Electrical | Splice 08/01/23 | A | 8/7/2023 | BERTHA | BERTHA | Revised one-line. | | Electrical | 1881601 |
Electronic Plan | Splice 08/01/23 | / | 8/7/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1881588 |
Resubmittal 1 | Splice 08/01/23 | / | 8/3/2023 | QUINTONW | QUINTONW | Resubmittal #1 | | Resubmittal 1 | 1879597 |
Electrical | Splice 08/01/23 | D | 8/1/2023 | BERTHA | BERTHA | 1. Please see either the "Progress Set" or the "Review Set" for required corrections. 2. The "Review Set" will become available after all department reviews are complete. 3. Electronic Plans may be re-submitted after the "Review Set" has been created. 4. After all reviews are complete, paper plans may be picked up from the same location they were submitted. | | Electrical | 1878828 |
Electronic Plan | Splice 08/01/23 | / | 8/1/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1878810 |
Electrical | Splice 06/03/23 | A | 6/7/2023 | BERTHA | BERTHA | Revised power, revised schedules. | | Electrical | 1853134 |
Electronic Plan | Splice 06/03/23 | / | 6/7/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1852936 |
CO Springs Fire | Splice 06/03/23 | A | 6/5/2023 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1851570 |
Plumbing | Splice 06/03/23 | A | 6/5/2023 | SHANEN | SHANEN | Delta 18 revisions: Adjusted sheet P0.0, P0.2, P1.0, P2.0, P2.1 and P3.0. | | Plumbing | 1851506 |
Construction | Splice 06/03/23 | A | 6/5/2023 | DANM | DANM | Minor revisions to Pantry and Fitness equipment/fixtures layouts | | Construction | 1851420 |
Electronic Plan | Splice 06/03/23 | / | 6/5/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1851264 |
Electrical | Splice 03/30/23 | A | 4/3/2023 | BERTHA | BERTHA | Revised power and schedules. | | Electrical | 1824440 |
Electronic Plan | Splice 03/30/23 | / | 4/3/2023 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1824419 |
CO Springs Fire | Splice 03/30/23 | A | 3/31/2023 | CSFIRE | CSFIRE | notes for duct penetrations at floor and ceiling assemblies (see full review) | Jacob.Watson | CO Springs Fire | 1823713 |
Mechanical | Splice 03/30/23 | A | 3/31/2023 | JUSTINC | JUSTINC | Layout revisions | | Mechanical | 1823642 |
Construction | Splice 03/30/23 | A | 3/30/2023 | DANM | DANM | Listed assembly for duct wrap and firestop penetration for ventilation ducts | | Construction | 1823331 |
Electronic Plan | Splice 03/30/23 | / | 3/30/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1823297 |
Mechanical | Splice 03/10/23 | A | 3/22/2023 | JUSTINC | JUSTINC | Revised laundry | | Mechanical | 1819594 |
Resubmittal 1 | Splice 03/10/23 | / | 3/22/2023 | KALLISTAJ | KALLISTAJ | Resubmittal #1 | | Resubmittal 1 | 1819587 |
Electrical | Splice 03/10/23 | A | 3/13/2023 | BERTHA | BERTHA | Revised power plan and schedules. | | Electrical | 1815405 |
CO Springs Fire | Splice 03/10/23 | A | 3/13/2023 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1814866 |
Mechanical | Splice 03/10/23 | D | 3/10/2023 | JUSTINC | JUSTINC | Provide revised mechanical pages to match these changes
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1814638 |
Plumbing | Splice 03/10/23 | A | 3/10/2023 | SHANEN | SHANEN | Delta 15 revisions: Adjusted sheet P0.0, P1.1, P1.2, P2.1 and P2.2. | | Plumbing | 1814620 |
Construction | Splice 03/10/23 | A | 3/10/2023 | DANM | DANM | Guest Laundry Room changes | | Construction | 1814582 |
Electronic Plan | Splice 03/10/23 | / | 3/10/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1814561 |
Mechanical | Splice 02/02/23 | A | 2/9/2023 | JUSTINC | JUSTINC | Layout, schedule, and note revisions | | Mechanical | 1801154 |
Resubmittal 1 | Splice 02/02/23 | / | 2/9/2023 | SIERRAC | SIERRAC | Resubmittal #1 | | Resubmittal 1 | 1800925 |
Mechanical | Splice 02/02/23 | D | 2/2/2023 | JUSTINC | JUSTINC | Please see the (M) sheets for specific comments related to this splice review.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1798058 |
