Electrical | Original | A | 10/11/2021 | SHELBY | SHELBY | | | Electrical | 1576816 |
Electronic Plan | Original | / | 10/11/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1576813 |
Resubmittal 3 | Original | / | 10/9/2021 | ANDREAL | ANDREAL | Resubmittal #3 | | Resubmittal 3 | 1576426 |
Electrical | Original | D | 10/1/2021 | SHELBY | SHELBY | Please address previous review comment 2. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1572430 |
Electronic Plan | Original | / | 10/1/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1572418 |
Resubmittal 2 | Original | / | 9/27/2021 | ANDREAL | ANDREAL | Resubmittal #2 | | Resubmittal 2 | 1569351 |
Electrical | Original | D | 9/16/2021 | SHELBY | SHELBY | 1. Lable components as new or existing ( PP3 etc.). 2. Provide listing for modular office assembly ( NRTL). 3. Show panel CE on overall floor plan. 4. Show panel CE on one line including conductors and raceway. 5. Show SCA, SCCR and AIC for all re fed and new electrical gear and equipment. See https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs%202020%20NEC.pdf (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1563499 |
Electronic Plan | Original | / | 9/16/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1563480 |
Mechanical | Original | A | 9/14/2021 | JUSTINC | JUSTINC | Inspector to verify Ptac and OSA connection meets manufacture installation requirements. | | Mechanical | 1561961 |
Electronic Plan | Original | / | 9/14/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1561921 |
Construction | Original | A | 9/14/2021 | DANM | DANM | | | Construction | 1561919 |
Electronic Plan | Original | / | 9/14/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1561883 |
Resubmittal 1 | Original | / | 9/14/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1561630 |
CO Springs Hazmat | Original | N | 9/3/2021 | CSFIRE | CSFIRE | | jt09ff | CO Springs Hazmat | 1558228 |
CO Springs Fire | Original | A | 9/3/2021 | CSFIRE | CSFIRE | Submitted By: Trimble, James Charles ,Submitted By: Trimble, James Charles (see full review) | csfdit | CO Springs Fire | 1558227 |
Health Dept. | Original | N | 8/23/2021 | HEALTHDEPT | HEALTHDEPT | Not applicable. AB | abrannon | Health Dept. | 1551139 |
City Engr | Original | N | 8/18/2021 | PMORRIS | PMORRIS | | | City Engr | 1548775 |
Electrical | Original | D | 8/13/2021 | SHELBY | SHELBY | Clearly indicate new VS existing on floor plan, panel schedules,and one line. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1546535 |
Electronic Plan | Original | / | 8/13/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1546532 |
Plumbing | Original | N | 8/12/2021 | SHANEN | SHANEN | No plumbing scope of work indicated. All required plumbing fixtures are existing to remain. | | Plumbing | 1546443 |
Mechanical | Original | D | 8/12/2021 | JUSTINC | JUSTINC | How providing ventilation to new office? Provide stamped (M) sheets with ventilation schedule per 2015 IMC 403.3.1.1 There are no previsions which allow using warehouse ventilation for ventilating the office
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1546424 |
Electronic Plan | Original | / | 8/12/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1546394 |
Elevators | Original | N | 8/12/2021 | ROBERTV | ROBERTV | No Conveyances | | Elevators | 1546355 |
CSU Contract Admin. | Original | N | 8/12/2021 | CSUAPPSPRM | CSUAPPSPRM | CWMSF approved and applicable Development fees/charges paid - master meter configuration. AG | aguerin | CSU Contract Admin. | 1546116 |
CO Springs DRE | Original | N | 8/12/2021 | PDOSCH | PDOSCH | Interior remodel only: No change in footprint, No change to exterior, No change in parking, No change in occupancy (see full review) | | CO Springs DRE | 1545899 |
Zoning/Planning | Original | / | 8/12/2021 | PDOSCH | PDOSCH | In Current Review by PDOSCH | | Zoning/Planning | 1545898 |
Gas/Elec. Utils | Original | N | 8/12/2021 | CSUREVIEW | CSUREVIEW | No apparent conflicts. DMM | dmakings | Gas/Elec. Utils | 1545852 |
CSU Waste Water | Original | N | 8/12/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. DMM | dmakings | CSU Waste Water | 1545851 |
CSU Water | Original | A | 8/12/2021 | CSUREVIEW | CSUREVIEW | Backflow okay. DMM | dmakings | CSU Water | 1545849 |
Construction | Original | D | 8/12/2021 | DANM | DANM | Portafab drawings/calculations should reference the 2015 IBC (not the 2018).
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1545833 |
Electronic Plan | Original | / | 8/12/2021 | DANM | DANM | In Current Review by DANM | | Electronic Plan | 1545818 |
Enumeration | Original | N | 8/11/2021 | BRENT | BRENT | | | Enumeration | 1545500 |
Electronic Plan | Original | / | 8/11/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1545457 |
Floodplain | Original | N | 6/23/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6424006003) | | Floodplain | 1521028 |