Electrical | Original | A | 7/28/2020 | SHELBY | SHELBY | | | Electrical | 1356563 |
Resubmittal 1 | Original | / | 7/28/2020 | JAY | JAY | Resubmittal #1 | | Resubmittal 1 | 1356220 |
CO Springs DRE | Original | N | 7/23/2020 | AOSBORNE | AOSBORNE | new a/c. interior work only, zoning n/a (see full review) | | CO Springs DRE | 1354377 |
CO Springs Fire | Original | N | 7/22/2020 | CSFIRE | CSFIRE | no fire final | csfdit | CO Springs Fire | 1353660 |
Hazmat | Original | N | 7/22/2020 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1353659 |
Zoning/Planning | Original | / | 7/21/2020 | AOSBORNE | AOSBORNE | In Current Review by AOSBORNE | | Zoning/Planning | 1353184 |
Electrical | Original | D | 7/20/2020 | SHELBY | SHELBY | 1. Size equipment grounds per 250.122 NEC. 2. Show SCA and SCCR at/for new cooling equipment. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1352600 |
Electronic Plan | Original | / | 7/20/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1352595 |
Water Division | Original | N | 7/20/2020 | CSUREVIEW | CSUREVIEW | No plumbing work. mjg | mgackle | Water Division | 1352573 |
Waste Water Div | Original | N | 7/20/2020 | CSUREVIEW | CSUREVIEW | No plumbing work. mjg | mgackle | Waste Water Div | 1352571 |
Mechanical | Original | A | 7/20/2020 | TCRIPPEN | TCRIPPEN | okay | | Mechanical | 1352439 |
Plumbing | Original | N | 7/20/2020 | SHANEN | SHANEN | No plumbing scope of work, issue no permit. | | Plumbing | 1352429 |
Electronic Plan | Original | / | 7/20/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1352427 |
Construction | Original | N | 7/20/2020 | MICHAELA | MICHAELA | | | Construction | 1352392 |
Electronic Plan | Original | / | 7/20/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1352385 |
Hazmat | Original | / | 7/16/2020 | WEBSITE | WEBSITE | Overtime Authorized for Hazmat by Sharon Styer | Sharon Styer | Hazmat | 1350761 |
Mechanical | Original | / | 7/16/2020 | WEBSITE | WEBSITE | Overtime Authorized for Mechanical by Sharon Styer | Sharon Styer | Mechanical | 1350760 |
Electrical | Original | / | 7/16/2020 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by Sharon Styer | Sharon Styer | Electrical | 1350757 |
Enumeration | Original | N | 7/14/2020 | AMY | AMY | | | Enumeration | 1349562 |
Electronic Plan | Original | / | 7/14/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1349559 |
Floodplain | Original | N | 7/13/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7415407009) | | Floodplain | 1348948 |