Mechanical | Splice 12/21/22 | A | 12/21/2022 | JUSTINC | JUSTINC | Layout and schedule revisions | | Mechanical | 1784450 |
CO Springs Fire | Splice 12/13/22 | A | 12/14/2022 | CSFIRE | CSFIRE | Revised Isolation PACU restrooms (see full review) | Jacob.Watson | CO Springs Fire | 1781940 |
Construction | Splice 12/13/22 | A | 12/13/2022 | SHELLEY | SHELLEY | Revised isolation PACU restrooms | | Construction | 1781542 |
CO Springs Fire | Splice 11/21/22 | A | 11/22/2022 | CSFIRE | CSFIRE | | dwithee | CO Springs Fire | 1773965 |
Construction | Splice 11/21/22 | A | 11/21/2022 | SHELLEY | SHELLEY | Suite square footages and finish clarifications. | | Construction | 1773633 |
CO Springs Fire | Original | A | 3/24/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website as they contain important inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – NOTE COMMENTS ARE AVAILABLE FOR 30 DAYS! ALL PLAN APPROVALS SUBJECT TO FINAL INSPECTION! (see full review) | csfdit | CO Springs Fire | 1655137 |
Construction | Original | A | 3/16/2022 | LBENNETT | LBENNETT | | | Construction | 1651548 |
Electronic Plan | Original | / | 3/16/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1651399 |
Resubmittal 4 | Original | / | 3/16/2022 | KALLISTAJ | KALLISTAJ | Resubmittal #4 | | Resubmittal 4 | 1651353 |
CO Springs Fire | Original | D | 3/1/2022 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1643053 |
Construction | Original | D | 2/7/2022 | LBENNETT | LBENNETT | Please resubmit ensuring all sheets are legible (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1633632 |
Electronic Plan | Original | / | 2/7/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1633624 |
Resubmittal 3 | Original | / | 2/7/2022 | SHELLEY | SHELLEY | Resubmittal #3 | | Resubmittal 3 | 1632915 |
CO Springs Hazmat | Original | A | 1/26/2022 | CSFIRE | CSFIRE | You are responsible for reviewing the APPROVAL comments found on the CSFD website for any corrections to be made and/or inspection information: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp NOTE: Plan review comments may take up to an hour to be uploaded (see full review) | DTillery94 | CO Springs Hazmat | 1627772 |
CO Springs Fire | Original | D | 1/21/2022 | CSFIRE | CSFIRE | Submitted by James Trimble: You are responsible for reviewing the DISAPPROVAL comments found on the CSFD website and responding to them in your resubmittal: https://web1.coloradosprings.gov/PreventionPlanReview/FPS_WebFPS.asp
PLEASE ALLOW UP TO AN HOUR FOR COMMENTS TO LOAD TO THE SERVERS – COMMENTS ARE AVAILABLE FOR ONLY 30 DAYS! (see full review) | csfdit | CO Springs Fire | 1625112 |
Mechanical | Original | A | 1/13/2022 | JUSTINC | JUSTINC | | | Mechanical | 1621426 |
Electrical | Original | A | 1/13/2022 | SHELBY | SHELBY | | | Electrical | 1621189 |
Electronic Plan | Original | / | 1/6/2022 | SHELBY | SHELBY | In Current Review by SHELBY | | Electronic Plan | 1618029 |
Plumbing | Original | A | 1/6/2022 | SHANEN | SHANEN | Plumbing plans reviewed and released for phase 4 scope of work. | | Plumbing | 1617546 |
CO Springs DRE | Original | N | 1/4/2022 | AODOM | AODOM | Interior Remodel, no exterior work. no change of use. (see full review) | | CO Springs DRE | 1616612 |
Zoning/Planning | Original | / | 1/3/2022 | AODOM | AODOM | In Current Review by AODOM | | Zoning/Planning | 1615752 |
CSU Water | Original | N | 1/3/2022 | CSUREVIEW | CSUREVIEW | No new water service outside of building. mjg | mgackle | CSU Water | 1615714 |
CSU Waste Water | Original | N | 1/3/2022 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. mjg | mgackle | CSU Waste Water | 1615713 |
Construction | Original | D | 1/3/2022 | LBENNETT | LBENNETT | LS100.P4: Please clarify area/occupant loads as noted A101.P4: Please specify all new wall types
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1615657 |
Electronic Plan | Original | / | 1/3/2022 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1615554 |
Enumeration | Original | N | 1/3/2022 | AMY | AMY | | | Enumeration | 1615224 |
Electronic Plan | Original | / | 1/3/2022 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1615221 |
Electronic Plan | Original | / | 12/29/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1614212 |
Resubmittal 2 | Original | / | 12/29/2021 | AUSTINK | AUSTINK | Resubmittal #2 | | Resubmittal 2 | 1614004 |
Plan Coordinator | Original | D | 10/5/2021 | LBENNETT | LBENNETT | Disapprove all remaining departments to allow plan to be resubmitted (coordinated with SLE)
Please submit 1 plan containing all work for this remodel project. OK to address the phases within the plan, but the plan scope must reflect start to completion. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Plan Coordinator | 1573648 |
Enumeration | Original | D | 10/5/2021 | LBENNETT | LBENNETT | Disapprove all remaining departments to allow plan to be resubmitted (coordinated with SLE)
Please submit 1 plan containing all work for this remodel project. OK to address the phases within the plan, but the plan scope must reflect start to completion. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Enumeration | 1573647 |
Electronic Plan | Original | / | 10/5/2021 | SHANEN | SHANEN | In Current Review by SHANEN | | Electronic Plan | 1573624 |
Construction | Original | D | 10/5/2021 | LBENNETT | LBENNETT | Please submit 1 plan containing all work for this remodel project. OK to address the phases within the plan, but the plan scope must reflect start to completion.
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Construction | 1573622 |
Electronic Plan | Original | / | 10/4/2021 | LBENNETT | LBENNETT | In Current Review by LBENNETT | | Electronic Plan | 1573276 |
Enumeration | Original | N | 10/4/2021 | AMY | AMY | | | Enumeration | 1573022 |
Electronic Plan | Original | / | 10/4/2021 | AMY | AMY | In Current Review by AMY | | Electronic Plan | 1573016 |
Resubmittal 1 | Original | / | 10/4/2021 | SAVANNAHT | SAVANNAHT | Resubmittal #1 | | Resubmittal 1 | 1572799 |
Electronic Plan | Original | / | 10/4/2021 | BECKYA | BECKYA | In Current Review by BECKYA | | Electronic Plan | 1572786 |
Floodplain | Original | N | 9/1/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6235212001) | | Floodplain | 1556243 |