Electrical | Original | D | 4/6/2022 | RICHG | RICHG | 1. Remove ground from service conductors.
2. Feeders from ATS to Gen panel is illegible.
3. Show compliance with 702.12 NEC.
4. Clearly identify all electrical gear - existing and new - on the overall electrical site plan.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1661461 |
Electrical | Original | D | 3/28/2022 | DANIELG | DANIELG | 1. Remove ground from service conductors.
2. Feeders from ATS to Gen panel is illegible.
3. Show compliance with 702.12 NEC.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1656044 |
Electronic Plan | Original | / | 3/28/2022 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1656009 |
Enumeration | Original | D | 3/25/2022 | BRENT | BRENT | The tax schedule number and legal description shown on the code study form are still incorrect. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1655768 |
Electronic Plan | Original | / | 3/25/2022 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1655762 |
Resubmittal 1 | Original | / | 3/25/2022 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1655532 |
Falcon Fire (CSFD) | Original | N | 10/8/2021 | CSFIRE | CSFIRE | Submitted By: Trimble, James Charles | csfdit | Falcon Fire (CSFD) | 1576031 |
Falcon Fire (CSFD) | Original | N | 9/17/2021 | CSFIRE | CSFIRE | HazMat N/A - DCT | DTillery94 | Falcon Fire (CSFD) | 1564145 |
Electrical | Original | D | 9/7/2021 | DANIELG | DANIELG | 1) Show size and voltage of utility transformer on one-line.
2) Remove parallel neutral (ground) from service conductors.
3) Provide fault current information (SCA, SCCR, AIC), in tabular form, for all new and re-fed electrical equipment including; panel boards, switchboards, service equipment, transfer equipment, and industrial control panels.
4) All information must be supplied and verified by the engineer at the time of plan submittal. Please see circled note on sheet E-601.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1558555 |
Plumbing | Original | N | 9/7/2021 | SHANEN | SHANEN | No plumbing scope of work. | | Plumbing | 1558516 |
Electronic Plan | Original | / | 9/7/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electronic Plan | 1558486 |
County Water | Original | N | 9/3/2021 | CSUREVIEW | CSUREVIEW | Not within are service territory area. | ajuvera | County Water | 1557941 |
County Waste Water | Original | N | 9/3/2021 | CSUREVIEW | CSUREVIEW | Not within are service territory area. | ajuvera | County Waste Water | 1557940 |
Mechanical | Original | N | 9/3/2021 | DALEH | DALEH | Exterior belly type Diesel Generator | | Mechanical | 1557769 |
Construction | Original | N | 9/3/2021 | MICHAELA | MICHAELA | | | Construction | 1557689 |
Electronic Plan | Original | / | 9/3/2021 | MICHAELA | MICHAELA | In Current Review by MICHAELA | | Electronic Plan | 1557687 |
Enumeration | Original | D | 9/2/2021 | BRENT | BRENT | The address for the T-Mobile installation on this tower is 4494 E. Blaney Rd. Update all plan pages and the code study form to show the correct address. The tax schedule number and legal description shown on the code study form are incorrect. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1557183 |
Electronic Plan | Original | / | 9/2/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1557158 |
Floodplain | Original | N | 8/12/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 4330000001) | | Floodplain | 1546413 |