Plumbing | Splice 01/19/21 | A | 2/1/2021 | SHANEN | SHANEN | Delta 2 revisions: P001 adjusted fixture schedule and calculations, PD111A adjusted water demo plan, P111, P111A adjusted waste & vent and domestic water plan | | Plumbing | 1449152 |
Resubmittal 2 | Splice 01/19/21 | / | 2/1/2021 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1449106 |
Plumbing | Splice 01/19/21 | D | 1/28/2021 | SHANEN | SHANEN | Sheet PD111A: Drinking fountain is a required fixture and must remain if existing. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1447304 |
Resubmittal 1 | Splice 01/19/21 | / | 1/27/2021 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1447201 |
Plumbing | Splice 01/19/21 | D | 1/20/2021 | SHANEN | SHANEN | All fixtures must be listed with manufacturer's model numbers per PPRBD commercial plumbing plan review requirements. HD Supply is a supplier and not the manufacturer. No information found for referenced model number WMDT-60. Provide manufacturer's cut sheets for drip tray and hand held sprayer. P111: Water connection to drip tray does not comply with section 608.13 Backflow protection and 608.13.1 Air gap. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1441913 |
CO Springs Hazmat | Original | A | 12/21/2020 | CSFIRE | CSFIRE | Plans acceptable. Fees to be paid through RBD. (see full review) | smitty91 | CO Springs Hazmat | 1430384 |
Resubmittal 2 | Original | / | 12/21/2020 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1430162 |
CO Springs Hazmat | Original | D | 12/10/2020 | CSFIRE | CSFIRE | Additional information is needed. See plan review comments and resubmit. You are responsible for reviewing the disapproval comments found on the CSFD website and responding to them in your resubmittal to RBD: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
Note it may take up to an hour for the review comments to appear. (see full review) | smitty91 | CO Springs Hazmat | 1425421 |
CO Springs Fire | Original | N | 12/4/2020 | CSFIRE | CSFIRE | Hazmat Review required NO FIRE FINAL REQUIRED FOR CONSTRUCTION SERVICES | rpeterson | CO Springs Fire | 1422520 |
Plumbing | Original | A | 12/3/2020 | SHANEN | SHANEN | | | Plumbing | 1421972 |
Construction | Original | A | 12/3/2020 | DANM | DANM | | | Construction | 1421956 |
Electronic Plan | Original | / | 12/3/2020 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1421952 |
Enumeration | Original | A | 12/3/2020 | BRENT | BRENT | | | Enumeration | 1421843 |
Electronic Plan | Original | / | 12/3/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1421804 |
Resubmittal 1 | Original | / | 12/2/2020 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1421658 |
CO Springs Fire | Original | D | 11/16/2020 | CSFIRE | CSFIRE | https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp | rpeterson | CO Springs Fire | 1413377 |
CO Springs Hazmat | Original | D | 11/16/2020 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1413376 |
Health Dept. | Original | N | 11/10/2020 | HEALTHDEPT | HEALTHDEPT | Not applicable. AB | abrannon | Health Dept. | 1410826 |
Electronic Plan | Original | / | 11/9/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1409528 |
Electronic Plan | Original | / | 11/9/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1409526 |
Plumbing | Original | D | 11/9/2020 | SHANEN | SHANEN | Show all existing restroom fixtures and service sink on backgrounds. Per sheet A0.00 there is 1 drinking fountain provided, show the location on the plumbing plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1409525 |
Electronic Plan | Original | / | 11/9/2020 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1409508 |
Electrical | Original | A | 11/6/2020 | SHELBY | SHELBY | | | Electrical | 1409376 |
Electronic Plan | Original | / | 11/6/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1409370 |
Mechanical | Original | N | 11/6/2020 | JUSTINC | JUSTINC | No new or revised mechanical scope indicated | | Mechanical | 1409322 |
Electronic Plan | Original | / | 11/6/2020 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1409317 |
CO Springs DRE | Original | N | 11/6/2020 | DFOXX | DFOXX | Interior remodel only, no change of use. (see full review) | | CO Springs DRE | 1409225 |
Zoning/Planning | Original | / | 11/6/2020 | DFOXX | DFOXX | In Current Review by DFOXX | | Zoning/Planning | 1409172 |
CSU Water | Original | N | 11/6/2020 | CSUREVIEW | CSUREVIEW | No new water service outside of building. Backflow OK. KDS | kschelhaas | CSU Water | 1409062 |
CSU Waste Water | Original | N | 11/6/2020 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. KDS | kschelhaas | CSU Waste Water | 1409061 |
Construction | Original | A | 11/6/2020 | DANM | DANM | | | Construction | 1409005 |
Electronic Plan | Original | / | 11/6/2020 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1408857 |
Enumeration | Original | D | 10/29/2020 | BRENT | BRENT | There are multiple addresses on this parcel. Include a site plan showing the tenant spaces with addressing and area of work highlighed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1405582 |
Electronic Plan | Original | / | 10/29/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1405578 |
Floodplain | Original | N | 10/28/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6418318024) | | Floodplain | 1404861 |