Construction | Splice 03/23/23 | A | 3/23/2023 | DANM | DANM | Minor structural scope of work removed | | Construction | 1819771 |
Electronic Plan | Splice 03/23/23 | / | 3/23/2023 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1819766 |
Mechanical | Splice 12/06/21 | A | 12/6/2021 | TCRIPPEN | TCRIPPEN | New splice field changes. | | Mechanical | 1603595 |
Electrical | Splice 09/29/21 | A | 10/18/2021 | SHELBY | SHELBY | | | Electrical | 1580688 |
Resubmittal 1 | Splice 09/29/21 | / | 10/18/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1580445 |
Electrical | Splice 09/29/21 | D | 10/1/2021 | SHELBY | SHELBY | 1. Provide accurate fault current values on one line. Let through current is irrelevant when breakers are introducing dynamic impedance to the circuit. Series rate or fully rate the installation. Fault current values ( SCA) are required for fully or series rated systems. If series rating include manufacturers list of series rated components. 2. Include SCCR and SCA on fault schedule for existing RTU's being re fed by the new service.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1572413 |
Electronic Plan | Splice 09/29/21 | / | 10/1/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1572097 |
Scanned/Finished Bin | Splice 09/22/21 | / | 9/22/2021 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1566756 |
Mechanical | Splice 09/22/21 | A | 9/22/2021 | TCRIPPEN | TCRIPPEN | new splice relocate gas line | | Mechanical | 1566588 |
Out to Review | Splice 09/22/21 | / | 9/22/2021 | VERONIKAP | VERONIKAP | Jesse 719-532-9725 | | Out to Review | 1566587 |
Mechanical | Original | A | 7/8/2021 | JUSTINC | JUSTINC | | | Mechanical | 1527659 |
Electronic Plan | Original | / | 7/8/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1527575 |
Resubmittal 2 | Original | / | 7/8/2021 | SHELLEY | SHELLEY | Resubmittal #2 | | Resubmittal 2 | 1527548 |
CO Springs High Pile | Original | A | 7/6/2021 | CSFIRE | CSFIRE | You are responsible for reviewing the comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | DTillery94 | CO Springs High Pile | 1526338 |
CO Springs Hazmat | Original | N | 6/28/2021 | CSFIRE | CSFIRE | | wtaylor | CO Springs Hazmat | 1523045 |
CO Springs Fire | Original | A | 6/28/2021 | CSFIRE | CSFIRE | Submitted By: Taylor II, Wyman L
See CSFD Plan Review Comments at: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp (see full review) | csfdit | CO Springs Fire | 1523034 |
Plumbing | Original | A | 6/17/2021 | SHANEN | SHANEN | | | Plumbing | 1518152 |
Electrical | Original | A | 6/17/2021 | SHELBY | SHELBY | | | Electrical | 1518130 |
Electronic Plan | Original | / | 6/17/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1518128 |
Mechanical | Original | D | 6/17/2021 | JUSTINC | JUSTINC | Clarify locations of alarms and type of alarms Clarify evaporator locations with condensate routing How providing combustion air to water heater
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1518039 |
Plumbing | Original | / | 6/16/2021 | WEBSITE | WEBSITE | Overtime Authorized for Plumbing by neil parker | 15255tnp | Plumbing | 1517794 |
Mechanical | Original | / | 6/16/2021 | WEBSITE | WEBSITE | Overtime Authorized for Mechanical by neil parker | 15255tnp | Mechanical | 1517793 |
Electrical | Original | / | 6/16/2021 | WEBSITE | WEBSITE | Overtime Authorized for Electrical by neil parker | 15255tnp | Electrical | 1517792 |
Construction | Original | A | 6/16/2021 | DANM | DANM | | | Construction | 1517775 |
Electronic Plan | Original | / | 6/16/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1517774 |
Plumbing | Original | / | 6/16/2021 | JAY | JAY | Overtime approved for Plumbing by Neil Parker | | Plumbing | 1517625 |
Mechanical | Original | / | 6/16/2021 | JAY | JAY | Overtime approved for Mechanical by Neil Parker | | Mechanical | 1517624 |
Electrical | Original | / | 6/16/2021 | JAY | JAY | Overtime approved for Electrical by Neil Parker | | Electrical | 1517623 |
Construction | Original | / | 6/16/2021 | JAY | JAY | Overtime approved for Construction by Neil Parker | | Construction | 1517622 |
Resubmittal 1 | Original | / | 6/16/2021 | JAY | JAY | Resubmittal #1 | | Resubmittal 1 | 1517620 |
CO Springs Hazmat | Original | D | 6/4/2021 | CSFIRE | CSFIRE | Disapproved by Fire to allow contractor to resubmit revised plans. CLT 6/4/21 | wtaylor | CO Springs Hazmat | 1511091 |
CO Springs Fire | Original | D | 6/4/2021 | CSFIRE | CSFIRE | Disapproved by Fire to allow contractor to resubmit revised plans. CLT 6/4/21 | wtaylor | CO Springs Fire | 1511090 |
Plumbing | Original | D | 5/27/2021 | SHANEN | SHANEN | Construction reviewer comments must first be addressed. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1507864 |
Electrical | Original | D | 5/27/2021 | BERTHA | BERTHA | Pending Construction approval
Provide 2015 IECC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1507376 |
Electronic Plan | Original | / | 5/27/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1507319 |
Mechanical | Original | D | 5/26/2021 | JUSTINC | JUSTINC | Update ventilation schedule for all new spaces Correct code year and reference
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1507173 |
Electronic Plan | Original | / | 5/26/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1507158 |
CSU Water | Original | N | 5/25/2021 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 1506342 |
CSU Waste Water | Original | N | 5/25/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 1506341 |
CO Springs DRE | Original | N | 5/25/2021 | PDOSCH | PDOSCH | Interior remodel only: No change in footprint, No change to exterior, No change in parking, No change in occupancy (see full review) | | CO Springs DRE | 1506331 |
Zoning/Planning | Original | / | 5/25/2021 | PDOSCH | PDOSCH | In Current Review by PDOSCH | | Zoning/Planning | 1506330 |
Construction | Original | D | 5/25/2021 | DANM | DANM | Clarify type of products being stored - typically warehouse storage is going to be S-1 occupancy Update fire resistive requirements chart for Construction Type III-B
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1506325 |
Electronic Plan | Original | / | 5/25/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1505818 |
Enumeration | Original | N | 5/18/2021 | BRENT | BRENT | | | Enumeration | 1502686 |
Electronic Plan | Original | / | 5/18/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1502671 |
Floodplain | Original | N | 5/17/2021 | KEITH | KEITH | | | Floodplain | 1501657 |
Floodplain | Original | / | 5/17/2021 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6326307035) | | Floodplain | 1501545 |