Electrical | Original | A | 6/23/2021 | SHELBY | SHELBY | | | Electrical | 1520973 |
Resubmittal 2 | Original | / | 6/21/2021 | ANDREAL | ANDREAL | Resubmittal #2 | | Resubmittal 2 | 1519708 |
Electrical | Original | D | 6/16/2021 | SHELBY | SHELBY | Previous review comments have not been addressed. ( Generator is overloaded, EPO for prime mover is not shown). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1517781 |
Resubmittal 1 | Original | / | 6/15/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1516708 |
CO Springs Hazmat | Original | A | 6/8/2021 | CSFIRE | CSFIRE | DEFERRED SUBMITTAL
The fuel tanks for the generator shall be a deferred submittal. Plans shall be marked approved on RBD plans to allow for building permit issuance; however, plans shall remain disapproved on CSFD plan review until plans are approved and permitted. Fuel tanks must be approved and permitted prior to installation. Hazmat and fire final inspections shall not be scheduled until system is approved and permitted.
Please have the installing contractor submit the following documents directly to CSFD for permitting.
1. A completed permit application 2. Site plan (Be sure to indicate the location of fill and vent lines.) 3. Cut sheets for both generator and fuel tank.
Plans can be submitted electronically via ePlan https://web1.coloradosprings.gov/ePlan
DCT (see full review) | DTillery94 | CO Springs Hazmat | 1513518 |
Electrical | Original | D | 6/7/2021 | SHELBY | SHELBY | 1. Show compliance with 445.18 NEC. 2. Provide load calculation for main panel ( Comply 702.4(B)(2) NEC). (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1512741 |
Electronic Plan | Original | / | 6/7/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1512732 |
CO Springs DRE | Original | N | 6/3/2021 | DFOXX | DFOXX | Generator replacement. Changes to the building are electrical only and do not trigger application to City Planning. (see full review) | | CO Springs DRE | 1510815 |
CO Springs Fire | Original | N | 6/3/2021 | CSFIRE | CSFIRE | plans checked in for hazmat review | csfdit | CO Springs Fire | 1510609 |
Mechanical | Original | N | 6/2/2021 | DALEH | DALEH | | | Mechanical | 1509833 |
Zoning/Planning | Original | / | 6/1/2021 | DFOXX | DFOXX | In Current Review by DFOXX | | Zoning/Planning | 1509601 |
Plumbing | Original | N | 6/1/2021 | SHANEN | SHANEN | No plumbing scope of work. | | Plumbing | 1509543 |
CSU Waste Water | Original | N | 6/1/2021 | CSUREVIEW | CSUREVIEW | No plumbing work. mjg | mgackle | CSU Waste Water | 1509500 |
CSU Water | Original | N | 6/1/2021 | CSUREVIEW | CSUREVIEW | No plumbing work. mjg | mgackle | CSU Water | 1509499 |
Construction | Original | N | 6/1/2021 | SHELLEY | SHELLEY | No construction work. | | Construction | 1509479 |
Enumeration | Original | A | 5/28/2021 | BRENT | BRENT | Tax schedule number and legal description added to code study form by Enumerations. | | Enumeration | 1508595 |
Electronic Plan | Original | / | 5/28/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1508588 |
Floodplain | Original | N | 5/27/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6234305001) | | Floodplain | 1508038 |