Electrical | Splice 09/14/21 | A | 9/21/2021 | SHELBY | SHELBY | | | Electrical | 1565612 |
Resubmittal 2 | Splice 09/14/21 | / | 9/21/2021 | ANDREAL | ANDREAL | Resubmittal #2 | | Resubmittal 2 | 1565538 |
Electrical | Splice 09/14/21 | D | 9/15/2021 | BERTHA | BERTHA | Comply with 250.122 NEC - New Panel A feeder.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1562283 |
Electronic Plan | Splice 09/14/21 | / | 9/15/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1562275 |
Resubmittal 1 | Splice 09/14/21 | / | 9/15/2021 | SAVANNAHT | SAVANNAHT | Resubmittal #1 | | Resubmittal 1 | 1562142 |
Electrical | Splice 09/14/21 | D | 9/14/2021 | BERTHA | BERTHA | Remove all old clouds. Provide sheets with clouds pertaining to the current splice only.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1562015 |
Electronic Plan | Splice 09/14/21 | / | 9/14/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1561950 |
Electrical | Splice 07/19/21 | A | 7/22/2021 | BERTHA | BERTHA | Revised power. | | Electrical | 1534443 |
Electronic Plan | Splice 07/19/21 | / | 7/22/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1534275 |
Plumbing | Splice 06/30/21 | A | 6/30/2021 | SHANEN | SHANEN | Delta 3 revisions: Adjusted sheet P-1 and P-2. | | Plumbing | 1524059 |
Electronic Plan | Splice 06/30/21 | / | 6/30/2021 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1524049 |
Plumbing | Splice 06/28/21 | A | 6/29/2021 | SHANEN | SHANEN | Delta 2 revisions: Adjusted sheet P-2. | | Plumbing | 1523425 |
Resubmittal 1 | Splice 06/28/21 | / | 6/29/2021 | NICKH | NICKH | Resubmittal #1 | | Resubmittal 1 | 1523407 |
Plumbing | Splice 06/28/21 | D | 6/28/2021 | SHANEN | SHANEN | P-1: Provide only sheets with clouded revisions. P-2: Remove all previous clouds and cloud only the revisions that apply to this splice request per PPRBD plan review policies. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1523178 |
Electrical | Original | A | 6/7/2021 | BERTHA | BERTHA | | | Electrical | 1512161 |
Electronic Plan | Original | / | 6/7/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1512156 |
Resubmittal 2 | Original | / | 6/2/2021 | SAVANNAHT | SAVANNAHT | Resubmittal #2 | | Resubmittal 2 | 1510373 |
Electrical | Original | D | 5/26/2021 | BERTHA | BERTHA | Comply with previous review comment #1 - Service conductor is overloaded.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1507032 |
Electronic Plan | Original | / | 5/26/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1507013 |
Plumbing | Original | A | 5/24/2021 | SHANEN | SHANEN | | | Plumbing | 1505448 |
Construction | Original | A | 5/24/2021 | MICHAELA | MICHAELA | | | Construction | 1505287 |
Resubmittal 1 | Original | / | 5/21/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1504479 |
CO Springs Hazmat | Original | N | 5/17/2021 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1501988 |
CO Springs Fire | Original | N | 5/17/2021 | CSFIRE | CSFIRE | no fire final | csfdit | CO Springs Fire | 1501987 |
Electrical | Original | D | 5/3/2021 | BERTHA | BERTHA | 1. Service conductor is overloaded. 2. Provide SCA for New Panel A.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1494348 |
Electronic Plan | Original | / | 5/3/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1494344 |
CO Springs DRE | Original | A | 4/30/2021 | ACOOPER | ACOOPER | Interior finish. Yoga studio is allowed by right in the C6 zone (see full review) | | CO Springs DRE | 1494136 |
CSU Water | Original | A | 4/29/2021 | CSUREVIEW | CSUREVIEW | Backflow okay. MLW | mlwilliams | CSU Water | 1493638 |
CSU Waste Water | Original | N | 4/29/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. MLW | mlwilliams | CSU Waste Water | 1493637 |
Plumbing | Original | D | 4/29/2021 | SHANEN | SHANEN | See construction reviewer comments regarding transfer shower as backgrounds and fixture schedule may change.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1493569 |
Zoning/Planning | Original | / | 4/29/2021 | ACOOPER | ACOOPER | In Current Review by ACOOPER | | Zoning/Planning | 1493567 |
Mechanical | Original | A | 4/29/2021 | JUSTINC | JUSTINC | | | Mechanical | 1493462 |
Electronic Plan | Original | / | 4/29/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1493449 |
Construction | Original | D | 4/29/2021 | MICHAELA | MICHAELA | Show exterior wall correctly. Show north arrow correctly. Revise to currently adopted codes.There is no record of any fire separation in this space. Revise transfer shower to required dimensions. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1493433 |
Electronic Plan | Original | / | 4/26/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1490963 |
Enumeration | Original | N | 4/23/2021 | BRENT | BRENT | | | Enumeration | 1490325 |
Electronic Plan | Original | / | 4/23/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1490317 |
Floodplain | Original | N | 4/22/2021 | KEITH | KEITH | | | Floodplain | 1489517 |
Floodplain | Original | / | 4/21/2021 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 7413314009) | | Floodplain | 1489139 |