Construction | Splice 01/13/23 | A | 1/13/2023 | DANM | DANM | Revised listing for floor/ceiling assembly | | Construction | 1791381 |
CO Springs Fire | Splice 11/01/22 | A | 11/14/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1769877 |
Mechanical | Splice 11/01/22 | A | 11/14/2022 | JUSTINC | JUSTINC | Various layout and schedule revisions | | Mechanical | 1769787 |
Construction | Splice 11/01/22 | A | 11/11/2022 | DANM | DANM | Various revisions throughout architectural and structural including changing guest room to restrooms and storage | | Construction | 1769512 |
Electronic Plan | Splice 11/01/22 | / | 11/8/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1767979 |
Resubmittal 1 | Splice 11/01/22 | / | 11/8/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #1 | | Resubmittal 1 | 1767932 |
Plumbing | Splice 11/01/22 | A | 11/2/2022 | TCRIPPEN | TCRIPPEN | Approved. | | Plumbing | 1764983 |
Mechanical | Splice 11/01/22 | D | 11/2/2022 | JUSTINC | JUSTINC | How protecting?When ducts are indicated as penetrating a rated assembly a fire or fire/smoke damper is required. When intent is to use a code section and exception to not install a damper then a sheet note indicating code section and all exceptions used are to be provided on the plan. Tag at penetration accordingly. If dampers are existing indicate on plan. Verify if above or below rated horizontal assembly? If above verify how protecting penetrations
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Mechanical | 1764799 |
Electrical | Splice 11/01/22 | A | 11/2/2022 | DANIELG | DANIELG | Delta revision 13. As built. | | Electrical | 1764776 |
Electronic Plan | Splice 11/01/22 | / | 11/2/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1764734 |
Electronic Plan | Splice 11/01/22 | / | 11/2/2022 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1764674 |
CO Springs Fire | Splice 11/01/22 | D | 11/2/2022 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! | rpeterson | CO Springs Fire | 1764638 |
Construction | Splice 11/01/22 | D | 11/2/2022 | DANM | DANM | Provide revised Code Data and Life Safety Plan sheets reflecting change of sleeping unit to restrooms and storage.
PLEASE NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF CORRECTIONS REQUIRED ON THE PLAN 1. FOR ELECTRONIC SUBMITTALS, A "PROGRESS SET" IS NOW AVAILABLE FOR REVIEW OF REQUIRED CORRECTIONS. 2. FOR ALL SUBMITTALS, A "REVIEW SET" WILL BE AVAILABLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. 3. PLANS CANNOT BE RE-SUBMITTED UNTIL EVERY DEPARTMENT HAS COMPLETED THIS CURRENT ROUND OF REVIEW. | | Construction | 1764589 |
Electronic Plan | Splice 11/01/22 | / | 11/1/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1764496 |
CO Springs Fire | Splice 10/13/22 | A | 10/19/2022 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 1758380 |
Construction | Splice 10/13/22 | A | 10/18/2022 | DANM | DANM | Revised and new fire-resistance rated assemblies | | Construction | 1757983 |
Electronic Plan | Splice 10/13/22 | / | 10/18/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1757976 |
Electrical | Splice 08/04/22 | A | 9/26/2022 | DANIELG | DANIELG | Various revisions throughout electrical sheets. Delta revision 9 and 10. | | Electrical | 1746124 |
Resubmittal 5 | Splice 08/04/22 | / | 9/25/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #5 | | Resubmittal 5 | 1746075 |
Plumbing | Splice 08/30/22 | A | 9/22/2022 | TCRIPPEN | TCRIPPEN | Approved Splice see clouded areas on plan set, ///// 5 hour review total \\\\\ | | Plumbing | 1745408 |
Resubmittal 2 | Splice 08/30/22 | / | 9/22/2022 | SIERRAC | SIERRAC | Resubmittal #2 | | Resubmittal 2 | 1745370 |
Electrical | Splice 08/04/22 | D | 9/22/2022 | DANIELG | DANIELG | Panel schedules 1C and 3C show the total load exceeding its main OCPD.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1744981 |
Electronic Plan | Splice 08/04/22 | / | 9/22/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1744958 |
