Mechanical | Splice 08/26/21 | A | 8/27/2021 | DALEH | DALEH | clouds change gas pipe | | Mechanical | 1553778 |
Mechanical | Splice 06/15/21 | A | 7/21/2021 | DALEH | DALEH | Clouds | | Mechanical | 1533456 |
Resubmittal 3 | Splice 06/15/21 | / | 7/20/2021 | NICKH | NICKH | Resubmittal #3 | | Resubmittal 3 | 1533274 |
Mechanical | Splice 06/15/21 | D | 7/16/2021 | DALEH | DALEH | Missing sheets M2.0 and M3.1 (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1531435 |
Resubmittal 2 | Splice 06/15/21 | / | 7/16/2021 | NICKH | NICKH | Resubmittal #2 | | Resubmittal 2 | 1531369 |
Electrical | Splice 06/15/21 | A | 7/6/2021 | BERTHA | BERTHA | Added water heater. | | Electrical | 1526108 |
Electronic Plan | Splice 06/15/21 | / | 7/6/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1526089 |
Mechanical | Splice 06/15/21 | D | 7/6/2021 | DALEH | DALEH | Only provide sheets that have changes and that are clouded Remove all others that have no changes or clouds (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1525742 |
Resubmittal 1 | Splice 06/15/21 | / | 7/2/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1525616 |
Mechanical | Splice 06/15/21 | D | 6/16/2021 | DALEH | DALEH | Revise your furnace detail page Revise your furnace schedules Revise your ventilation schedule previous approval shows natural ventilation for shop 1 See plans for comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1517255 |
Plumbing | Splice 06/15/21 | A | 6/15/2021 | SHANEN | SHANEN | Delta 4 revisions: Adjusted sheet P-0.0 and P-1.0. | | Plumbing | 1516605 |
Electrical | Splice 06/15/21 | D | 6/15/2021 | BERTHA | BERTHA | Provide revised Panel A schedule.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1516569 |
Electronic Plan | Splice 06/15/21 | / | 6/15/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1516560 |
County Zoning | Original | A | 3/16/2021 | DSDRANGEL | DSDRANGEL | | | County Zoning | 1471016 |
Resubmittal 5 | Original | / | 3/16/2021 | SHELLEY | SHELLEY | Resubmittal #5 | | Resubmittal 5 | 1470987 |
Electrical | Original | A | 2/24/2021 | BERTHA | BERTHA | | | Electrical | 1461956 |
Black Forest Fire (CSFD) | Original | A | 2/24/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the approval comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | Black Forest Fire (CSFD) | 1461497 |
County Zoning | Original | D | 2/24/2021 | DSDRANGEL | DSDRANGEL | Site development plan is not yet approved. Reference file PPR2023. | | County Zoning | 1461143 |
Construction | Original | A | 2/24/2021 | MICHAELA | MICHAELA | | | Construction | 1461106 |
Resubmittal 4 | Original | / | 2/23/2021 | JAY | JAY | Resubmittal #4 | | Resubmittal 4 | 1460945 |
Plan Coordinator | Original | D | 2/23/2021 | MICHAELA | MICHAELA | Disapprove all remaining departments to allow plan to be resubmitted (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1460680 |
Electrical | Original | A | 2/23/2021 | BERTHA | BERTHA | | | Electrical | 1460660 |
Mechanical | Original | A | 2/23/2021 | DALEH | DALEH | | | Mechanical | 1460359 |
Plumbing | Original | A | 2/22/2021 | SHANEN | SHANEN | | | Plumbing | 1460094 |
County Zoning | Original | D | 2/22/2021 | DSDRANGEL | DSDRANGEL | Site development plan is not yet approved. Reference file PPR2023. | | County Zoning | 1460001 |
Construction | Original | D | 2/22/2021 | MICHAELA | MICHAELA | See plan (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1459895 |
Resubmittal 3 | Original | / | 2/19/2021 | SHELLEY | SHELLEY | Resubmittal #3 | | Resubmittal 3 | 1459097 |
Black Forest Fire (CSFD) | Original | D | 2/16/2021 | CSFIRE | CSFIRE | previous comments not addressed:
