Mechanical | Splice 12/11/20 | A | 1/5/2021 | DALEH | DALEH | Clouds | | Mechanical | 1434753 |
Resubmittal 1 | Splice 12/11/20 | / | 12/29/2020 | JAY | JAY | Resubmittal #1 | | Resubmittal 1 | 1433137 |
Mechanical | Splice 12/11/20 | D | 12/14/2020 | DALEH | DALEH | It appears gas piping has been changed to low pressure gas The gas pressure reg. is now not shown at RTU-35 If change in pressure provide all required documentation (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1426681 |
CO Springs Hazmat | Original | N | 10/26/2020 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1403656 |
CO Springs Fire | Original | A | 10/26/2020 | CSFIRE | CSFIRE | You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp (see full review) | csfdit | CO Springs Fire | 1403655 |
Mechanical | Original | A | 10/16/2020 | JUSTINC | JUSTINC | | | Mechanical | 1399593 |
Electronic Plan | Original | / | 10/16/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1399584 |
Construction | Original | A | 10/16/2020 | MICHAELA | MICHAELA | | | Construction | 1399573 |
Mechanical | Original | D | 10/15/2020 | JUSTINC | JUSTINC | Same comment as last review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1399026 |
Electronic Plan | Original | / | 10/15/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1399025 |
Construction | Original | D | 10/15/2020 | MICHAELA | MICHAELA | A-3 is a separate occupancy not an accessory occupancy. Provide compliant separation. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1399013 |
Enumeration | Original | A | 10/15/2020 | BRENT | BRENT | | | Enumeration | 1398926 |
Electronic Plan | Original | / | 10/15/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1398921 |
Resubmittal 2 | Original | / | 10/15/2020 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1398874 |
CO Springs Fire | Original | D | 10/15/2020 | CSFIRE | CSFIRE | Disapproved at contractor request | fdjah74 | CO Springs Fire | 1398660 |
CO Springs Hazmat | Original | D | 10/15/2020 | CSFIRE | CSFIRE | Disapproved at contractor request | fdjah74 | CO Springs Hazmat | 1398659 |
Mechanical | Original | D | 10/14/2020 | JUSTINC | JUSTINC | Pending approved floor plan from construction reviewer. Penetrations into corridor are shown as unprotected can you please clarify if this is a rated corridor.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1398456 |
Electronic Plan | Original | / | 10/14/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1398414 |
Construction | Original | D | 10/14/2020 | MICHAELA | MICHAELA | Per the Building Official accessory use is applied per suite, not per building. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1398402 |
Enumeration | Original | A | 10/14/2020 | BRENT | BRENT | | | Enumeration | 1398155 |
Electronic Plan | Original | / | 10/14/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1398146 |
Resubmittal 1 | Original | / | 10/13/2020 | SHELLEY | SHELLEY | Resubmittal #1 | | Resubmittal 1 | 1397857 |
CO Springs Fire | Original | D | 10/13/2020 | CSFIRE | CSFIRE | disapproved at contractor request without review | dwithee | CO Springs Fire | 1397624 |
CO Springs Hazmat | Original | D | 10/13/2020 | CSFIRE | CSFIRE | disapproved at contractor request without review | dwithee | CO Springs Hazmat | 1397623 |
CO Springs DRE | Original | N | 10/7/2020 | KSCHOTT | KSCHOTT | interior remodel only, no exterior work, no change to parking, medical office permitted in PIP2 zone (see full review) | | CO Springs DRE | 1395061 |
CSU Water | Original | N | 10/6/2020 | CSUREVIEW | CSUREVIEW | No plumbing work. mjg | mgackle | CSU Water | 1394134 |
CSU Waste Water | Original | N | 10/6/2020 | CSUREVIEW | CSUREVIEW | No plumbing work. mjg | mgackle | CSU Waste Water | 1394133 |
Plumbing | Original | N | 10/5/2020 | SHANEN | SHANEN | No plumbing plans provided. No plumbing scope of work indicated, issue no permit. | | Plumbing | 1393443 |
Zoning/Planning | Original | / | 10/5/2020 | KSCHOTT | KSCHOTT | In Current Review by KSCHOTT | | Zoning/Planning | 1393423 |
Electrical | Original | A | 10/5/2020 | SHELBY | SHELBY | | | Electrical | 1393409 |
Electronic Plan | Original | / | 10/5/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1393390 |
Mechanical | Original | D | 10/5/2020 | JUSTINC | JUSTINC | Pending approved floor plan from construction reviewer (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1393337 |
Electronic Plan | Original | / | 10/5/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1393325 |
Construction | Original | D | 10/5/2020 | MICHAELA | MICHAELA | A conference room with an occupant load of 70 is an A occupancy. This is a partial change of occupancy for this structure. Address height and area based on non-separated use for an A occupancy. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1393292 |
Electronic Plan | Original | / | 10/5/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1393203 |
Enumeration | Original | D | 10/2/2020 | BRENT | BRENT | There are multipile tenants in this building. Show all tenant spaces with addressing and area of work hightlighted on the site plan in the architectural pages. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1392899 |
Electronic Plan | Original | / | 10/2/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1392880 |
Mechanical | Original | / | 10/1/2020 | WEBSITE | WEBSITE | Overtime Authorized for Mechanical by Christina Zani | Bryan7025 | Mechanical | 1392263 |
Electrical | Original | / | 10/1/2020 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by Christina Zani | Bryan7025 | Electrical | 1392262 |
Construction | Original | / | 10/1/2020 | WEBSITE | WEBSITE | Overtime Authorized for Construction by Christina Zani | Bryan7025 | Construction | 1392261 |
Floodplain | Original | N | 10/1/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7323106007) | | Floodplain | 1392202 |