Resubmittal 4 | Splice 08/04/22 | / | 9/21/2022 | ANDREAL | ANDREAL | Resubmittal #4 | | Resubmittal 4 | 1744833 |
Plumbing | Splice 08/30/22 | D | 9/14/2022 | SHANEN | SHANEN | P3.0, P3.1, P3.2, P3.3: Floor drains located under clothes washers do not comply with section 802.3 Waste receptors. P4.0 ISO 4: WB-1s do not comply with sections 1002.3 Prohibited traps and 905.4 Vertical rise of vent. //// Note: 2 hours 30 minutes reviewing this splice so far.\\\\ (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1740908 |
Resubmittal 1 | Splice 08/30/22 | / | 9/14/2022 | SIERRAC | SIERRAC | Resubmittal #1 | | Resubmittal 1 | 1740792 |
Electrical | Splice 08/04/22 | D | 9/9/2022 | DANIELG | DANIELG | Provide AIC rating for all "S" panels.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1739528 |
Electronic Plan | Splice 08/04/22 | / | 9/9/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1739460 |
Resubmittal 3 | Splice 08/04/22 | / | 9/7/2022 | SIERRAC | SIERRAC | Resubmittal #3 | | Resubmittal 3 | 1738246 |
Electrical | Splice 08/04/22 | D | 9/1/2022 | BERTHA | BERTHA | Comply with previous review comment - Provide plans with all revision clouds pertaining to this splice - see original splice submittal.
Comply with previous review comment - Specify CU or AL for all conductors - CU or AL must be specified, alternatives are not allowed.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1736650 |
Electronic Plan | Splice 08/04/22 | / | 8/31/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1736296 |
Resubmittal 2 | Splice 08/04/22 | / | 8/31/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #2 | | Resubmittal 2 | 1736090 |
Mechanical | Splice 08/15/22 | A | 8/31/2022 | JUSTINC | JUSTINC | Revised penetration protection | | Mechanical | 1735922 |
Plumbing | Splice 08/30/22 | D | 8/31/2022 | SHANEN | SHANEN | P0.2: Clarify clouded area revisions where there are no apparent changes. P0.3: Lint interceptor (LT-1) removed from plumbing equipment schedule and floor plan. Describe how complying with section 1003.6 Clothes washer discharge interceptor. P1.2: 2" floor drain (FD-1) in laundry room does not comply with section 412.4 and shall be a 3" floor drain. P1.3: Cloud all revisions. P3.0, P3.1, P3.2, P3.3: Floor drains located under clothes washers does not comply with section 802.3 Waste receptors. P4.1 ISO 4: WB-1s do not comply with sections 1002.3 Prohibited traps and 905.4 Vertical rise of vent. //// Note: 1 hour 35 minutes reviewing this splice so far.\\\\ (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1735861 |
Resubmittal 1 | Splice 08/15/22 | / | 8/31/2022 | SIERRAC | SIERRAC | Resubmittal #1 | | Resubmittal 1 | 1735827 |
Electrical | Splice 08/04/22 | D | 8/25/2022 | BERTHA | BERTHA | Provide plans with all revision clouds pertaining to this splice.
Provide specific model # for breakers in series rated combinations on the plans.
Specify CU or AL for all conductors
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1733768 |
Electronic Plan | Splice 08/04/22 | / | 8/25/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1733522 |
Construction | Splice 08/04/22 | A | 8/25/2022 | DANM | DANM | Various revisions throughout architectural and structural sheets | | Construction | 1733510 |
Electronic Plan | Splice 08/04/22 | / | 8/24/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1733265 |
Resubmittal 1 | Splice 08/04/22 | / | 8/24/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #1 | | Resubmittal 1 | 1732692 |
Mechanical | Splice 08/15/22 | D | 8/16/2022 | JUSTINC | JUSTINC | Detail on is on M0.6 and the detail is for PVC concentric piping not duct. Clarify how penetrations of horizontal assembly will comply with 2015 IBC 714.4.1 - 714.4.1.2 with no damper.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1728443 |
Electrical | Splice 08/04/22 | D | 8/9/2022 | BERTHA | BERTHA | Provide compliance with 210.65 NEC - include dimension and partition of all meeting rooms per 210.65 NEC
Provide model # for breakers in series rated combinations.
