Construction | Original | N | 4/12/2022 | DANM | DANM | Upon further review, proposed WIC Shelter on Sheet C-6 meets exemption for a building permit - no separate submittal and permit required | | Construction | 1664311 |
Electrical | Original | A | 4/11/2022 | SHELBY | SHELBY | | | Electrical | 1663047 |
Electronic Plan | Original | / | 4/11/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1663040 |
Construction | Original | N | 3/31/2022 | DANM | DANM | Separate submittal and permit required for commercial accessory structures that exceed 120 sf in area - sheet C-6 crossed off since WIC shelter appears to be greater than 120 sf | | Construction | 1658804 |
Electronic Plan | Original | / | 3/31/2022 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1658761 |
Resubmittal 4 | Original | / | 3/30/2022 | BPHILLIPS | BPHILLIPS | Resubmittal #4 | | Resubmittal 4 | 1657881 |
Tri-Lakes Fire (CSFD) | Original | N | 1/13/2022 | CSFIRE | CSFIRE | (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1621093 |
Tri-Lakes Fire (CSFD) | Original | N | 1/13/2022 | CSFIRE | CSFIRE | (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1621090 |
Electrical | Original | D | 12/29/2021 | SHELBY | SHELBY | 1. Please address previous review comments. Show the manner in which installation will comply with 445.18 NEC (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1614532 |
Construction | Original | D | 12/28/2021 | DANM | DANM | Does not appear that last disapproval comment was addressed:
See plan C153712 for tower modification. This plan cannot be approved until the tower modification is approved and permitted.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1613630 |
Electronic Plan | Original | / | 12/28/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1613628 |
Resubmittal 3 | Original | / | 12/28/2021 | AUSTINK | AUSTINK | Resubmittal #3 | | Resubmittal 3 | 1613438 |
Tri-Lakes Hazmat (CSFD) | Original | A | 12/17/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | DTillery94 | Tri-Lakes Hazmat (CSFD) | 1610190 |
Tri-Lakes Fire (CSFD) | Original | D | 11/30/2021 | CSFIRE | CSFIRE | Previous comments not addressed | dwithee | Tri-Lakes Fire (CSFD) | 1600420 |
Tri-Lakes Fire (CSFD) | Original | D | 11/30/2021 | CSFIRE | CSFIRE | Submitted By: Trimble, James Charles | csfdit | Tri-Lakes Fire (CSFD) | 1600417 |
Tri-Lakes Fire (CSFD) | Original | D | 11/30/2021 | CSFIRE | CSFIRE | Previous comments not addressed | jt09ff | Tri-Lakes Fire (CSFD) | 1600415 |
Tri-Lakes Hazmat (CSFD) | Original | D | 11/30/2021 | CSFIRE | CSFIRE | PENDING RECEIPT OF COMPLETED DOCUMENTS REQUIRED BY FIRE CONSTRUCTION REVIEW | jt09ff | Tri-Lakes Hazmat (CSFD) | 1600412 |
Electrical | Original | D | 11/11/2021 | SHELBY | SHELBY | Please address previous review comments( 445.18 (B)&(C) NEC. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1592847 |
Electronic Plan | Original | / | 11/11/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1592846 |
Construction | Original | D | 11/10/2021 | SHELLEY | SHELLEY | See plan C153712 for tower modification. This plan cannot be approved until the tower modification is approved and permitted. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1591921 |
Resubmittal 2 | Original | / | 11/10/2021 | ANDREAL | ANDREAL | Resubmittal #2 | | Resubmittal 2 | 1591818 |
Tri-Lakes Hazmat (CSFD) | Original | D | 10/14/2021 | CSFIRE | CSFIRE | PENDING RECEIPT OF COMPLETED DOCUMENTS REQUIRED BY FIRE CONSTRUCTION REVIEW | dwithee | Tri-Lakes Hazmat (CSFD) | 1579018 |
Tri-Lakes Fire (CSFD) | Original | D | 10/14/2021 | CSFIRE | CSFIRE | PREVIOUS COMMENTS NOT ADDRESSED | dwithee | Tri-Lakes Fire (CSFD) | 1579016 |
Electrical | Original | D | 9/21/2021 | SHELBY | SHELBY | Add components for 445.18 NEC compliance. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1565911 |
Electronic Plan | Original | / | 9/21/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1565894 |
Construction | Original | D | 9/21/2021 | SHELLEY | SHELLEY | Provide structural plans for tower extension (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1565693 |
Resubmittal 1 | Original | / | 9/21/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1565617 |
Tri-Lakes Hazmat (CSFD) | Original | D | 6/8/2021 | CSFIRE | CSFIRE | | dwithee | Tri-Lakes Hazmat (CSFD) | 1513224 |
Tri-Lakes Fire (CSFD) | Original | D | 6/8/2021 | CSFIRE | CSFIRE | (DISAPPROVED) HAZARDOUS MATERIALS: Provide completed Hazardous Materials Operations Triage form for all Use/Dispensing/Storage of Hazardous Materials and Flammable Liquids that will be used within this facility. Provide an inventory list, including their uses and amounts, for all chemicals and/or compressed gases, you indicated Yes to on the HazMat Triage Form. List of chemicals to be categorized according to 2009 IFC Table 105.6.20. PLEASE INSURE YOU ANSWER ALL QUESTIONS AT THE BOTTOM OF THE FORMS, AND FILL OUT THE REQUESTED INFORMATION. All forms and packets are available at https://coloradosprings.gov/hazmat?mlid=42381 | dwithee | Tri-Lakes Fire (CSFD) | 1513223 |
Electrical | Original | D | 5/26/2021 | SHELBY | SHELBY | 1. Please submit a complete one line. See htte/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs.pdfps://www.pprbd.org/Fil 2. Provide fault current information ( See link). 3. Specify 2 or 3 pole ATS. 4. Show generator over current device ampacity on one line. 5. Show location of all electrical equipment on Electrical site plan. | | Electrical | 1506643 |
Electronic Plan | Original | / | 5/24/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1505562 |
Mechanical | Original | N | 5/21/2021 | JUSTINC | JUSTINC | No new or revised mechanical scope indicated | | Mechanical | 1504375 |
County Zoning | Original | N | 5/19/2021 | DSDRANGEL | DSDRANGEL | | | County Zoning | 1503345 |
County Water | Original | N | 5/19/2021 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities water service territory. MLW | mlwilliams | County Water | 1503236 |
County Waste Water | Original | N | 5/19/2021 | CSUREVIEW | CSUREVIEW | Not in Colorado Springs Utilities wastewater service territory. MLW | mlwilliams | County Waste Water | 1503234 |
Zoning/Planning | Original | / | 5/19/2021 | DSDRANGEL | DSDRANGEL | In Current Review by DSDRANGEL | | Zoning/Planning | 1503158 |
Construction | Original | D | 5/19/2021 | SHELLEY | SHELLEY | Provide structural plans for tower extension (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1503079 |
Enumeration | Original | N | 5/18/2021 | BECKYA | BECKYA | | | Enumeration | 1502298 |
Electronic Plan | Original | / | 5/17/2021 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1501791 |
Floodplain | Original | N | 5/14/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6100000508) | | Floodplain | 1501273 |