Monument Waste Water | Original | N | 11/5/2021 | JAY | JAY | N/A per email in Images. | | Monument Waste Water | 1589907 |
Waste Water Div | Original | / | 10/21/2021 | SYSTEM | SYSTEM | Contact Waste Water Div department for approval prior to permit | | Waste Water Div | 1582577 |
Electrical | Original | A | 10/21/2021 | DANIELG | DANIELG | | | Electrical | 1582524 |
Electronic Plan | Original | / | 10/21/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1582503 |
Enumeration | Original | N | 10/20/2021 | BECKYA | BECKYA | | | Enumeration | 1581580 |
Resubmittal 1 | Original | / | 10/19/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1581357 |
Tri-Lakes Fire (CSFD) | Original | N | 9/8/2021 | CSFIRE | CSFIRE | Submitted By: Trimble, James Charles no fire final | csfdit | Tri-Lakes Fire (CSFD) | 1559248 |
Monument Zoning | Original | N | 8/17/2021 | TOWNOFMON | TOWNOFMON | Pikes Peak Regional Building inspection is needed. The Town of Monument zoning approval is based on the submission to Monument provided within our Cascade permitting system. If that submission differs or is changed within Pikes Peak Regional Building, we cannot be held liable for the zoning decision. | trust@tomgov.org | Monument Zoning | 1548550 |
Monument Water | Original | N | 8/17/2021 | TOWNOFMON | TOWNOFMON | Pikes Peak Regional Building inspection is needed. The Town of Monument zoning approval is based on the submission to Monument provided within our Cascade permitting system. If that submission differs or is changed within Pikes Peak Regional Building, we cannot be held liable for the zoning decision. | trust@tomgov.org | Monument Water | 1548548 |
Monument Water | Original | N | 8/17/2021 | TOWNOFMON | TOWNOFMON | Pikes Peak Regional Building inspection is needed. The Town of Monument zoning approval is based on the submission to Monument provided within our Cascade permitting system. If that submission differs or is changed within Pikes Peak Regional Building, we cannot be held liable for the zoning decision. | trust@tomgov.org | Monument Water | 1548268 |
Monument Water | Original | N | 8/17/2021 | TOWNOFMON | TOWNOFMON | Pikes Peak Regional Building inspection is needed. The Town of Monument zoning approval is based on the submission to Monument provided within our Cascade permitting system. If that submission differs or is changed within Pikes Peak Regional Building, we cannot be held liable for the zoning decision. | trust@tomgov.org | Monument Water | 1548267 |
Electrical | Original | D | 8/13/2021 | DANIELG | DANIELG | 1) List conductors between the transformer and utility meter.
2) Fault current information (SCA, SCCR, AIC) must be included, in tabular form, for all new and re-fed electrical equipment including; panel boards, switchboards, and service equipment.
3) Provide manufacturers list of series rated components for all series rated designs.
4) Please update code references. PPRBD has adopted the 2020 NEC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1547224 |
Electronic Plan | Original | / | 8/13/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1546974 |
Mechanical | Original | N | 8/11/2021 | JUSTINC | JUSTINC | No new or revised mechanical scope indicated | | Mechanical | 1545766 |
Construction | Original | N | 8/11/2021 | SHELLEY | SHELLEY | No construction work. | | Construction | 1545252 |
Enumeration | Original | D | 8/9/2021 | BECKYA | BECKYA | All plan pages show incorrect address. Update each and every page showing the correct address of the site, 1228 Baptist Road, not the lot/parcel address, 1220 Baptist Road. In the future, please go to our website and search the address to see if you have current permit history under that address. If not do a broad range of addresses for that street to confirm you are using the correct address for the project and not the address for the parcel. The address to a cell site will never be shown on the El Paso County Assessor's website.
For internal information only, location of cell site was first permitted under Sprint, T-Mobile is Sprint.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1543717 |
Electronic Plan | Original | / | 8/9/2021 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1543697 |
Waste Water Div | Original | / | 8/6/2021 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 1543267 |
Floodplain | Original | N | 8/6/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 7126001002) | | Floodplain | 1543266 |