CO Springs Fire | Splice 12/14/20 | A | 12/30/2020 | CSFIRE | CSFIRE | fire sprinklers are noted as being removed from CAR storage room - this building requires fire sprinklers throughout by adopted codes. If water-based fire sprinklers are being removed, then an alternative system such as clean agent must be installed. (see full review) | csfdit | CO Springs Fire | 1433338 |
Mechanical | Splice 12/14/20 | A | 12/15/2020 | JUSTINC | JUSTINC | Revised to add area D scope | | Mechanical | 1427685 |
Electronic Plan | Splice 12/14/20 | / | 12/15/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1427681 |
Electrical | Splice 12/14/20 | A | 12/15/2020 | BERTHA | BERTHA | Revised power, lighting and schedules. | | Electrical | 1427429 |
Electronic Plan | Splice 12/14/20 | / | 12/15/2020 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1427316 |
Construction | Splice 12/14/20 | A | 12/15/2020 | DANM | DANM | Revisions to Kiosk area | | Construction | 1427148 |
Electronic Plan | Splice 12/14/20 | / | 12/15/2020 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1427134 |
Plumbing | Splice 12/08/20 | A | 12/10/2020 | SHANEN | SHANEN | Delta 5 revisions: 1 sheet provided, P1.03 adjusted second floor plumbing plan | | Plumbing | 1425099 |
Resubmittal 1 | Splice 12/08/20 | / | 12/9/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1424861 |
Plumbing | Splice 12/08/20 | D | 12/8/2020 | SHANEN | SHANEN | Per provided pipe sizing analysis and table E201.1, 3/4" HW is undersized to serve 34.5 wsfu. Delta 4 revisions previously approved. Provide new delta number for current revisions. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1423613 |
Plumbing | Splice 11/24/20 | A | 11/24/2020 | SHANEN | SHANEN | Delta 4 revisions: 1 sheet provided, P1.03 adjusted second floor plumbing plan | | Plumbing | 1418452 |
Health Dept. | Original | A | 9/30/2020 | HEALTHDEPT | HEALTHDEPT | Retail Food Plan Review still in process. Do not proceed with construction of food services before final review of application is approved by Public Health. Thank you. | skirst | Health Dept. | 1391435 |
Resubmittal 4 | Original | / | 9/30/2020 | BECKYA | BECKYA | Resubmittal #4 | | Resubmittal 4 | 1391120 |
Health Dept. | Original | D | 9/23/2020 | HEALTHDEPT | HEALTHDEPT | Retail food establishment plan review required. Information and application may be accessed online at https://www.elpasocountyhealth.org/service/retail-food-establishment-licensing-0 For questions, contact Environmental Health at 719-578-3199 option 3. AF | Amanda Furno | Health Dept. | 1387734 |
Plumbing | Original | A | 9/23/2020 | SHANEN | SHANEN | | | Plumbing | 1387625 |
Resubmittal 3 | Original | / | 9/23/2020 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1387259 |
Plumbing | Original | D | 9/18/2020 | SHANEN | SHANEN | Remove all references to HVAC and gas piping from plumbing plans and provide on mechanical plans. 2" SS is undersized for a clothes washer connection per section 406 Automatic clothes washers. paragraph 406.2 Waste connection. Provide water pipe size analysis data, see 2015 IPC appendix E. Provide materials schedule for DWV piping. Schedule indoor grease interceptor that is sized per CSU variance letter. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1384997 |
Mechanical | Original | A | 9/18/2020 | JUSTINC | JUSTINC | | | Mechanical | 1384994 |
Electronic Plan | Original | / | 9/18/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1384970 |
CSU Waste Water | Original | A | 9/18/2020 | CSUREVIEW | CSUREVIEW | Variance letter provided. The size of the internal interceptor/trap shall be in accordance with the requirement of the variance letter. MLW | mlwilliams | CSU Waste Water | 1384951 |
Resubmittal 2 | Original | / | 9/17/2020 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1384813 |
CO Springs Fire | Original | A | 9/17/2020 | CSFIRE | CSFIRE | https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp | rpeterson | CO Springs Fire | 1384669 |
Electrical | Original | A | 9/11/2020 | BERTHA | BERTHA | | | Electrical | 1381676 |
Waste Water Div | Original | D | 9/3/2020 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | Waste Water Div | 1378035 |
Mechanical | Original | D | 9/3/2020 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Address comments from last review.
Review stopped
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1377707 |
Electronic Plan | Original | / | 9/3/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1377703 |
Electrical | Original | D | 9/3/2020 | BERTHA | BERTHA | Comply with previous review comments. Information is required at time of plan submittal.
