Out to Review | Splice 03/01/23 | / | 3/1/2023 | SCANNING | SCANNING | Wendel | | Out to Review | 1808988 |
Electrical | Splice 03/01/23 | A | 3/1/2023 | SCANNING | SCANNING | SLE 3/1/2023 | | Electrical | 1808987 |
Electrical | Splice 02/13/23 | A | 3/1/2023 | SHELBY | SHELBY | | | Electrical | 1808965 |
Canceled Plans | Splice 02/13/23 | / | 3/1/2023 | | RITA | Location = Canceled Plans by RITA | | Canceled Plans | 1808952 |
Out to Review | Splice 01/23/23 | / | 2/28/2023 | NELIDA | NELIDA | Wendel 719-499-1550 | | Out to Review | 1808259 |
Electrical | Splice 02/13/23 | D | 2/13/2023 | DANIELG | DANIELG | Please clarify. The most recent one-line does not have the splice revisions matching the delta 8 revision.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Electrical | 1802209 |
Electronic Plan | Splice 02/13/23 | / | 2/13/2023 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1802206 |
Scanned/Finished Bin (Main) | Splice 01/23/23 | / | 1/26/2023 | | SCANNING | Location = Scanned/Finished Bin (Main) by SCANNING- routing to North 1/26/23 9am | | Scanned/Finished Bin (Main) | 1795480 |
Plan Coordinator (North) | Splice 01/23/23 | / | 1/25/2023 | | SHANEN | Location = Plan Coordinator (North) by SHANEN | | Plan Coordinator (North) | 1794942 |
Plumbing | Splice 01/23/23 | A | 1/25/2023 | SHANEN | SHANEN | Delta 7 revisions: Adjusted sheet P0.2.1 and P1.1.1. | | Plumbing | 1794941 |
Plumbing | Splice 01/23/23 | / | 1/23/2023 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1794241 |
Plan Coordinator (Main) | Splice 01/23/23 | / | 1/23/2023 | | JUSTINC | Location = Plan Coordinator (Main) by JUSTINC | | Plan Coordinator (Main) | 1794133 |
Mechanical | Splice 01/23/23 | A | 1/23/2023 | JUSTINC | JUSTINC | Revised EF tag and schedule | | Mechanical | 1794132 |
Mechanical | Splice 01/23/23 | / | 1/23/2023 | | JANE | Location = Mechanical by JANE | | Mechanical | 1793926 |
Electrical | Splice 01/28/22 | N | 2/4/2022 | SHELBY | SHELBY | | | Electrical | 1632616 |
Mechanical | Splice 01/28/22 | A | 2/2/2022 | JUSTINC | JUSTINC | Removed exhaust fan from scope | | Mechanical | 1631373 |
Resubmittal 1 | Splice 01/28/22 | / | 2/1/2022 | AUSTINK | AUSTINK | Resubmittal #1 | | Resubmittal 1 | 1630909 |
Mechanical | Splice 01/28/22 | D | 1/28/2022 | JUSTINC | JUSTINC | How will bathroom be exhausted with fan removed and no operable window. Per (A) sheets this is a bathroom
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1629207 |
Plumbing | Splice 12/20/21 | A | 1/19/2022 | SHANEN | SHANEN | Delta 6 revisions: Adjusted sheet P1.1.1 (see alternate in images). Per telephone conversation with engineer Orlando Gonzales on 1/19/22. | | Plumbing | 1623341 |
Resubmittal 1 | Splice 12/20/21 | / | 1/19/2022 | AUSTINK | AUSTINK | Resubmittal #1 | | Resubmittal 1 | 1623290 |
Elevators | Original | A | 12/23/2021 | ERIC | ERIC | Conventional machineroom type hydraulic elevator. Provide elevator submittals prior to permitting elevator | | Elevators | 1612367 |
Electrical | Splice 12/20/21 | A | 12/21/2021 | SHELBY | SHELBY | | | Electrical | 1611281 |
Electronic Plan | Splice 12/20/21 | / | 12/21/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1611278 |
Plumbing | Splice 12/20/21 | D | 12/21/2021 | SHANEN | SHANEN | P1.1.1: Clarify keynote 5. Elevator sump discharging to the exterior does not comply with section 301.6 Exception: Floor drains, sumps and sump pumps shall be permitted at the base of the shaft, provided that they are indirectly connected to the plumbing system. //// PPRBD note added 1/7/22: See images for elevator sump discharge alternate.\\\\ (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1611020 |
Mechanical | Splice 12/20/21 | A | 12/20/2021 | JUSTINC | JUSTINC | Removed unit heaters and associated gas | | Mechanical | 1610815 |
Electronic Plan | Splice 12/20/21 | / | 12/20/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1610807 |
Mechanical | Splice 11/09/21 | A | 11/9/2021 | JUSTINC | JUSTINC | Scope and layout revised | | Mechanical | 1591156 |
Electronic Plan | Splice 11/09/21 | / | 11/9/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1591128 |
CO Springs DRE | Original | A | 4/12/2021 | WGRAY | WGRAY | Approved by WEG pursuant to the approved UHAUL Centennial Blvd Development Plan, AR DPA 98-00294-AM1J20 (see full review) | | CO Springs DRE | 1483463 |
Mechanical | Original | A | 4/9/2021 | JUSTINC | JUSTINC | | | Mechanical | 1482864 |
Electronic Plan | Original | / | 4/9/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1482858 |
Zoning/Planning | Original | / | 4/9/2021 | WGRAY | WGRAY | In Current Review by WGRAY | | Zoning/Planning | 1482747 |
Construction | Original | A | 4/9/2021 | MICHAELA | MICHAELA | | | Construction | 1482743 |
Enumeration | Original | A | 4/8/2021 | BRENT | BRENT | | | Enumeration | 1482438 |
Electronic Plan | Original | / | 4/8/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1482435 |
