Scanned/Finished Bin | Original | / | 12/14/2021 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1607603 |
Plan Coordinator | Original | / | 12/14/2021 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1607524 |
Electrical | Original | A | 12/14/2021 | SHELBY | SHELBY | | | Electrical | 1607522 |
Electrical | Original | / | 12/10/2021 | SHELBY | SHELBY | In Current Review by SHELBY | | Electrical | 1606063 |
Electrical | Original | / | 12/9/2021 | | JANE | Location = Electrical by JANE | | Electrical | 1605418 |
Resubmittal 2 | Original | / | 12/9/2021 | JANE | JANE | Resubmittal #2 | | Resubmittal 2 | 1605417 |
Scanned/Finished Bin | Original | / | 10/19/2021 | | SCANNING | Location = Scanned/Finished Bin by SCANNING | | Scanned/Finished Bin | 1580782 |
Plan Coordinator | Original | / | 10/18/2021 | | SHELBY | Location = Plan Coordinator by SHELBY | | Plan Coordinator | 1580680 |
Electrical | Original | D | 10/18/2021 | SHELBY | SHELBY | Specify SCCR of RTU 1. (NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1580679 |
Electrical | Original | / | 10/13/2021 | | RITA | Location = Electrical by RITA | | Electrical | 1578150 |
Resubmittal 1 | Original | / | 10/13/2021 | RITA | RITA | Resubmittal #1 | | Resubmittal 1 | 1578149 |
Finished Bin | Original | / | 10/7/2021 | | SCANNING | Location = Finished Bin by SCANNING | | Finished Bin | 1575687 |
CSU Water | Original | N | 10/7/2021 | CSUREVIEW | CSUREVIEW | No new water service outside of building. | cquinn_ds | CSU Water | 1575673 |
CSU Waste Water | Original | N | 10/7/2021 | CSUREVIEW | CSUREVIEW | No new wastewater service outside of building. | cquinn_ds | CSU Waste Water | 1575672 |
CSU Utilities | Original | / | 10/7/2021 | | SCANNING | Location = CSU Utilities by SCANNING | | CSU Utilities | 1575320 |
Plan Coordinator | Original | / | 10/7/2021 | | SHANEN | Location = Plan Coordinator by SHANEN | | Plan Coordinator | 1575270 |
Plumbing | Original | N | 10/7/2021 | SHANEN | SHANEN | No plumbing scope of work. | | Plumbing | 1575268 |
Plumbing | Original | / | 10/7/2021 | SHANEN | SHANEN | In Current Review by SHANEN | | Plumbing | 1575262 |
Plumbing | Original | / | 10/7/2021 | | SCANNING | Location = Plumbing by SCANNING | | Plumbing | 1575243 |
CO Springs Hazmat | Original | N | 10/1/2021 | CSFIRE | CSFIRE | | dwithee | CO Springs Hazmat | 1572169 |
CO Springs Fire | Original | N | 10/1/2021 | CSFIRE | CSFIRE | no fire final | csfdit | CO Springs Fire | 1572166 |
Fire | Original | / | 9/29/2021 | | MGRABER | Location = Fire by MGRABER | | Fire | 1571121 |
CO Springs DRE | Original | N | 9/29/2021 | MGRABER | MGRABER | Interior remodel, no change of use or occupancy. Electrical/mechanical only in lower level print shop area. (see full review) | | CO Springs DRE | 1571120 |
Zoning/Planning | Original | / | 9/29/2021 | MGRABER | MGRABER | In Current Review by MGRABER | | Zoning/Planning | 1571111 |
Zoning/Planning | Original | / | 9/29/2021 | | SCANNING | Location = Zoning/Planning by SCANNING | | Zoning/Planning | 1570790 |
Plan Coordinator | Original | / | 9/29/2021 | | DALEH | Location = Plan Coordinator by DALEH | | Plan Coordinator | 1570733 |
Mechanical | Original | A | 9/29/2021 | DALEH | DALEH | | | Mechanical | 1570732 |
Mechanical | Original | / | 9/28/2021 | | SCANNING | Location = Mechanical by SCANNING | | Mechanical | 1570455 |
Plan Coordinator | Original | / | 9/28/2021 | | DANIELG | Location = Plan Coordinator by DANIELG | | Plan Coordinator | 1570384 |
Electrical | Original | D | 9/28/2021 | DANIELG | DANIELG | 1) List conductors for panel "HMPC1"
2) Fault current information (SCA, SCCR, AIC) must be included, in tabular form, for all new and re-fed air conditioning and refrigeration equipment.
3) Please clarify. Panel "LPC1" is rated for 125A with 305A of load.
4) Please clarify. 300A fuse for a 225A MLO (panel "HMP1".)
(NOTE - THE DISAPPROVAL COMMENTS ABOVE MAY NOT REPRESENT THE COMPLETE LIST OF COMMENTS. FOR ALL COMMENTS, THE DESIGNER SHALL CONDUCT A FULL EXAMINATION OF THE DISAPPROVED SET, WHICH WILL BE ACCESSIBLE UPON COMPLETION OF ALL DEPARTMENT REVIEWS. AFTER THE DESIGNER’S EXAMINATION, INDIVIDUAL REVIEWERS ARE AVAILABLE FOR DISCUSSION ON COMMENTS VIA PHONE, EMAIL, OR IN PERSON.) | | Electrical | 1570382 |
Electrical | Original | / | 9/28/2021 | DANIELG | DANIELG | In Current Review by DANIELG | | Electrical | 1570227 |
Electrical | Original | / | 9/27/2021 | | SCANNING | Location = Electrical by SCANNING | | Electrical | 1569069 |
Plan Coordinator | Original | / | 9/27/2021 | | DANM | Location = Plan Coordinator by DANM | | Plan Coordinator | 1569019 |
Construction | Original | N | 9/27/2021 | DANM | DANM | No Construction in Scope of Work | | Construction | 1569018 |
Construction | Original | / | 9/27/2021 | DANM | DANM | In Current Review by DANM | | Construction | 1568997 |
Construction | Original | / | 9/27/2021 | | SCANNING | Location = Construction by SCANNING | | Construction | 1568932 |
Construction | Original | / | 9/15/2021 | | SCANNING | Location = Construction by SCANNING | | Construction | 1562606 |
Plan Coordinator | Original | / | 9/15/2021 | | BRENT | Location = Plan Coordinator by BRENT | | Plan Coordinator | 1562600 |
Enumeration | Original | N | 9/15/2021 | BRENT | BRENT | | | Enumeration | 1562598 |
Enumeration | Original | / | 9/15/2021 | BRENT | BRENT | In Current Review by BRENT | | Enumeration | 1562591 |
Enumeration | Original | / | 9/15/2021 | BECKYA | BECKYA | In Current Review by BECKYA | | Enumeration | 1562447 |
Floodplain | Original | N | 9/15/2021 | RBD GIS | RBD GIS | Autogenerated Review: Outside 100 Year Floodplain. (Parcel: 6233201004) | | Floodplain | 1562269 |