Finished Bin | Original | / | 9/7/2021 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1558335 |
Plan Coordinator | Original | / | 9/3/2021 | | MPFITZSIMMONS | Location = Plan Coordinator by MPFITZSIMMONS | | Plan Coordinator | 1558276 |
CO Springs DRE | Original | N | 9/3/2021 | MPFITZSIMMONS | MPFITZSIMMONS | (see full review) | | CO Springs DRE | 1558277 |
CO Springs DRE | Original | N | 9/3/2021 | MPFITZSIMMONS | MPFITZSIMMONS | the plans will be on the finishing counter (see full review) | | CO Springs DRE | 1558275 |
Zoning/Planning | Original | / | 8/30/2021 | MPFITZSIMMONS | MPFITZSIMMONS | In Current Review by MPFITZSIMMONS | | Zoning/Planning | 1555296 |
Zoning/Planning | Original | / | 8/27/2021 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1553814 |
Plan Coordinator | Original | / | 8/27/2021 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1553812 |
Plumbing | Original | N | 8/27/2021 | SHANEN | SHANEN | No plumbing scope of work indicted. All required plumbing fixtures are existing to remain. | | Plumbing | 1553811 |
Plumbing | Original | / | 8/27/2021 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1553806 |
Plumbing | Original | / | 8/26/2021 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1553669 |
CO Springs Fire | Original | N | 8/26/2021 | CSFIRE | CSFIRE | no fire final required | rpeterson | CO Springs Fire | 1553645 |
CO Springs Hazmat | Original | N | 8/26/2021 | CSFIRE | CSFIRE | | rpeterson | CO Springs Hazmat | 1553644 |
CSU Water | Original | N | 8/26/2021 | CSUREVIEW | CSUREVIEW | No new water service outside of building. | cquinn_ds | CSU Water | 1553267 |
CSU Waste Water | Original | N | 8/26/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. | cquinn_ds | CSU Waste Water | 1553265 |
Electrical | Original | D | 8/26/2021 | DANIELG | DANIELG | 1) Conduit/conductor size, type, and quantity, beginning at the utility transformer, to include all conductors in the chain of supply for the electrical equipment in the scope of work.
2) Show location of walk in freezer and cooler disconnect.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1553249 |
Mechanical | Original | D | 8/26/2021 | TCRIPPEN | TCRIPPEN | show cooler doors, show condensate lines (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Mechanical | 1553222 |
Construction | Original | A | 8/26/2021 | GITA | GITA | per DM | | Construction | 1553178 |
Floodplain | Original | A | 8/26/2021 | BRENT | BRENT | | | Floodplain | 1553167 |
Out to Review | Original | / | 8/26/2021 | BRENT | BRENT | | | Out to Review | 1553166 |
Enumeration | Original | N | 8/26/2021 | BRENT | BRENT | | | Enumeration | 1553164 |
Floodplain | Original | / | 8/26/2021 | RBD GIS | RBD GIS | Autogenerated Review: Parcel intersects with 100 Year Floodplain. (Parcel: 6419308028) | | Floodplain | 1553161 |