Resubmittal 4 | Original | / | 4/8/2021 | SAVANNAHT | SAVANNAHT | Resubmittal #4 | | Resubmittal 4 | 1482006 |
CO Springs DRE | Original | A | 4/1/2021 | WGRAY | WGRAY | Approved per file number AR DPA 98-00294-AM1J20 (see full review) | | CO Springs DRE | 1479263 |
Zoning/Planning | Original | A | 3/29/2021 | WGRAY | WGRAY | | | Zoning/Planning | 1477244 |
Plumbing | Original | A | 3/26/2021 | SHANEN | SHANEN | | | Plumbing | 1476413 |
Construction | Original | A | 3/26/2021 | MICHAELA | MICHAELA | | | Construction | 1476174 |
Enumeration | Original | A | 3/26/2021 | BRENT | BRENT | | | Enumeration | 1475927 |
Electronic Plan | Original | / | 3/26/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1475922 |
Resubmittal 3 | Original | / | 3/24/2021 | BECKYA | BECKYA | Resubmittal #3 | | Resubmittal 3 | 1475092 |
CO Springs DRE | Original | D | 3/9/2021 | AODOM | AODOM | Add approved Development plan to construction set (see full review) | | CO Springs DRE | 1468040 |
Zoning/Planning | Original | D | 1/29/2021 | WGRAY | WGRAY | Add approved Development Plan to the Construction Set. | | Zoning/Planning | 1448058 |
Mechanical | Original | A | 1/27/2021 | JUSTINC | JUSTINC | | | Mechanical | 1446800 |
Electronic Plan | Original | / | 1/27/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1446771 |
Plumbing | Original | D | 1/27/2021 | SHANEN | SHANEN | Sheet P2.1.1 waste water piping schematic 5: 4" minimum effective sink drain opening, 4" trap and 4" waste required to handle 50 gpm (100 dfu) discharge from elevator sump.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1446677 |
Construction | Original | D | 1/27/2021 | MICHAELA | MICHAELA | Provide as built structural plans for these stairs built prior to permit. The second floor of this structure still has a certificate of occupancy. You cannot return just the upper level to a shell space and so the upper level area and occupant load need to be included here. This is true regardless of whether you occupy that area of the structure or not. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1446475 |
Enumeration | Original | A | 1/26/2021 | BRENT | BRENT | | | Enumeration | 1445580 |
Electronic Plan | Original | / | 1/26/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1445576 |
Resubmittal 2 | Original | / | 1/25/2021 | JAY | JAY | Resubmittal #2 | | Resubmittal 2 | 1445431 |
CO Springs Fire | Original | A | 12/30/2020 | CSFIRE | CSFIRE | You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1433362 |
CO Springs DRE | Original | D | 12/18/2020 | ASERRANO | ASERRANO | This project has a major amendment development plan in reviewed and has not been approved. (see full review) | | CO Springs DRE | 1429802 |
Zoning/Planning | Original | / | 12/18/2020 | ASERRANO | ASERRANO | In Current Review by ASERRANO | | Zoning/Planning | 1429392 |
Plumbing | Original | D | 12/17/2020 | SHANEN | SHANEN | Waste receptor (US-1) for elevator sump discharge is under sized, must be capable of handling 50 gpm. All gas piping related items to be on mechanical plans.Remove all references to gas piping from plumbing plans and provide on mechanical plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1429215 |
Electrical | Original | A | 12/15/2020 | SHELBY | SHELBY | | | Electrical | 1427836 |
Mechanical | Original | A | 12/15/2020 | JUSTINC | JUSTINC | | | Mechanical | 1427709 |
Zoning/Planning | Original | / | 12/15/2020 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1427697 |
Electronic Plan | Original | / | 12/15/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1427696 |
Elevators | Original | N | 12/15/2020 | ERIC | ERIC | Basis of design is 1-7500# conventional machineroom type Hydraulic elevator
Plans marked N/A until elevator submittals are provided as a splice, no elevator permit will be granted until splice is approved. | | Elevators | 1427644 |
Construction | Original | D | 12/15/2020 | MICHAELA | MICHAELA | Response letter indicated attachment #C1. Please include. These are not separate fire areas, they are separate buildings. Please only include information on the structure on the side of the Fire Wall where the work is occurring. Second level exterior stairs and opening have been constructed without a permit. They need to be included in the scope of work for a proper inspection. An elevator and new stairs are being provided to the second level. A floor plan and a use is required whether the floor will be currently occupied or not. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1427625 |
Enumeration | Original | A | 12/15/2020 | BRENT | BRENT | | | Enumeration | 1427212 |
Electronic Plan | Original | / | 12/15/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1427201 |
Resubmittal 1 | Original | / | 12/14/2020 | JAY | JAY | Resubmittal #1 | | Resubmittal 1 | 1427031 |
Hazmat | Original | N | 8/25/2020 | CSFIRE | CSFIRE | | dwithee | Hazmat | 1372734 |
