CO Springs Hazmat | Original | A | 5/7/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | DTillery94 | CO Springs Hazmat | 1497294 |
Electrical | Original | A | 4/30/2021 | BERTHA | BERTHA | | | Electrical | 1493985 |
Plumbing | Original | A | 4/28/2021 | SHANEN | SHANEN | | | Plumbing | 1492636 |
Resubmittal 1 | Original | / | 4/26/2021 | SHELLEY | SHELLEY | Resubmittal #1 | | Resubmittal 1 | 1491255 |
CO Springs Hazmat | Original | D | 4/9/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the disapproval comments found on the CSFD website and responding to them in your resubmittal to RBD: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded | DTillery94 | CO Springs Hazmat | 1483055 |
CO Springs Fire | Original | N | 3/29/2021 | CSFIRE | CSFIRE | (see full review) | csfdit | CO Springs Fire | 1477006 |
Electrical | Original | D | 3/26/2021 | BERTHA | BERTHA | 1. All information must be supplied and verified by engineer at time of plan submittal 2. Provide volt amps on all branch circuits and calculated load of panel for all panels affected by the scope of work. 3. Patient care areas must show compliance with 517.13 - 2017 NEC 4. Provide 2015 IECC
Complete re-review. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1475917 |
Electronic Plan | Original | / | 3/26/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1475903 |
CO Springs DRE | Original | N | 3/18/2021 | KDODGE | KDODGE | Interior remodel, commercial, no change of use or occupancy. Vascular equipment swap-out in equipment room. (see full review) | | CO Springs DRE | 1472116 |
CSU Water | Original | A | 3/18/2021 | CSUREVIEW | CSUREVIEW | Backflow okay. MLW | mlwilliams | CSU Water | 1472058 |
CSU Waste Water | Original | N | 3/18/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | CSU Waste Water | 1472057 |
Plumbing | Original | A | 3/18/2021 | SHANEN | SHANEN | | | Plumbing | 1471976 |
Zoning/Planning | Original | / | 3/18/2021 | KDODGE | KDODGE | In Current Review by KDODGE | | Zoning/Planning | 1471961 |
Mechanical | Original | A | 3/18/2021 | JUSTINC | JUSTINC | | | Mechanical | 1471929 |
Electronic Plan | Original | / | 3/18/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1471901 |
Construction | Original | A | 3/18/2021 | MICHAELA | MICHAELA | | | Construction | 1471876 |
Electronic Plan | Original | / | 3/18/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1471816 |
Enumeration | Original | N | 3/11/2021 | BRENT | BRENT | | | Enumeration | 1469529 |
Electronic Plan | Original | / | 3/11/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1469507 |
Floodplain | Original | N | 3/10/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6406108027) | | Floodplain | 1468928 |