Electrical | Original | A | 3/11/2021 | BERTHA | BERTHA | | | Electrical | 1469001 |
Electronic Plan | Original | / | 3/11/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1468999 |
Electronic Plan | Original | / | 3/11/2021 | BPHILLIPS | BPHILLIPS | In Current Review by BPHILLIPS | | Electronic Plan | 1468998 |
Resubmittal 4 | Original | / | 3/10/2021 | SAVANNAHT | SAVANNAHT | Resubmittal #4 | | Resubmittal 4 | 1468279 |
CO Springs Fire | Original | A | 3/8/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the approval comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1467057 |
Plumbing | Original | A | 3/5/2021 | SHANEN | SHANEN | | | Plumbing | 1466320 |
Mechanical | Original | A | 3/3/2021 | JUSTINC | JUSTINC | | | Mechanical | 1465271 |
Electrical | Original | D | 3/3/2021 | SHELBY | SHELBY | Please provide load calculation for building service ( Load on service lateral). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1465147 |
CSU Waste Water | Original | A | 3/3/2021 | CSUREVIEW | CSUREVIEW | Comments addressed. MLW | mlwilliams | CSU Waste Water | 1465113 |
Construction | Original | A | 3/3/2021 | MICHAELA | MICHAELA | | | Construction | 1465039 |
Enumeration | Original | A | 3/3/2021 | BRENT | BRENT | | | Enumeration | 1464838 |
Electronic Plan | Original | / | 3/3/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1464827 |
Resubmittal 3 | Original | / | 3/1/2021 | SAVANNAHT | SAVANNAHT | Resubmittal #3 | | Resubmittal 3 | 1463512 |
Health Dept. | Original | A | 2/10/2021 | HEALTHDEPT | HEALTHDEPT | Approved in plan review. A pre-operational inspection will be required before final approval for opening is granted. CM | cmille96 | Health Dept. | 1454185 |
Health Dept. | Original | / | 2/10/2021 | HEALTHDEPT | HEALTHDEPT | | cmille96 | Health Dept. | 1454182 |
CO Springs Hazmat | Original | A | 2/1/2021 | CSFIRE | CSFIRE | Deferred submittal required. | rpeterson | CO Springs Hazmat | 1449330 |
CO Springs Fire | Original | D | 2/1/2021 | CSFIRE | CSFIRE | https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp | rpeterson | CO Springs Fire | 1449329 |
Electrical | Original | D | 1/28/2021 | SHELBY | SHELBY | One line is missing service lateral size, type, and quantity. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1447581 |
Electronic Plan | Original | / | 1/28/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1447577 |
Plumbing | Original | D | 1/26/2021 | SHANEN | SHANEN | P0.1: Adjust water pipe size analysis data to show flush tank water closets as 5 wsfu each. P1.3: Provide required CSU variance letter for existing indoor grease interceptor. Contact Robert Bowren at 719-668-1735. Indicate size of grease interceptor per CSU comments. P2.2: 2" waste is undersized to serve restroom. See red lines. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1445939 |
Mechanical | Original | D | 1/26/2021 | JUSTINC | JUSTINC | As walk-in coolers are part of this work provide refrigeration calculations. OR remove walk-in coolers from all scopes of work.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1445856 |
Electronic Plan | Original | / | 1/26/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1445804 |
CSU Waste Water | Original | D | 1/26/2021 | CSUREVIEW | CSUREVIEW | Indicate size of existing grease interceptor/trap on the plan set. mjg | mgackle | CSU Waste Water | 1445752 |
Health Dept. | Original | D | 1/26/2021 | HEALTHDEPT | HEALTHDEPT | Health department plan review is in process and not yet approved. For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1445662 |
Construction | Original | D | 1/26/2021 | MICHAELA | MICHAELA | Life Safety Plan - Egress route 26 - This egress path does not end until travel up the stairs to an exit. Verify travel distance to the protected corridor from the most remote point or add the travel up the stairs. Provide a legend for the numbered routes. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1445605 |
Enumeration | Original | A | 1/25/2021 | BRENT | BRENT | | | Enumeration | 1445076 |
Electronic Plan | Original | / | 1/25/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1445060 |
Resubmittal 2 | Original | / | 1/25/2021 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1444948 |
CO Springs Hazmat | Original | D | 11/24/2020 | CSFIRE | CSFIRE | pending receipt of requested documents per fire construction review | dwithee | CO Springs Hazmat | 1418374 |
CO Springs Fire | Original | D | 11/24/2020 | CSFIRE | CSFIRE | previous comments not addressed and remain outstanding (see full review) | csfdit | CO Springs Fire | 1418372 |
City Engr | Original | A | 11/19/2020 | PMORRIS | PMORRIS | | | City Engr | 1415581 |
Electrical | Original | D | 11/18/2020 | SHELBY | SHELBY | Please address previous review comments 1,2 and 3. See link provided with previous review. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1415124 |
Electronic Plan | Original | / | 11/18/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1415120 |
CSU Waste Water | Original | D | 11/18/2020 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Waste Water | 1414961 |
Plumbing | Original | D | 11/18/2020 | SHANEN | SHANEN | See construction reviewer comments. Show grease interceptor location per CSU waste water comments. Provide required CSU variance letter if grease interceptor is indoors. Contact Robert Bowren at 719-668-1735. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1414815 |
