6/22/2020 | SHANEN | SHANEN | FOUNDATION ONLY No plumbing plans provided. No underground piping. Issue no permit. | | Plumbing | 1339742 |
Electronic Plan | Original | / | 6/22/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1339740 |
Electronic Plan | Original | / | 6/22/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1339726 |
Construction | Original | D | 6/22/2020 | LBENNETT | LBENNETT | Provide an IECC certificate in addition to the Total Building Performance Report G101: Clarify whether occupancies are separated or non-separated; clarify whether a horizontal assembly will be used; Provide frontage increase calculation; clarify new area per story
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1339724 |
Electronic Plan | Original | / | 6/19/2020 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1339147 |
Enumeration | Original | A | 6/17/2020 | BRENT | BRENT | | | Enumeration | 1337858 |
Electronic Plan | Original | / | 6/17/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1337807 |
Elevators | Original | A | 6/15/2020 | ERIC | ERIC | APPROVED FOR FOUNDATION ONLY
2 ThyssenKrupp conventional machineroom type elevators 1-2500# 1-4000#
Please include elevator submittals on thru finish plan set . | | Elevators | 1336530 |
Floodplain | Original | N | 6/15/2020 | KEITH | KEITH | | | Floodplain | 1336180 |
Floodplain | Original | / | 6/5/2020 | RBD GIS | RBD GIS | Autogenerated Review: Floodplain status unknown. (Parcel: 5500000300) | | Floodplain | 1332485 |