Clarify feeder for Panel 1C
Privide compliance with 240.87 NEC including verification that the method chosen to reduce clearing time is set to operate at less than the available arcing current.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1725578 |
Electronic Plan | Splice 08/04/22 | / | 8/9/2022 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1725330 |
Construction | Splice 08/04/22 | D | 8/9/2022 | DANM | DANM | 2-hr lid of Corridor 006 must be a floor/ceiling assembly not a roof/ceiling assembly. Clouded structural revision 2 was already approved - remove cloud and sheet if no new revisions (Sheets S1.1, S2.1, S2.5, S3.1)
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1725258 |
Electronic Plan | Splice 08/04/22 | / | 8/5/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1723899 |
Construction | Splice 04/18/22 Trusses | A | 4/19/2022 | DANM | DANM | Deferred roof trusses | | Construction | 1667531 |
Electronic Plan | Splice 04/18/22 Trusses | / | 4/19/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1667351 |
City Engr | Original | A | 9/17/2021 | PMORRIS | PMORRIS | | | City Engr | 1563921 |
CSU Contract Admin. | Original | A | 9/10/2021 | CSUAPPSPRM | CSUAPPSPRM | Commercial water meter sizing form approved and applicable development charges and fees paid.
VLC | VCornwell | CSU Contract Admin. | 1560571 |
Gas/Elec. Utils | Original | A | 9/9/2021 | CSUREVIEW | CSUREVIEW | Comments addressed. DMM | dmakings | Gas/Elec. Utils | 1559790 |
CSU Waste Water | Original | A | 9/9/2021 | CSUREVIEW | CSUREVIEW | Comments addressed. DMM | dmakings | CSU Waste Water | 1559789 |
CSU Water | Original | A | 9/9/2021 | CSUREVIEW | CSUREVIEW | Comments addressed. DMM | dmakings | CSU Water | 1559787 |
CSU Contract Admin. | Original | D | 9/9/2021 | CSUAPPSPRM | CSUAPPSPRM | See previous comment. Requires payment of development fees/charges. Please contact Utilities Development Services at 719-668-8111 for assistance or to request an estimate. VLC | VCornwell | CSU Contract Admin. | 1559685 |
Construction | Original | A | 9/8/2021 | DANM | DANM | | | Construction | 1559399 |
CO Springs DRE | Original | A | 9/7/2021 | WGRAY | WGRAY | Phase 1 (Hotel Addition) site improvements must conform to the approved development plan (dated 07/06/2021), AR DP 16-00396-A1MJ20. (see full review) | | CO Springs DRE | 1558801 |
Electronic Plan | Original | / | 9/3/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1558169 |
Enumeration | Original | A | 9/3/2021 | AMY | AMY | Copy of the final recorded plat received. Secondary Addressing will be reviewed and approved through CSFD. | | Enumeration | 1557724 |
Electronic Plan | Original | / | 9/3/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1557709 |
Resubmittal 4 | Original | / | 9/2/2021 | ANDREAL | ANDREAL | Resubmittal #4 | | Resubmittal 4 | 1557557 |
Mechanical | Original | A | 7/21/2021 | JUSTINC | JUSTINC | | | Mechanical | 1533848 |
CO Springs DRE | Original | D | 7/20/2021 | WGRAY | WGRAY | Update the site plan and architectural plans to match the approved development plan. If you have any questions, please contact William Gray at 719-385-5090 or william.gray@coloradosprings.gov. (see full review) | | CO Springs DRE | 1533301 |
City Engr | Original | D | 7/16/2021 | PMORRIS | PMORRIS | Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit. | | City Engr | 1531301 |
CSU Contract Admin. | Original | D | 7/15/2021 | CSUAPPSPRM | CSUAPPSPRM | See previous comment. Requires payment of development fees/charges. Please contact Utilities Development Services at 719-668-8111 for assistance or to request an estimate. VLC | VCornwell | CSU Contract Admin. | 1531027 |
Zoning/Planning | Original | / | 7/15/2021 | WGRAY | WGRAY | In Current Review by WGRAY | | Zoning/Planning | 1531017 |
CSU Water | Original | D | 7/15/2021 | CSUREVIEW | CSUREVIEW | See previous comments AJ | ajuvera | CSU Water | 1530818 |
CSU Waste Water | Original | D | 7/15/2021 | CSUREVIEW | CSUREVIEW | See previous comments AJ | ajuvera | CSU Waste Water | 1530817 |
Gas/Elec. Utils | Original | D | 7/15/2021 | CSUREVIEW | CSUREVIEW | See previous comments AJ | ajuvera | Gas/Elec. Utils | 1530815 |
Electronic Plan | Original | / | 7/15/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1530775 |