See the following for Electrical Plan Review Requirements
https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs.pdf
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1377676 |
Plumbing | Original | D | 9/3/2020 | SHANEN | SHANEN | Plumbing review incomplete.
Separate plumbing scope from mechanical plans. Provide plumbing plans that comply with PPRBD plumbing plan review requirements. See link below:https://www.pprbd.org/Downloads/CommercialHandout/comm%20plumb%20reqs.pdf Provide an occupant load to fixture count analysis to verify compliance with section 403.1 Minimum number of fixtures. CSU variance letter required for indoor grease interceptor. Contact Robert Bowren at 719-668-1735. All gas piping, mechanical condensate piping, hydronics and mechanical venting items to be on M pages. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1377647 |
Construction | Original | A | 9/3/2020 | DANM | DANM | | | Construction | 1377514 |
Electronic Plan | Original | / | 9/3/2020 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1377450 |
Resubmittal 1 | Original | / | 9/2/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1377385 |
Hazmat | Original | N | 8/24/2020 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1371716 |
CO Springs Fire | Original | D | 8/24/2020 | CSFIRE | CSFIRE | clarify what is meant by car storge on first floor. | csfdit | CO Springs Fire | 1371715 |
CO Springs DRE | Original | N | 8/17/2020 | AODOM | AODOM | Interior Remodel, no exterior work. no change of use. (see full review) | | CO Springs DRE | 1367501 |
Electrical | Original | D | 8/13/2020 | SHELBY | SHELBY | 1. Label all new and existing electrical equipment/devices with panel and circuit number ( Lights, TV outlets etc.). 2. Provide one line. 3. Clearly label electrical components in this scope as new or existing. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1366105 |
Electronic Plan | Original | / | 8/13/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1366061 |
Water Division | Original | N | 8/13/2020 | CSUREVIEW | CSUREVIEW | No new water service outside of building. Backflow OK. KDS | kschelhaas | Water Division | 1365478 |
Waste Water Div | Original | D | 8/13/2020 | CSUREVIEW | CSUREVIEW | Contact CSU Industrial Pretreatment (Bob Bowren at 719-668-1735) to determine if a variance for an interior grease trap is applicable. If applicable, provide a copy of the Variance letter in the building plan set. KDS | kschelhaas | Waste Water Div | 1365477 |
Plumbing | Original | D | 8/13/2020 | SHANEN | SHANEN | Plumbing review incomplete
Separate plumbing scope from mechanical plans. Provide plumbing plans that comply with PPRBD plumbing plan review requirements. See link below:https://www.pprbd.org/Downloads/CommercialHandout/comm%20plumb%20reqs.pdf Provide approved occupant load and occupant load to fixture count analysis to verify compliance with section 403.1 Minimum number of fixtures. CSU variance letter required for indoor grease interceptor. Contact Robert Bowren at 719-668-1735. All gas piping, mechanical condensate piping, hydronics and mechanical venting items to be on M pages. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1365459 |
Electronic Plan | Original | / | 8/13/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1365424 |
Mechanical | Original | D | 8/12/2020 | JUSTINC | JUSTINC | Mechanical review incomplete
Separate plumbing scope from mechanical plans. Separate fire protection sheets from mechanical upload
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1365219 |
Electronic Plan | Original | / | 8/12/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1365203 |
Zoning/Planning | Original | / | 8/12/2020 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1365173 |
Enumeration | Original | N | 8/12/2020 | AMY | AMY | single tenant building | | Enumeration | 1365101 |
Electronic Plan | Original | / | 8/12/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1365090 |
Floodplain | Original | N | 8/12/2020 | KEITH | KEITH | | | Floodplain | 1365004 |
Construction | Original | D | 8/4/2020 | DANM | DANM | Code Study Form - Fill out Page 2 as completely as possible Provide construction cost on contractor's letterhead with breakdown for 20% accessibility upgrades Provide summary of occupant load calculations showing the increase or decrease in existing occupant load based on remodel scope of work Clarify reason for 1-hr rating at CAR Storage - if other than IBC requirements then note as such Swing door out of Cafe (near kitchen) in direction of egress travel Sheet A4.702 - only one listing allowed for rated wall assembly All wood blocking must be fire-retardant-treated
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1360411 |
Electronic Plan | Original | / | 8/3/2020 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1359833 |
Floodplain | Original | / | 8/3/2020 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7326201002) | | Floodplain | 1359464 |