Manitou Zoning | Original | A | 5/18/2021 | MATTHEWM | MATTHEWM | See images | | Manitou Zoning | 1502604 |
Manitou Waste Water | Original | A | 5/17/2021 | MATTHEWM | MATTHEWM | See images | | Manitou Waste Water | 1502022 |
Manitou Water | Original | A | 5/17/2021 | MATTHEWM | MATTHEWM | See images | | Manitou Water | 1502021 |
Manitou Fire | Original | A | 5/17/2021 | MATTHEWM | MATTHEWM | See images | | Manitou Fire | 1502020 |
Waste Water Div | Original | / | 5/12/2021 | SYSTEM | SYSTEM | Contact Waste Water Div department for approval prior to permit | | Waste Water Div | 1499873 |
Zoning/Planning | Original | / | 5/12/2021 | SYSTEM | SYSTEM | Contact Zoning/Planning department for approval prior to permit | | Zoning/Planning | 1499874 |
Water Division | Original | / | 5/12/2021 | SYSTEM | SYSTEM | Contact Water Division department for approval prior to permit | | Water Division | 1499871 |
Fire | Original | / | 5/12/2021 | SYSTEM | SYSTEM | Contact Fire department for approval prior to permit | | Fire | 1499872 |
Electrical | Original | N | 5/10/2021 | SHELBY | SHELBY | 90.2(B)(5) NEC | | Electrical | 1498234 |
Resubmittal 3 | Original | / | 5/10/2021 | SHELBY | SHELBY | Resubmittal #3 | | Resubmittal 3 | 1498232 |
Electrical | Original | D | 5/7/2021 | SHELBY | SHELBY | Please address previous review comments 2,3,4,and 5. For comment 2 no site plan is included. For comment 3 an NRTL listing is required for the generator. For comment 4 conductor size, type, and quantity must be shown on E1 for non control panel conductors. For comment 5 Show SCA, AIC and SCCR on sheet E1. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1497189 |
Resubmittal 2 | Original | / | 5/3/2021 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1494992 |
Electrical | Original | D | 4/20/2021 | SHELBY | SHELBY | Please address previous review comments 2,3,4, and 5. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1488405 |
Electronic Plan | Original | / | 4/20/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1488396 |
Mechanical | Original | N | 4/16/2021 | JUSTINC | JUSTINC | No new or revised mechanical scope indicated | | Mechanical | 1486716 |
Electronic Plan | Original | / | 4/16/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1486711 |
Plumbing | Original | N | 4/16/2021 | SHANEN | SHANEN | Process piping. Plumbing plans are for reference only. No plumbing scope of work. | | Plumbing | 1486680 |
Construction | Original | N | 4/16/2021 | MICHAELA | MICHAELA | | | Construction | 1486656 |
Resubmittal 1 | Original | / | 4/16/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1486536 |
Electrical | Original | D | 10/22/2020 | SHELBY | SHELBY | 1. Engineer's stamp is not signed. 2. Please provide site/floor plan showing location of existing MCC and new generator and generator control panel. 3. Include listing documentation ( From NRTL website) for generator and generator control panel. 4. Show conductor and raceway size, type, and quantity on one line. 5. Show SCCR and SCA at/for generator control panel. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1402308 |
Electronic Plan | Original | / | 10/20/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1401090 |
Plumbing | Original | D | 10/16/2020 | SHANEN | SHANEN | Address construction reviewer comments. Engineer's stamps must be signed on sheets G-1 & PID-1. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1399495 |
Mechanical | Original | D | 10/14/2020 | JUSTINC | JUSTINC | Pending floor plans (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1398334 |
Electronic Plan | Original | / | 10/14/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1398324 |
Construction | Original | D | 10/14/2020 | MICHAELA | MICHAELA | Complete the Code Study form. Provide an architectural plan view of areas where structures are being modified or erected with the egress path indicated, rooms labeled as to use. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1398266 |
Electronic Plan | Original | / | 10/14/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1398069 |
Zoning/Planning | Original | / | 10/5/2020 | SYSTEM | SYSTEM | You will need to contact Zoning/Planning department for approval prior to permit. This department will not review the plan electronically. | | Zoning/Planning | 1393564 |
Waste Water Div | Original | / | 10/5/2020 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 1393563 |
Fire | Original | / | 10/5/2020 | SYSTEM | SYSTEM | You will need to contact Fire department for approval prior to permit. This department will not review the plan electronically. | | Fire | 1393562 |
Water Division | Original | / | 10/5/2020 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 1393561 |
Floodplain | Original | N | 10/5/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7406200003) | | Floodplain | 1393560 |