Construction | Original | D | 7/14/2021 | LBENNETT | LBENNETT | Sheet A2.21/2.30/9.5: Please clarify location of 1-hr fire partition where corridor configuration has changed Sheet A0.13/9.5 Please provide a listing for the wood beams
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1530606 |
Electronic Plan | Original | / | 7/14/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1530372 |
Enumeration | Original | D | 7/13/2021 | AMY | AMY | A copy of the final recorded plat is required prior to approval in the Enumerations department on any COMMERCIAL plan submittal. Amy@pprbd.org
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1529800 |
Electronic Plan | Original | / | 7/13/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1529795 |
Resubmittal 3 | Original | / | 7/13/2021 | ANDREAL | ANDREAL | Resubmittal #3 | | Resubmittal 3 | 1529634 |
CO Springs DRE | Original | D | 6/15/2021 | WGRAY | WGRAY | Approved development plan must be attached to the permit set. Contact William Gray at 719-385-5090 with any questions. WEG (see full review) | | CO Springs DRE | 1517134 |
Electrical | Original | A | 6/11/2021 | SHELBY | SHELBY | | | Electrical | 1515439 |
CSU Contract Admin. | Original | D | 6/11/2021 | CSUAPPSPRM | CSUAPPSPRM | Requires payment of applicable utility charges/fees. Please contact our office at 719-668-8111 for additional information on charges/feeS.
VLC | VCornwell | CSU Contract Admin. | 1515285 |
City Engr | Original | D | 6/10/2021 | PMORRIS | PMORRIS | Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) into the building permit. Upload a copy of the approved Development Plan into the building permit. | | City Engr | 1514709 |
Mechanical | Original | D | 6/9/2021 | JUSTINC | JUSTINC | Typical first floor - Fans appear to penetrate the horizontal assembly with the duct routed within the assembly? How will fans be protected without radiation dampers.If fans and duct are below rated assembly, How protecting rated wall penetrations? Pleas clarify Note 6 does not apply to exhaust only S/A and R/A
Clarify this layout? This does not appear to match the detail TYPICAL Room exhaust floors 2-4
Revised detail indicates duct in wall. clarify or revise Floor plan sheets note 4
Clarify roof / ceiling membrane penetrations provide detail for V-A structure. Verify with Architect as this will most likely also need to be indicated on (A) sheets as well.
Exhaust on floors 2-4 indicate fan located in drop ceiling not within wall assembly. This does not meet exception 1 of 2015 IMC 607.6.1. As indicated need to clarify how the fire partition wall assembly will be protected. The revised detail shows ducts within wall not in chase or shaft.
See Plans.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1514141 |
CSU Water | Original | D | 6/9/2021 | CSUREVIEW | CSUREVIEW | See previous comments. SSM | stefanm | CSU Water | 1513993 |
CSU Waste Water | Original | D | 6/9/2021 | CSUREVIEW | CSUREVIEW | See previous comments. SSM | stefanm | CSU Waste Water | 1513992 |
Gas/Elec. Utils | Original | D | 6/9/2021 | CSUREVIEW | CSUREVIEW | See previous comments. SSM | stefanm | Gas/Elec. Utils | 1513991 |
Plumbing | Original | A | 6/9/2021 | SHANEN | SHANEN | | | Plumbing | 1513965 |
Zoning/Planning | Original | / | 6/9/2021 | WGRAY | WGRAY | In Current Review by WGRAY | | Zoning/Planning | 1513880 |
Electronic Plan | Original | / | 6/9/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1513824 |
Construction | Original | D | 6/9/2021 | DANM | DANM | Sheet A0.13 These beam listings are for non-combustible construction - cannot be used for V-A construction - Engineering Judgement from a fire protection engineer will be required Sheet A2.24 Enlarged Plan - King Standard shows rated walls at roof drains but Life Safety plans show non-rated walls - clarify Sheet A9.5 Dropped beams in Details 3 & 4 need listed assembly for 1-hr rating
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1513798 |
Electronic Plan | Original | / | 6/8/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1513310 |
Enumeration | Original | D | 6/8/2021 | AMY | AMY | Approval of plan pending : 1. Enumerations will review the mylar prior to plat for address placement, street names, and title block.