Mechanical | Original | D | 11/18/2020 | JUSTINC | JUSTINC | See (M) sheets for ALL mechanical comments associated with this review.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1414722 |
Electronic Plan | Original | / | 11/18/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1414568 |
Health Dept. | Original | D | 11/18/2020 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1414565 |
Construction | Original | D | 11/18/2020 | MICHAELA | MICHAELA | Provide a Life Safety Plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1414506 |
Enumeration | Original | D | 11/17/2020 | BRENT | BRENT | See comments from 07/20/20 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1413726 |
Electronic Plan | Original | / | 11/17/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1413709 |
Electronic Plan | Original | / | 11/16/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1413335 |
Resubmittal 1 | Original | / | 11/16/2020 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1413274 |
Hazmat | Original | D | 8/7/2020 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1362666 |
CO Springs Fire | Original | D | 8/7/2020 | CSFIRE | CSFIRE | Reference CSFD website for disapproval comments: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp (see full review) | csfdit | CO Springs Fire | 1362665 |
Health Dept. | Original | D | 8/5/2020 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions, contact Environmental Health at 719-578-3199 option 3. AB | abrannon | Health Dept. | 1361028 |
CSU Contract Admin. | Original | N | 8/4/2020 | CSUAPPSPRM | CSUAPPSPRM | No fees due for permit. ZS | zshearer | CSU Contract Admin. | 1360417 |
CO Springs DRE | Original | N | 7/28/2020 | DFOXX | DFOXX | Interior remodel only, no change of use. (see full review) | | CO Springs DRE | 1356170 |
City Engr | Original | D | 7/28/2020 | JDAGNILLO | JDAGNILLO | Include a copy of the approved Development Plan. | | City Engr | 1356121 |
Mechanical | Original | D | 7/27/2020 | JUSTINC | JUSTINC | See mechanical pages for mechanical disapproval comments as they relate to the structure.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1355806 |
Electronic Plan | Original | / | 7/27/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1355767 |
Water Division | Original | N | 7/24/2020 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | Water Division | 1355137 |
Gas/Elec. Utils | Original | N | 7/24/2020 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | Gas/Elec. Utils | 1355136 |
Waste Water Div | Original | D | 7/24/2020 | CSUREVIEW | CSUREVIEW | NEED TO SHOW THE EXISTING GREESE INTERCEAPTOR AND SIZE ON THE PLUMBING PLAN PLEASE AJ | ajuvera | Waste Water Div | 1355135 |
Electrical | Original | D | 7/24/2020 | SHELBY | SHELBY | 1. provide complete one line. See https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs.pdf 2. Show SCA and SCCR at/for all new and relocated refrigeration and cooling equipment. 3. GFCI devices may not be located above or behind appliances. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1354916 |
Electronic Plan | Original | / | 7/24/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1354884 |
Plumbing | Original | D | 7/24/2020 | SHANEN | SHANEN | Address construction reviewer comments regarding accessible route to the toilet rooms. P0.1 Reference currently adopted 2015 IPC. P1.0, P2.3 All gas piping related items to be on mechanical plans.Remove all references to gas piping from plumbing plans and provide on mechanical plans. P1.2, P2.2 All plumbing fixtures in a restaurant, except restroom fixtures and water entry floor drain, must discharge to the grease waste. P2.2 KS1, KS2, & DW must comply with section 802 INDIRECT WASTES.Section 802.1 Where required. Food handling equipment, clear water waste, dishwashing machines and utensils, pots, pans, and dishwashing sinks shall discharge through an indirect waste pipe as specified in Sections 802.1.1 through 802.1.8. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1354839 |
Elevators | Original | N | 7/24/2020 | ERIC | ERIC | No Conveyance in this scope. See C121068 | | Elevators | 1354800 |
Zoning/Planning | Original | / | 7/23/2020 | DFOXX | DFOXX | In Current Review by DFOXX | | Zoning/Planning | 1354737 |
Construction | Original | D | 7/23/2020 | MICHAELA | MICHAELA | Revise Code Data to current locally adopted codes. A Life Safety Plan with all of this information is required. Page G111 is out of order. Occupants on the main level must be provided an accessible route to the toilet rooms that does not involve leaving the building. Missing 18" vertical grab bar at toilet. Provide structural plans for the new floor opening. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1354722 |
Electronic Plan | Original | / | 7/23/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1354219 |
Enumeration | Original | D | 7/20/2020 | BRENT | BRENT | Show all tenant spaces with addressing for spaces on the first floor with area of work highlighted. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1352603 |
Electronic Plan | Original | / | 7/20/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1352583 |
Floodplain | Original | N | 7/14/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418210011) | | Floodplain | 1349741 |