Fountain Zoning | Original | N | 8/25/2022 | ZONINGF | ZONINGF | N/A per Dale Hoke -ME | MEstrada | Fountain Zoning | 1733708 |
Fountain Zoning | Original | / | 8/25/2022 | ZONINGF | ZONINGF | Plan re-opened | MEstrada | Fountain Zoning | 1733508 |
Zoning/Planning | Original | / | 1/14/2022 | SYSTEM | SYSTEM | Contact Zoning/Planning department for approval prior to permit | | Zoning/Planning | 1621591 |
Construction | Original | A | 1/14/2022 | SHELLEY | SHELLEY | No changes | | Construction | 1621580 |
Resubmittal 4 | Original | / | 1/12/2022 | AUSTINK | AUSTINK | Resubmittal #4 | | Resubmittal 4 | 1620436 |
Stratmoor Hills Water | Original | A | 1/11/2022 | STRATMOORWSD | STRATMOORWSD | | nancy@stratmoorhills | Stratmoor Hills Water | 1619610 |
Stratmoor Hills Waste Water | Original | A | 1/11/2022 | STRATMOORWSD | STRATMOORWSD | | nancy@stratmoorhills | Stratmoor Hills Waste Water | 1619608 |
Plan Coordinator | Original | D | 1/7/2022 | ANDREAL | ANDREAL | Disapprove all remaining departments to allow plan to be resubmitted. They need to upload the Zoning, Water and Waste Water Approvals to the ePlan. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1618618 |
Zoning/Planning | Original | / | 1/7/2022 | SYSTEM | SYSTEM | Contact Zoning/Planning department for approval prior to permit | | Zoning/Planning | 1618424 |
Waste Water Div | Original | / | 1/7/2022 | SYSTEM | SYSTEM | Contact Waste Water Div department for approval prior to permit | | Waste Water Div | 1618423 |
Water Division | Original | / | 1/7/2022 | SYSTEM | SYSTEM | Contact Water Division department for approval prior to permit | | Water Division | 1618422 |
Mechanical | Original | A | 1/7/2022 | DALEH | DALEH | | | Mechanical | 1618390 |
Fountain Fire | Original | A | 1/7/2022 | FNTNFIRE | FNTNFIRE | Nothing for FD, approved. MG | mgates | Fountain Fire | 1618288 |
Construction | Original | A | 1/3/2022 | SHELLEY | SHELLEY | | | Construction | 1615890 |
Resubmittal 3 | Original | / | 1/3/2022 | AUSTINK | AUSTINK | Resubmittal #3 | | Resubmittal 3 | 1615827 |
Fountain Fire | Original | D | 12/17/2021 | STRATMOORFIRE | STRATMOORFIRE | I Cannot Approve these plans. They must be submitted to the City of Fountain Department for Approval. Please Submit to Fountain FD Mark Stanwood Stratmoor Hills Fire 719-360-0578 | Stratmoorfd | Fountain Fire | 1610098 |
Mechanical | Original | D | 12/13/2021 | JUSTINC | JUSTINC | Same comment as last review (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1606968 |
Electronic Plan | Original | / | 12/13/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1606961 |
Construction | Original | D | 12/13/2021 | SHELLEY | SHELLEY | Structural sheets still missing (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1606918 |
Fountain Fire | Original | D | 12/8/2021 | STRATMOORFIRE | STRATMOORFIRE | Need to submit to Fountain Fire Department not Stratmoor Fire | Stratmoorfd | Fountain Fire | 1605095 |
Electrical | Original | A | 12/6/2021 | BERTHA | BERTHA | | | Electrical | 1603722 |
Electronic Plan | Original | / | 12/6/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1603693 |
Mechanical | Original | D | 12/3/2021 | JUSTINC | JUSTINC | Pending construction reviewer approval of structural pages.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1602384 |
Electronic Plan | Original | / | 12/3/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1602330 |
Construction | Original | D | 12/3/2021 | SHELLEY | SHELLEY | Structural plans are missing from resubmittal. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1602315 |
Resubmittal 2 | Original | / | 12/2/2021 | ANDREAL | ANDREAL | Resubmittal #2 | | Resubmittal 2 | 1602164 |
Fountain Fire | Original | D | 11/25/2021 | STRATMOORFIRE | STRATMOORFIRE | Need to submit these plans to the City of Fountain Fire Department for review, NOT Stratmoor Hills Fire | Stratmoorfd | Fountain Fire | 1599082 |
Electrical | Original | D | 11/12/2021 | BERTHA | BERTHA | Provide electrical plans. See the following for Electrical Plan Requirements.
https://www.pprbd.org/File/Resources/Downloads/CommercialHandout/Com%20Elect%20reqs%202020%20NEC.pdf
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1592931 |
Electronic Plan | Original | / | 11/12/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1592923 |
Mechanical | Original | D | 10/25/2021 | JUSTINC | JUSTINC | Unable to complete mechanical review.
The (M) sheets were not reuploaded for review? Relocate ALL structural pages to the structural tab when uploading and upload (M) sheets to the mechanical tab.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1583422 |
Electronic Plan | Original | / | 10/25/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1583420 |
Construction | Original | A | 10/22/2021 | SHELLEY | SHELLEY | | | Construction | 1583251 |
Resubmittal 1 | Original | / | 10/22/2021 | ANDREAL | ANDREAL | Resubmittal #1 | | Resubmittal 1 | 1583200 |
Fountain Fire | Original | D | 10/13/2021 | STRATMOORFIRE | STRATMOORFIRE | OK For SHFD - Need to submit to Fountain Fire department for review | Stratmoorfd | Fountain Fire | 1578034 |
Electrical | Original | D | 9/3/2021 | BERTHA | BERTHA | Provide electrical.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1558098 |
Electronic Plan | Original | / | 9/3/2021 | BERTHA | BERTHA | In Current Review by BERTHA | | Electronic Plan | 1558093 |
Mechanical | Original | D | 8/31/2021 | JUSTINC | JUSTINC | New AHU exceeds 300 pounds. Provide stamped letter or sheet from structural engineer.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1555597 |
Electronic Plan | Original | / | 8/31/2021 | JUSTINC | JUSTINC | In Current Review by JUSTINC | | Electronic Plan | 1555563 |
Plumbing | Original | N | 8/31/2021 | SHANEN | SHANEN | No plumbing scope of work indicated. | | Plumbing | 1555447 |
Construction | Original | D | 8/30/2021 | SHELLEY | SHELLEY | A stamped plan for modifications is required for roof to support new unit. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1555117 |
Enumeration | Original | N | 8/27/2021 | BRENT | BRENT | | | Enumeration | 1554051 |
Electronic Plan | Original | / | 8/27/2021 | BRENT | BRENT | In Current Review by BRENT | | Electronic Plan | 1554048 |
Zoning/Planning | Original | / | 8/25/2021 | SYSTEM | SYSTEM | You will need to contact Zoning/Planning department for approval prior to permit. This department will not review the plan electronically. | | Zoning/Planning | 1552547 |
Waste Water Div | Original | / | 8/25/2021 | SYSTEM | SYSTEM | You will need to contact Waste Water Div department for approval prior to permit. This department will not review the plan electronically. | | Waste Water Div | 1552546 |
Water Division | Original | / | 8/25/2021 | SYSTEM | SYSTEM | You will need to contact Water Division department for approval prior to permit. This department will not review the plan electronically. | | Water Division | 1552545 |
Floodplain | Original | N | 8/25/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6504412001) | | Floodplain | 1552544 |