Triview Water | Original | A | 5/7/2024 | TRIVIEWMETRO | TRIVIEWMETRO | | rnortonTMD | Triview Water | 1999669 |
Water Division | Original | / | 5/6/2024 | SYSTEM | SYSTEM | Contact Water Division department for approval prior to permit | | Water Division | 1998832 |
Plumbing | Original | A | 5/6/2024 | SHANEN | SHANEN | | | Plumbing | 1998713 |
Electronic Plan | Original | / | 5/6/2024 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1998710 |
Resubmittal 6 | Original | / | 5/3/2024 | QUINTONW | QUINTONW | Resubmittal #6 | | Resubmittal 6 | 1998661 |
Monument Zoning | Original | A | 5/2/2024 | TOWNOFMON | TOWNOFMON | Plan conditionally approved by Town of Monument. Permit Fees are due within 10 days of permit authorization. Note that no final Monument Inspection for C/O can be completed unless all permit fees are paid, Development items/requests are completed and inspection requirements are met which could include the Monument Water Department. Any change to the approved plot plan or variations in the model as depicted on the plot plan requires a plot plan modification and re-review. For more information you may email the Planning Department at planning@tomgov.org. Thank you | Rey Medina | Monument Zoning | 1998172 |
Triview Water | Original | D | 3/11/2024 | TRIVIEWMETRO | TRIVIEWMETRO | 1. Sheet P003 – Modify the Domestic Water Entry Diagram to include a 2” water meter before the tee splitting between domestic and irrigation to allow Triview Metropolitan District to meter all water entering the facility. The meter will require a bypass line as shown in the District’s Engineering Standards on Sheet 60 to allow for meter maintenance. A floor drain within 10-feet of the meter is also required.
2. Add a Cover Sheet to the Civil Drawings for Triview Metropolitan District to sign off on public improvements. The format that was used for the surrounding infrastructure improvements for Monument Industrial Park is acceptable. | rnortonTMD | Triview Water | 1973668 |
Triview Waste Water | Original | A | 3/11/2024 | TRIVIEWMETRO | TRIVIEWMETRO | | rnortonTMD | Triview Waste Water | 1973665 |
Resubmittal 5 | Original | / | 2/21/2024 | BRIANNAM | BRIANNAM | Resubmittal #5 | | Resubmittal 5 | 1965540 |
Canceled Plans | Original | / | 12/4/2022 | ADMIN | ADMIN | Electronic Plan automatically cancelled due to inactivity. | | Canceled Plans | 1777676 |
Monument Zoning | Original | D | 12/3/2021 | TOWNOFMON | TOWNOFMON | DELIQUENT PAYMENT- *Missing Monument permit payment please contact Theresa Rust at 719-884-8015, https://monument.cascadesoftware.net/Account/SignIn | trust@tomgov.org | Monument Zoning | 1602194 |
Monument Zoning | Original | D | 12/3/2021 | TOWNOFMON | TOWNOFMON | DELIQUENT PAYMENT- *Missing Monument permit payment please contact Theresa Rust at 719-884-8015, https://monument.cascadesoftware.net/Account/SignIn | trust@tomgov.org | Monument Zoning | 1602193 |
Resubmittal 4 | Original | / | 12/2/2021 | ANDREAL | ANDREAL | Resubmittal #4 | | Resubmittal 4 | 1602163 |
Triview Water | Original | D | 10/5/2021 | TRIVIEWMETRO | TRIVIEWMETRO | Please refer to the original JDS provided memorandum dated 7/19/21 for all unaddressed comments. | nharrisTMD | Triview Water | 1573778 |
Triview Waste Water | Original | D | 10/5/2021 | TRIVIEWMETRO | TRIVIEWMETRO | Please refer to the original JDS provided memorandum dated 7/19/21 for all unaddressed comments. | nharrisTMD | Triview Waste Water | 1573774 |
Monument Zoning | Original | D | 10/5/2021 | TOWNOFMON | TOWNOFMON | DECLINED-Cannot review or approve without Construction Documents that are approved and signed and until we receive and record the Improvement Agreement which comes with a bond or letter of credit. | trust@tomgov.org | Monument Zoning | 1573692 |
Monument Zoning | Original | / | 10/5/2021 | TOWNOFMON | TOWNOFMON | | trust@tomgov.org | Monument Zoning | 1573689 |
Waste Water Div | Original | / | 10/4/2021 | SYSTEM | SYSTEM | Contact Waste Water Div department for approval prior to permit | | Waste Water Div | 1573392 |
Water Division | Original | / | 10/4/2021 | SYSTEM | SYSTEM | Contact Water Division department for approval prior to permit | | Water Division | 1573391 |
Tri-Lakes Fire (CSFD) | Original | A | 10/4/2021 | CSFIRE | CSFIRE | Submitted By: Valdez, Philip Warren (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1573301 |
Tri-Lakes Fire (CSFD) | Original | A | 10/4/2021 | CSFIRE | CSFIRE | Submitted By: Valdez, Philip Warren (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1573299 |
Electrical | Original | A | 10/1/2021 | SHELBY | SHELBY | | | Electrical | 1572053 |
Electronic Plan | Original | / | 10/1/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1572048 |
Resubmittal 3 | Original | / | 9/28/2021 | SAVANNAHT | SAVANNAHT | Resubmittal #3 | | Resubmittal 3 | 1570193 |
Tri-Lakes Fire (CSFD) | Original | D | 9/20/2021 | CSFIRE | CSFIRE | Walk OK Previous comments not addressed:
*****(DISAPROVED) DELEGATED PROJECTS:
Provide documentation of site plan and water supply approvals by ---TRI-LAKES MONUMENT-- Fire Protection District.