$10.00 per lot & tract platting fee will be due at the time of the review of the mylar, (2 addresses per lot and tract). If an address is not needed on a tract then no fee applies. Check should be made out to PIKES PEAK REGIONAL BUILDING DEPARTMENT or PPRBD. Paid directly to the Enumerations Department.
A copy of the final recorded plat is required prior to approval in the Enumerations department on any COMMERCIAL plan submittal. Amy@pprbd.org
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1513227 |
Electronic Plan | Original | / | 6/8/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1513218 |
Resubmittal 2 | Original | / | 6/7/2021 | DANM | DANM | Resubmittal #2 | | Resubmittal 2 | 1512192 |
CO Springs Fire | Original | A | 5/24/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1505528 |
Plumbing | Original | D | 5/11/2021 | SHANEN | SHANEN | The increased occupant load of this addition requires the installation of a high/low drinking fountain. Existing drinking fountain is a single level and does not comply with section 410.3 Provide high and low drinking fountains. Schedule and show location of and piping for the required drinking fountain. ////PPRBD note added 5/27/21: Section 410.4 Substitution requirements are met.\\\\ (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1499033 |
Electronic Plan | Original | / | 5/11/2021 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1498993 |
CSU Contract Admin. | Original | D | 5/11/2021 | CSUAPPSPRM | CSUAPPSPRM | Requires payment of development fees/charges. Please contact Utilities Development Services at 719-668-8111 for assistance or to request an estimate.
VLC | VCornwell | CSU Contract Admin. | 1498898 |
CO Springs DRE | Original | D | 5/10/2021 | WGRAY | WGRAY | Please attach one copy of the approved development plan set to each set of construction drawings submitted to the Regional Building Department in conjunction with the building permit application. WEG (see full review) | | CO Springs DRE | 1498258 |
Zoning/Planning | Original | / | 5/7/2021 | WGRAY | WGRAY | In Current Review by WGRAY | | Zoning/Planning | 1497186 |
Electrical | Original | D | 5/7/2021 | SHELBY | SHELBY | Please address previous review comments 2 and 4. Door swing for room Mech 109 must swing out on Architectural and Electrical sheets. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1497170 |
Electronic Plan | Original | / | 5/7/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1497143 |
City Engr | Original | D | 5/7/2021 | PMORRIS | PMORRIS | Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) . Upload a copy of the approved Development Plan. | | City Engr | 1497119 |
CSU Water | Original | D | 5/6/2021 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Water | 1496921 |
CSU Waste Water | Original | D | 5/6/2021 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | CSU Waste Water | 1496920 |
Gas/Elec. Utils | Original | D | 5/6/2021 | CSUREVIEW | CSUREVIEW | See previous comments. MLW | mlwilliams | Gas/Elec. Utils | 1496919 |
Mechanical | Original | D | 5/6/2021 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
Architect and mechanical engineer need to coordinate on exhaust routing and what shaft will be. (A) sheets do not indicate this as shaft.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1496898 |
Construction | Original | D | 5/6/2021 | DANM | DANM | Code Study Form - there still seems to be a discrepancy with the areas listed on Page 2 vs. the total addition area listed on Page 1 A0.1 - 1st floor is non-separated mixed occupancies so sum of the ratios chart does not apply A0.1C - CRS 9-5 only applies to residential developments with dwelling units, not to typical hotels and motels A0.4 - Partition Type W2/R2 - System A only provides 1-hr rating - clarify A0.13 - Since beam listings are noncombustible construction and do not match proposed wood construction, they cannot be used - engineering judgment by a fire protection engineer required A0.14 - Listed assembly required for wall behind recessed portion for panel - pre-rock is not compliant A2.21-A2.29 - Running exhaust lines in stud cavity does not match mechanical sheets which show a continuous shaft - clarify how horizontal assembly through penetration will be addressed A9.4 - Details 5 & 6 - UL n 717 is a tested assembly for a beam no a column
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1496822 |
Elevators | Original | A | 5/5/2021 | ERIC | ERIC | Otis GEN2 machineroom-less traction elevator with fire rated suspension means - 2013 Code | | Elevators | 1495962 |
Electronic Plan | Original | / | 5/5/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1495867 |
Enumeration | Original | D | 5/4/2021 | AMY | AMY | Approval of plan pending : 1. Enumerations will review the mylar prior to plat for address placement, street names, and title block.
