Electrical | Original | A | 1/29/2021 | SHELBY | SHELBY | | | Electrical | 1448635 |
Mechanical | Original | A | 1/28/2021 | DALEH | DALEH | | | Mechanical | 1447758 |
Construction | Original | N | 1/28/2021 | SHELLEY | SHELLEY | Equipment replacement. No construction workk. | | Construction | 1447712 |
Resubmittal 1 | Original | / | 1/28/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1447543 |
CO Springs Hazmat | Original | N | 1/4/2021 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1434407 |
CO Springs Fire | Original | N | 1/4/2021 | CSFIRE | CSFIRE | | rpeterson | CO Springs Fire | 1434406 |
Plumbing | Original | N | 12/21/2020 | SHANEN | SHANEN | No plumbing scope of work, issue no permit. | | Plumbing | 1430277 |
Mechanical | Original | A | 12/17/2020 | DALEH | DALEH | | | Mechanical | 1429102 |
Electronic Plan | Original | / | 12/17/2020 | DALEH | DALEH | In Current Review by DALEH | | Electronic Plan | 1428960 |
CO Springs DRE | Original | N | 12/16/2020 | KCARLEO | KCARLEO | OK ONLY FOR MECHANICAL WORK ON ROOF WITH NO OTHER EXTERIOR CHANGES. (see full review) | | CO Springs DRE | 1428656 |
Zoning/Planning | Original | / | 12/16/2020 | KCARLEO | KCARLEO | In Current Review by KCARLEO | | Zoning/Planning | 1428648 |
Electrical | Original | D | 12/16/2020 | SHELBY | SHELBY | Show SCA and SCCR at/for cooling equipment in this scope of work. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1428562 |
Electronic Plan | Original | / | 12/16/2020 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1428558 |
CSU Water | Original | N | 12/16/2020 | CSUREVIEW | CSUREVIEW | No plumbing work. KDS | kschelhaas | CSU Water | 1428539 |
CSU Waste Water | Original | N | 12/16/2020 | CSUREVIEW | CSUREVIEW | No plumbing work. KDS | kschelhaas | CSU Waste Water | 1428537 |
Construction | Original | D | 12/16/2020 | LBENNETT | LBENNETT | Please provide an engineers letter verifying the roofs structural ability to support the 5 new rooftop AHUs (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1428525 |
Electronic Plan | Original | / | 12/16/2020 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1428502 |
Enumeration | Original | N | 12/15/2020 | AMY | AMY | | | Enumeration | 1427776 |
Electronic Plan | Original | / | 12/15/2020 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1427764 |
Floodplain | Original | N | 12/14/2020 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6217204001) | | Floodplain | 1427102 |