1. Address RBD comments regarding F1 fire areas and fire sprinklers.
2. any combustible wood dust producing operations involved with the F1 occupancy and assembling roof structures? (see full review) | csfdit | Black Forest Fire (CSFD) | 1456673 |
Electrical | Original | D | 2/11/2021 | BERTHA | BERTHA | Pending construction review.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1454853 |
Electronic Plan | Original | / | 2/11/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1454852 |
County Zoning | Original | D | 2/11/2021 | DSDRANGEL | DSDRANGEL | Site development plan is not yet approved. Reference file PPR2023. | | County Zoning | 1454822 |
Mechanical | Original | D | 2/11/2021 | DALEH | DALEH | Pending Construction review comments (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1454811 |
Plumbing | Original | D | 2/11/2021 | SHANEN | SHANEN | Pending outcome of variance request. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1454727 |
Construction | Original | D | 2/11/2021 | MICHAELA | MICHAELA | Non-separated use require the worst case occupancy to be extended to the entire structure. You need to separate the F-1 occupancy from the other occupancies with listed wall and horizontal assemblies or add a sprinkler system to the structure. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1454701 |
Resubmittal 2 | Original | / | 2/10/2021 | BECKYA | BECKYA | Resubmittal #2 | | Resubmittal 2 | 1454333 |
Black Forest Hazmat | Original | N | 1/19/2021 | CSFIRE | CSFIRE | | dwithee | Black Forest Hazmat | 1441124 |
Black Forest Fire (CSFD) | Original | D | 1/19/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
Please allow up to 1 hour for comments to load to the server (see full review) | csfdit | Black Forest Fire (CSFD) | 1441122 |
Black Forest Fire (CSFD) | Original | D | 1/19/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
Please allow up to 1 hour for comments to load to the server (see full review) | csfdit | Black Forest Fire (CSFD) | 1441121 |
Electrical | Original | D | 1/13/2021 | BERTHA | BERTHA | Pending approval in Construction.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1439218 |
Electronic Plan | Original | / | 1/12/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1439036 |
Electronic Plan | Original | / | 1/12/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1439025 |
Mechanical | Original | D | 1/12/2021 | DALEH | DALEH | No revisions on plans to previous comments about room usage See previous comments and resubmit revisions to comments on plans (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1438923 |
Plumbing | Original | D | 1/12/2021 | SHANEN | SHANEN | B occupancy with an occupant load of 33 requires separate mens and womens toilet facilities and a high/low drinking fountain per 2015 IPC section 403.1 Minimum number of fixtures. Please know that chapter 29 of the IBC has been deleted in its entirety by the state of Colorado and all plumbing fixture requirements are per 2015 IPC. Schedule required high/low drinking fountain.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1438643 |
County Zoning | Original | D | 1/12/2021 | DSDRANGEL | DSDRANGEL | Site development plan is not yet approved. Reference file PPR2023. | | County Zoning | 1438598 |
Construction | Original | D | 1/12/2021 | MICHAELA | MICHAELA | Per the occupancy explanation letter the area where the wood models will be created/constructed will be an F-1 occupancy. Please locate that space and revise the code study accordingly. F-1 occupancy may not be 2-story and non-sprinklered. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1438538 |
Resubmittal 1 | Original | / | 1/11/2021 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1438171 |
Black Forest Hazmat | Original | D | 12/11/2020 | CSFIRE | CSFIRE | | dwithee | Black Forest Hazmat | 1426224 |
Black Forest Fire (CSFD) | Original | D | 12/11/2020 | CSFIRE | CSFIRE | You are responsible for reviewing the disapproval comments found on the CSFD website and responding to them in your resubmittal to RBD: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp (see full review) | csfdit | Black Forest Fire (CSFD) | 1426223 |
Health Dept. | Original | N | 12/7/2020 | HEALTHDEPT | HEALTHDEPT | Not applicable. KM | kmaldonado | Health Dept. | 1423364 |
Electrical | Original | D | 12/7/2020 | BERTHA | BERTHA | 1. Provide indication of compliance with 110.26(A)(3) - equipment over wireway. 2. Provide SCA and SCCR for air conditioning and refrigeration equipment.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1422971 |
Plumbing | Original | D | 12/2/2020 | SHANEN | SHANEN | B occupancy with an occupant load of 33 requires separate mens and womens toilet facilities and a high/low drinking fountain per 2015 IPC section 403.1 Minimum number of fixtures. Schedule required high/low drinking fountain. Building drain must discharge to a public sewer or an approved private sewage disposal system (referenced leach field not adequate must discharge to a septic tank if private). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1421387 |
Mechanical | Original | D | 12/2/2020 | DALEH | DALEH | Show complete condensate routing, size and material for all equipment What kind of work is being done in shop 1 and 2 and open work area ? See Construction plan reviewers comments about room usage Provide equipment schedules Explain the intent of this room Hair ? Nails ? ETC....... (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1421372 |
Electronic Plan | Original | / | 12/2/2020 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1421348 |
County Zoning | Original | D | 12/2/2020 | DSDRANGEL | DSDRANGEL | Site development plan is not yet approved. Reference file PPR2023. | | County Zoning | 1421013 |
County Water | Original | N | 12/1/2020 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities water service territory. KDS | kschelhaas | County Water | 1420722 |
County Waste Water | Original | N | 12/1/2020 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities wastewater service territory. KDS | kschelhaas | County Waste Water | 1420721 |
Zoning/Planning | Original | / | 12/1/2020 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 1420623 |
Construction | Original | D | 12/1/2020 | MICHAELA | MICHAELA | Provide IECC certificate for envelope compliance. Provide Code Data - Codes being complied with Design loads Occupancy Occupant load, etc. Clarify use of "Shop 1 & 2" and "Open Work area". Does not seem to be a B occupancy label. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1420608 |
Electronic Plan | Original | / | 12/1/2020 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1420538 |
Enumeration | Original | N | 12/1/2020 | BRENT | BRENT | | | Enumeration | 1420404 |
Electronic Plan | Original | / | 12/1/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1420386 |
Floodplain | Original | N | 11/29/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 5207000004) | | Floodplain | 1419206 |