$10.00 per lot & tract platting fee will be due at the time of the review of the mylar, (2 addresses per lot and tract). If an address is not needed on a tract then no fee applies. Check should be made out to PIKES PEAK REGIONAL BUILDING DEPARTMENT or PPRBD. Paid directly to the Enumerations Department.
A copy of the final recorded plat is required prior to approval in the Enumerations department on any COMMERCIAL plan submittal. Amy@pprbd.org (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1495514 |
Electronic Plan | Original | / | 5/4/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1495497 |
Resubmittal 1 | Original | / | 5/3/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1494504 |
CO Springs DRE | Original | D | 4/12/2021 | WGRAY | WGRAY | Approved development plan must be attached to the permit set. Contact William Gray at 719-385-5090 with any questions. WEG (see full review) | | CO Springs DRE | 1484030 |
Plumbing | Original | D | 3/17/2021 | SHANEN | SHANEN | Per sheet A0.1 2 drinking fountains and one service sink are provided. The service sink sink is provided in the existing building. The increased occupant load of this addition requires the installation of a high/low drinking fountain. Schedule and show location of and piping for the required drinking fountain. Elevator sump detail is mislabeled. Lint interceptor required for clothes washers. CSU variance letter required for indoor sand/oil interceptor. Contact Robert Bowren at 719-668-1735 or fog@csu.org. 3" FS-1 is undersized to receive a 50 gpm discharge. Discharge elevator sump indirectly to a waste receptor capable of handling a minimum of 50 gpm (100 dfu). Provide isometric and/or riser diagram for complete water distribution system showing connections to each branch and riser. Provide water supply fixture units served by each branch and riser. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1471613 |
City Engr | Original | D | 3/17/2021 | PMORRIS | PMORRIS | Upload a copy of the Stormwater Enterprise approved Grading & Erosion Control Plan (GECP) . Upload a copy of the approved Development Plan. | | City Engr | 1471574 |
CSU Contract Admin. | Original | D | 3/17/2021 | CSUAPPSPRM | CSUAPPSPRM | Requires approved Commercial Water Meter Sizing Form (CWMSF) and payment of applicable utility charges/fees. Please contact our office at 719-668-8111 or cca@csu.org for information on charges/fees and to request an estimate. ZS
CWMSF available online at: https://www.csu.org/Documents/CommercialWaterMeterSizing.pdf?csf=1&e=WVWzT5 | zshearer | CSU Contract Admin. | 1471432 |
CO Springs Hazmat | Original | N | 3/15/2021 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1470590 |
CO Springs Fire | Original | D | 3/15/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the disapproval comments found on the CSFD website and responding to them in your resubmittal to RBD: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS (see full review) | csfdit | CO Springs Fire | 1470589 |
Electronic Plan | Original | / | 3/12/2021 | TCRIPPEN | TCRIPPEN | In Current Review by TCRIPPEN | | Electronic Plan | 1469985 |
Health Dept. | Original | N | 3/11/2021 | HEALTHDEPT | HEALTHDEPT | Not applicable. AF | Amanda Furno | Health Dept. | 1469561 |
Electrical | Original | D | 3/10/2021 | SHELBY | SHELBY | 1. Electrical approval is not possible without Elevator comments being addressed. 2. Door swing for MDC electrical room violates 110.26(C) NEC. 3. Show location of suite panels comply 240.24(B)(2) NEC. Panels may not be located in rated walls. 4. Show elevator horse power on one line. Complete re review. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1468832 |
Electronic Plan | Original | / | 3/10/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1468822 |
Mechanical | Original | D | 3/10/2021 | JUSTINC | JUSTINC | MECHANICAL REVIEW INCOMPLETE
See all mechanical pages for comments associated with this review.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1468419 |
Electronic Plan | Original | / | 3/10/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1468356 |
