Electrical | Original | A | 4/7/2021 | BERTHA | BERTHA | | | Electrical | 1481548 |
Electronic Plan | Original | / | 4/7/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1481461 |
Enumeration | Original | A | 4/6/2021 | BRENT | BRENT | | | Enumeration | 1480941 |
Electronic Plan | Original | / | 4/6/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1480937 |
Resubmittal 3 | Original | / | 4/6/2021 | SAVANNAHT | SAVANNAHT | Resubmittal #3 | | Resubmittal 3 | 1480925 |
Electrical | Original | D | 4/5/2021 | BERTHA | BERTHA | Comply with previous review comments 2 and 3.
Please see red-line mark up.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1480091 |
Electronic Plan | Original | / | 4/5/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1480075 |
Enumeration | Original | A | 4/2/2021 | BRENT | BRENT | | | Enumeration | 1479656 |
Electronic Plan | Original | / | 4/2/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1479655 |
Resubmittal 2 | Original | / | 4/1/2021 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1479172 |
Electrical | Original | D | 3/30/2021 | BERTHA | BERTHA | 1. Provide all loads (panel D) in load summary 2. Comply 250.122 - 2017 NEC 3. Provide compliance with 250.66 - 2017 NEC 4. Provide complete feeder schedule for all conduit/conductor size, type and quantity beginning at the utility transformer to include all conductors in the chain of supply for the electrical equipment in the scope of work
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1477764 |
Electronic Plan | Original | / | 3/30/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1477747 |
Enumeration | Original | A | 3/29/2021 | BRENT | BRENT | | | Enumeration | 1477435 |
Electronic Plan | Original | / | 3/29/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1477429 |
Resubmittal 1 | Original | / | 3/29/2021 | SHELLEY | SHELLEY | Resubmittal #1 | | Resubmittal 1 | 1477019 |
Electrical | Original | D | 3/26/2021 | BERTHA | BERTHA | 1. Provide plans without previous "released for permit" stamps. 2. Remove parallel neutral 3. Provide service load summary. 4. Provide location of all electrical equipment with panel and circuit number
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1476586 |
CO Springs Hazmat | Original | N | 3/24/2021 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1474823 |
CO Springs Fire | Original | N | 3/24/2021 | CSFIRE | CSFIRE | no fire final | csfdit | CO Springs Fire | 1474822 |
CO Springs DRE | Original | N | 3/23/2021 | DFOXX | DFOXX | Electrical service only. No exterior structural changes. (see full review) | | CO Springs DRE | 1474004 |
Zoning/Planning | Original | / | 3/23/2021 | DFOXX | DFOXX | In Current Review by DFOXX | | Zoning/Planning | 1473814 |
CSU Water | Original | N | 3/22/2021 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | CSU Water | 1473538 |
CSU Waste Water | Original | N | 3/22/2021 | CSUREVIEW | CSUREVIEW | AJ | ajuvera | CSU Waste Water | 1473537 |
Plumbing | Original | N | 3/22/2021 | TCRIPPEN | TCRIPPEN | no plumbing work purposed. | | Plumbing | 1473407 |
Mechanical | Original | N | 3/22/2021 | TCRIPPEN | TCRIPPEN | No mechanical work purposed, | | Mechanical | 1473405 |
Construction | Original | N | 3/22/2021 | SHELLEY | SHELLEY | No construction work | | Construction | 1473348 |
Enumeration | Original | A | 3/22/2021 | BRENT | BRENT | | | Enumeration | 1473166 |
Electronic Plan | Original | / | 3/22/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1473151 |
Floodplain | Original | N | 3/16/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6310111028) | | Floodplain | 1471175 |