1 - APPROVAL OF SITE ACCESS FROM ---TRI-LAKES MONUMENT-- FIRE
2 - APPROVAL OF HYDRANT LOCATION FROM --TRI-LAKES MONUMENT--- FIRE - A MINIMUM OF 4 FIRE HYDRANTS ARE REQUIRED FOR THIS BUILDING
3 - APPLICANT MUST PROVIDE DOCUMENTATION HYDRANT WILL PROVIDE MINIMUM FIRE FLOW OF ----4,000-GPM FOR THIS FACILITY. (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1564527 |
Electrical | Original | D | 9/16/2021 | SHELBY | SHELBY | Previous review comments have not been addressed. Code sections in response letter are for circuits supplying a fire pump. Previous review comments are driven by over current protection size for the service lateral. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1563108 |
Electronic Plan | Original | / | 9/16/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1563075 |
Plumbing | Original | A | 9/14/2021 | SHANEN | SHANEN | | | Plumbing | 1561899 |
Construction | Original | A | 9/14/2021 | MICHAELA | MICHAELA | | | Construction | 1561697 |
Enumeration | Original | A | 9/13/2021 | BRENT | BRENT | | | Enumeration | 1560864 |
Electronic Plan | Original | / | 9/13/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1560859 |
Resubmittal 2 | Original | / | 9/13/2021 | JAY | JAY | Resubmittal #2 | | Resubmittal 2 | 1560828 |
Tri-Lakes Fire (CSFD) | Original | D | 8/12/2021 | CSFIRE | CSFIRE | PREVIOUS COMMENTS NOT ADDRESSED:
You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1546346 |
Plumbing | Original | D | 8/3/2021 | SHANEN | SHANEN | No plumbing plans were provided with this plan re-submittal. Sheet A140 scupper opening dimensions and locations not provided. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1540876 |
Electrical | Original | D | 7/28/2021 | SHELBY | SHELBY | 1. Fire pump service lateral is undersized. 2. A 600 amp service requires a C/T enclosure. Consultation is available shelby@pprbd.org 719 203 8943 | | Electrical | 1538095 |
Electronic Plan | Original | / | 7/28/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1538078 |
Mechanical | Original | A | 7/28/2021 | DALEH | DALEH | | | Mechanical | 1537672 |
Construction | Original | A | 7/28/2021 | MICHAELA | MICHAELA | | | Construction | 1537616 |
Enumeration | Original | A | 7/27/2021 | BRENT | BRENT | Legal description added to code study form by Enumerations. | | Enumeration | 1537182 |
Electronic Plan | Original | / | 7/27/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1537153 |
Resubmittal 1 | Original | / | 7/26/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1536470 |
Monument Zoning | Original | N | 7/15/2021 | TOWNOFMON | TOWNOFMON | Pikes Peak Regional Building inspection is needed. The Town of Monument zoning approval is based on the submission to Monument provided within our Cascade permitting system. If that submission differs or is changed within Pikes Peak Regional Building, we cannot be held liable for the zoning decision. | trust@tomgov.org | Monument Zoning | 1531231 |
Monument Zoning | Original | / | 7/15/2021 | TOWNOFMON | TOWNOFMON | | trust@tomgov.org | Monument Zoning | 1531229 |
Tri-Lakes Hazmat (CSFD) | Original | N | 7/7/2021 | CSFIRE | CSFIRE | no hazmat at shell - will be addressed at finish | dwithee | Tri-Lakes Hazmat (CSFD) | 1526857 |
Tri-Lakes Fire (CSFD) | Original | D | 7/7/2021 | CSFIRE | CSFIRE | WALK OK – See our “Virtual” Walk Through process here: https://coloradosprings.gov/sites/default/files/inline-images/walk-thru_memo.pdf You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | Tri-Lakes Fire (CSFD) | 1526856 |
Monument Zoning | Original | D | 7/7/2021 | TOWNOFMON | TOWNOFMON | Town permit application is incomplete- *Missing permit-See Town of Monument website for permit process using CASCADE SOFTWARE online. https://www.townofmonument.org/433/Permits | trust@tomgov.org | Monument Zoning | 1526729 |
Electrical | Original | D | 6/16/2021 | SHELBY | SHELBY | 1. Show fire pump horse power on one line ( Controller HP shown). 2. Show fire pump controller Main circuit breaker size on one line. 3. Show fire pump controller location on floor plan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1517498 |
Electronic Plan | Original | / | 6/14/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1516341 |
Plumbing | Original | D | 6/14/2021 | SHANEN | SHANEN | Show locations of overflow scuppers. Provide overflow scupper opening dimensions. All required overflow scupper information is not provided on the architectural plans. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plumbing | 1516216 |
Mechanical | Original | A | 6/14/2021 | DALEH | DALEH | | | Mechanical | 1516187 |
Construction | Original | A | 6/14/2021 | MICHAELA | MICHAELA | | | Construction | 1515985 |
Electronic Plan | Original | / | 6/11/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1515215 |
Enumeration | Original | D | 6/7/2021 | BRENT | BRENT | Show the secondary addressing for the maximum number of tenants the building could hold on page G100 which follows the RBD secondary addressing guidelines available on our website. The legal description is missing from the code study form. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1512705 |
Electronic Plan | Original | / | 6/7/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1512665 |
Waste Water Div | Original | / | 6/7/2021 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 1512111 |
Water Division | Original | / | 6/7/2021 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 1512110 |
Floodplain | Original | N | 6/7/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7126002014) | | Floodplain | 1512109 |