CSU Water | Original | D | 3/9/2021 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | CSU Water | 1468073 |
CSU Waste Water | Original | D | 3/9/2021 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | CSU Waste Water | 1468072 |
Gas/Elec. Utils | Original | D | 3/9/2021 | CSUREVIEW | CSUREVIEW | Approved Development Plan and CSU-approved Construction Drawings must be attached to the permit set. Contact Utilities Development Services at 719-668-8259 with any questions. MLW | mlwilliams | Gas/Elec. Utils | 1468071 |
Elevators | Original | D | 3/9/2021 | ERIC | ERIC | Otis Gen2 Machineroom-less elevator with fire rated suspension means
M0.1 EF-4 to be equipped with an approved motorized damper, controlled via top of hoistway thermostat, interlocked with fire alarm initiating devices located in elevator lobbies and top of hoistway, damper shall close upon activation of said devices.
P0.3 Plumbing equipment schedule. SP-1 Oil guard controls not required for traction type elevators P0.4 Sump pump circuit can not be switched P1.0 Sump pump must discharge indirectly to sanitary sewer
E2.3, E4.0, E6.1 Remove references to shunt trip as it is not allowed in this jurisdiction for this type of occupancy E2.3 Pit light and pit GFCI to be on separate circuits, Top of hoistway light and GFCI to be on separate circuits E2.4 EF-4 motorized damper needs to be interlocked with fire alarm initiating devices in elevator lobbies and top of hoistway, damper to close upon activation of any device. . (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Elevators | 1467777 |
Zoning/Planning | Original | / | 3/9/2021 | WGRAY | WGRAY | In Current Review by WGRAY | | Zoning/Planning | 1467766 |
Construction | Original | D | 3/8/2021 | DANM | DANM | Areas of occupancies listed on Code Study Form page 2 do not total addition area shown on page 1 - clarify Sheet A9.2 missing from submittal Provide Accessibility Plan per RBD requirements Provide allowable area for 1st floor with non-separated mixed occupancies and include that with the sum of the ratios calculations Provide table showing all occupancies and corresponding areas for each floor for existing and new - note accessory occupancies and show < 10% of floor area Specify which system is being used (1-15) for listed assembly UL M502 Beam listings are non-combustible construction - cannot be used for V-A construction Provide listed assembly for columns supporting fire-resistance-rated beams Specify 1-hr listed assembly for what was an exterior wall where addition connects to existing building Specify 2-hr listed assembly for what was an exterior wall where addition connects to existing building (stair enclosure) All four walls of shaft by bathtubs on each floor required to be 2-hr fire-resistance-rated - provide typical section through shaft showing vertical continuity Reference submitted Soils Report on Sheet S1.1 Identify primary structural framing members on all levels that will require individual encasement per IBC 704.2 & 704.3
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1467358 |
Electronic Plan | Original | / | 3/8/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1467200 |
Enumeration | Original | D | 3/2/2021 | AMY | AMY | Approval of plan pending : 1. Enumerations will review the mylar prior to plat for address placement, street names, and title block.
$10.00 per lot & tract platting fee will be due at the time of the review of the mylar, (2 addresses per lot and tract). If an address is not needed on a tract then no fee applies. Check should be made out to PIKES PEAK REGIONAL BUILDING DEPARTMENT or PPRBD. Paid directly to the Enumerations Department.
A copy of the final recorded plat is required prior to approval in the Enumerations department on any COMMERCIAL plan submittal. Amy@pprbd.org
2. Secondary addressing will be reviewed and approved by CSFD.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1464433 |
Electronic Plan | Original | / | 3/2/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1464415 |
Floodplain | Original | N | 2/26/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7336109016) | | Floodplain | 1462717 |