Electrical | Original | A | 1/29/2021 | SHELBY | SHELBY | | | Electrical | 1448719 | Resubmittal 3 | Original | / | 1/28/2021 | JAY | JAY | Resubmittal #3 | | Resubmittal 3 | 1447999 | Electrical | Original | D | 1/20/2021 | SHELBY | SHELBY | No change made (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1442602 | Resubmittal 2 | Original | / | 1/19/2021 | JAY | JAY | Resubmittal #2 | | Resubmittal 2 | 1441589 | Electrical | Original | D | 12/21/2020 | SHELBY | SHELBY | 500 KVA transformer primary conductor incorrect ( 570 amps of conductor on 800 amp OCD. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1430564 | Resubmittal 1 | Original | / | 12/18/2020 | BECKYA | BECKYA | Resubmittal #1 | | Resubmittal 1 | 1429891 | Electrical | Original | D | 12/15/2020 | SHELBY | SHELBY | 1. Conductor 15 is incorrect. 2. Show supply side bonding jumper size and quantity for 500 KVA transformer secondary. 3. Please make clear the purpose of the 600 amp disconnect on the primary side of the 500 KVA transformer ( disconnect is shown as connected to the primary side but not in the primary conductor). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1427843 | Enumeration | Original | N | 12/15/2020 | BRENT | BRENT | | | Enumeration | 1427542 | Electronic Plan | Original | / | 12/15/2020 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1427532 | Floodplain | Original | N | 12/14/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6408423013) | | Floodplain | 1426435 |
|
| |
|