CO Springs Fire | Original | D | 8/25/2020 | CSFIRE | CSFIRE | REFERENCE CSFD WEBSITE FOR DETAILS ON DISAPPROVAL ITEMS; https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp (see full review) | csfdit | CO Springs Fire | 1372732 |
CO Springs DRE | Original | D | 8/19/2020 | ASERRANO | ASERRANO | This project has a major amendment development plan that is in reviewed and has not been approved. (see full review) | | CO Springs DRE | 1369188 |
Zoning/Planning | Original | / | 8/18/2020 | ASERRANO | ASERRANO | In Current Review by ASERRANO | | Zoning/Planning | 1368189 |
Electrical | Original | D | 8/17/2020 | SHELBY | SHELBY | 1. Use 2015 IECC 2018 has not been adopted. 2. Verify fault current prior to plan submittal ( See keyed note 1 sheet E5.0.1). 3. Show existing feeder size, type and quantity on one line. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1367828 |
Electronic Plan | Original | / | 8/17/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1367637 |
Zoning/Planning | Original | / | 8/17/2020 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1367089 |
Plumbing | Original | D | 8/14/2020 | SHANEN | SHANEN | P0.2.1 Schedule US-1, SP-1 and SP-2. Model number shown for WC-1 not found on the manufacturer's web site. P1.1.1 All gas piping related items to be on mechanical plans.Remove all references to gas piping from plumbing plans and provide on mechanical plans. Waste receptor (US-1) for elevator sump discharge is under sized, must be capable of handling 50 gpm. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1366527 |
Mechanical | Original | D | 8/13/2020 | JUSTINC | JUSTINC | Add note: Provide (1) copy of test and balance report to mechanical inspector at time of heating final inspection.
Remove work not associated with this remodel permit
Relocate all gas drawings, notes, details, etc... to (M) sheets for PPRBD review
Clarify ALL duct sizes on (M) sheet floor plan.
How complying with 2015 IECC C403.2.4.3?
MECHANICAL REVIEW INCOMPLETE
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1365967 |
Electronic Plan | Original | / | 8/13/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1365951 |
Elevators | Original | D | 8/13/2020 | ERIC | ERIC | Basis of design is 1 conventional machineroom type hydraulic elevator Please provide elevator submittals/shop drawings Page T 1.1 Add ASME A17.1 Code for Elevators and Escalators to code analysis Page E 2.2.1 Keynote 6 Remove reference to shunt trip as it is not allowed in this fire jurisdiction for this type of occupancy Page E 2.5.1 Keynote 8 Remove disconnect from elevator pit for sump pump and add single non-gfci outlet Page E 2.5.1 Show all elevator pit circuits, pit lighting and pit gfci to be on separate circuits
NOTE: All elevator pit electrical to be kept 30" AFF and can be done in NEMA 3R, If below 30", must be done in 4 or 4X
See https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Elevator%20conveyance%20plan%20submittal.pdf for all elevator plan requirements. . (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1365950 |
Water Division | Original | N | 8/13/2020 | CSUREVIEW | CSUREVIEW | No new water service outside of building. Backflow OK. KDS | kschelhaas | Water Division | 1365868 |
Waste Water Div | Original | N | 8/13/2020 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. KDS | kschelhaas | Waste Water Div | 1365866 |
Construction | Original | D | 8/13/2020 | MICHAELA | MICHAELA | Provide the equations that result in the allowable area numbers. Code data indicates two fire areas. Where re they and what separates them? There is no permit history for the exterior stairs. Include them in the scope of work in order to effect an inspection. Missing notes 5 and 6 for the listed assemblies. The upper level is not existing and it is not a mezzanine it is a story. Provide a floor plan for the second floor with a plan for egress. Provide a listing for the top of stairs assembly or an IBC item number from table 721. Indicate actual rise and run at stairs Provide a framing plan for the roof where the elevator shaft penetrates it. Also framing for the elevator roof. Foundation Plan is not correct
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1365841 |
Electronic Plan | Original | / | 8/13/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1365630 |
Enumeration | Original | D | 8/12/2020 | BRENT | BRENT | Show all addresses in this building with area of work highlighted on page A1.1 There are 2 legal descriptions shown on the code study form. Remove the one referencing the access easement. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1364901 |
Electronic Plan | Original | / | 8/12/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1364865 |
Floodplain | Original | N | 8/11/2020 | KEITH | KEITH | | | Floodplain | 1364357 |
Floodplain | Original | / | 8/6/2020 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7323404007) | | Floodplain | 1362435 |